Project Name
| Philippines Caisaka 220 MLD Water Treatment Plant Design and Build Project
|
Serial Number
| Material Name
| Specifications/Feature Description
| Code
| Execution Standard
| Unit
| Quantity
|
| | | | | | (1) |
1 | DC Screen
| 1. Name: DC Distribution Panel
2. Feature: (DC 110 110AH)
3. Dimensions: 800x600x2000 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
5.Installation Method: Floor-mounted Installation
| DC-A | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
2 | Dry-type transformer
| 1. Name: Diesel Generator Distribution Cabinet
2. Feature: (0.46KV/0.22KV, 50KVA)
3. Dimensions: 800x600x2000 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
5.Installation Method: Floor-mounted Installation
| LV-T-4100-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
3 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
4 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-02 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
5 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-03 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
6 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-04 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
7 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-05 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
8 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-06 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
9 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-07 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
10 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-08 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
11 | Modular Switchgear Cabinet
| 1. Name: 0.46V incoming line cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-007
7. Installation method: Floor-mounted installation
| LV-DP-4100-09 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
12 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
13 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-02 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
14 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-03 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
15 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-04 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
16 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-05 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
17 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-06 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
18 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation Method: Floor-mounted Installation
| LV-MCC-2200-07 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
19 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3.Dimensions: 1000x600x2200 (Width x Depth x Height)
4.Reference Diagram Number: ADD18-2053-DD-1000-E-01-061
5.Installation Method: Floor-mounted Installation
| LV-DP-2300-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
20 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3.Dimensions: 1000x600x2200 (Width x Depth x Height)
4.Reference Diagram Number: ADD18-2053-DD-1000-E-01-061
5.Installation Method: Floor-mounted Installation
| LV-DP-2300-02 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
21 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3.Dimensions: 1000x600x2200 (Width x Depth x Height)
4.Reference Diagram Number: ADD18-2053-DD-1000-E-01-061
5.Installation Method: Floor-mounted Installation
| LV-DP-2300-03 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
22 | DCS2-UPS1 Power Cabinet
| 1.Name: UPS Power Cabinet
2. Specifications: (0.46KV, 60HZ)
3.Dimensions: 1000x600x2200 (Width x Depth x Height)
4.Reference Diagram Number: ADD18-2053-DD-1000-E-01-061
5.Installation Method: Floor-mounted Installation
| DCS2-UPS1 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
23 | Dry-type transformer
| 1. Name: Feeder Cabinet
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 1000x800x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-078
5.Installation Method: Floor-mounted Installation
| LV-T-2500-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
24 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3.Dimensions: 1000x600x2200 (Width x Depth x Height)
4.Reference drawing number: ADD18-2053-DD-1000-E-01-077
5.Installation Method: Floor-mounted Installation
| LV-DP-2500-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
25 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x800x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-078
5.Installation Method: Floor-mounted Installation
| LV-MCC-2500-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
26 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x800x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-078
5.Installation Method: Floor-mounted Installation
| LV-MCC-2500-02 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
27 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x800x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-078
5.Installation Method: Floor-mounted Installation
| LV-MCC-2500-03 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
28 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x800x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-078
5.Installation Method: Floor-mounted Installation
| LV-MCC-2500-04 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
29 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x800x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-078
5.Installation Method: Floor-mounted Installation
| LV-MCC-2500-05 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
30 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3.Dimensions: 1000x600x1800 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-044
5.Installation Method: Floor-mounted Installation
| LV-DP-2600-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
31 | Dry-type transformer
| 1. Name: Feeder Cabinet
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 800x100x2200 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-046
5.Installation Method: Floor-mounted Installation
| LV-T-2600-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
32 | DCS1-UPS power cabinet
| 1. Name: DCS1-UPS
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x100x2200 (Width x Depth x Height)
4. Reference Diagram Number: ADD18-2053-DD-1000-E-01-047
5.Installation Method: Floor-mounted Installation
| DCS1-UPS | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
33 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-095
5.Installation Method: Floor-mounted Installation
| LV-DP-3300-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
34 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-095
5.Installation Method: Floor-mounted Installation
| LV-DP-3300-02 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
35 | DCS3-UPS Power Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-098
5.Installation Method: Floor-mounted Installation
| DCS3-UPS | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
36 | Dry-type transformer
| 1. Name: Feeder Cabinet
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4.Reference drawing number: ADD18-2053-DD-1000-E-01-099
5.Installation Method: Floor-mounted Installation
| LV-T-3300-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
37 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation Method: Floor-mounted Installation
| LV-MCC-3100-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
38 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation Method: Floor-mounted Installation
| LV-MCC-3100-02 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
39 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation Method: Floor-mounted Installation
| LV-MCC-3100-03 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
40 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation Method: Floor-mounted Installation
| LV-MCC-3100-04 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
41 | Modular Switchgear Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 1000x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation Method: Floor-mounted Installation
| LV-MCC-3100-05 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
42 | Dry-type transformer
| 1. Name: Feeder Cabinet
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 800x800x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-113
5.Installation Method: Floor-mounted Installation
| LV-T-5100-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
43 | Modular Switchgear Cabinet
| 1.Name: Integrated Building Power Distribution Box
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 800x800x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-113
5.Installation Method: Floor-mounted Installation
| LV-DP-5100-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
44 | Modular Switchgear Cabinet
| 1. Name: Central Control Room Power Distribution
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 800x800x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-113
5.Installation Method: Floor-mounted Installation
| LV-DP-5100-03 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
45 | Modular Switchgear Cabinet
| 1. Name: Duty Room Power Distribution
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 800x800x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-113
5.Installation Method: Floor-mounted Installation
| LV-DP-5100-04 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
46 | Server room air inlet fan switch box
| 1.Name: 1# Axial flow fan control box
2.Feature: 7.5KW
3. Size: -
4.Reference drawing number: ADD18-2053-DD-1000-E-01-004
5.Installation method: Wall-mounted installation
6.Configuration description: Fan power 7.5kw, using contactor start-stop control, equipped with thermal relay, start-stop fault light, start-stop button, equipped with universal switch for remote/local control switching, reserved DCS control dry contact
| 4100-FAN-008B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
47 | 2# Axial flow fan control box
| 1.Name: 2# Axial flow fan control box
2.Feature: 7.5KW
3. Size: -
4.Reference drawing number: ADD18-2053-DD-1000-E-01-004
5.Installation method: Wall-mounted installation
6.Configuration description: Fan power 7.5kw, using contactor start-stop control, equipped with thermal relay, start-stop fault light, start-stop button, equipped with universal switch for remote/local control switching, reserved DCS control dry contact
| 4100-FAN-007A-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
48 | Axial Flow Fan Control Box No. 3
| 1.Name: 2# Axial flow fan control box
2.Feature: 7.5KW
3. Size: -
4.Reference drawing number: ADD18-2053-DD-1000-E-01-004
5.Installation method: Wall-mounted installation
6. Configuration description: Fan motor power 7.5kw, using contactor start-stop control, equipped with thermal relay, start-stop fault light, start-stop button, universal switch for remote/local control, and reserved DCS control dry contact.
| 4100-FAN-007B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
49 | Lighting distribution box
| 1. Name: Lighting distribution box
2. Feature: Working circuit current 20A
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-017
5. Installation method: Indoor wall mounting
6. Description: Configure the distribution box circuit according to the load calculation table of reference drawing number ADD18-2053-DD-1000-E-01-017. Emergency lighting circuit uses a normal charging circuit (lights on when power is off, lights off and charging when power is on).
| LV-LPP-4100-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
50 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2.Feature: (2.0KV)
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
7.Installation Method: Wall-mounted Installation
8.Configuration Description: Function: A control box used for on-site power distribution, operation, and protection of integrated valve actuators.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 1000-MBT-001, 002, 003, 010, 011-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
51 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 0.55KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: Wall-mounted installation
6.Configuration description: Function: A control box used for power distribution, operation, and protection of integrated valve actuators on-site at the valve location.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2100-MBT-001A, 001B-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
52 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 0.37KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: -
6.Configuration description: Function: A control box used for power distribution, operation, and protection of integrated valve actuators on-site at the valve location.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2100-MBT-004, 003A, 003B-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
53 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 3KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: Wall-mounted installation
6.Configuration description: Function: A control box used for power distribution, operation, and protection of integrated valve actuators on-site at the valve location.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2100-MBT-002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 10 |
54 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2.Features: 1.5KW, 2KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: -
6.Configuration description: Function: A control box used for power distribution, operation, and protection of integrated valve actuators on-site at the valve location.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2100-MSG-003A~D, 004A~D, 005A, 006B-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
55 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 3KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: Wall-mounted installation
6.Configuration description: Function: A control box used for power distribution, operation, and protection of integrated valve actuators on-site at the valve location.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2100-MSG-001, 002-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
56 | Electric ball valve control box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: Wall-mounted installation
6.Configuration description: Function: A control box used for power distribution, operation, and protection of integrated valve actuators on-site at the valve location.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 1000-MGV-002, 009-LCP
1000-MGV-005, 006-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
57 | Sampling pump control box
| 1. Name: Sampling pump control box
2. Feature: 0.75KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: Wall-mounted installation
6. Configuration description: Function: Sampling pump control box
AC contactor start-stop, equipped with thermal protection, on-off fault lights, start-stop buttons, and a universal rotary switch.
Reserved remote start-stop contacts (relay isolation), dry contact for status feedback.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2100-SMP-001, 002-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 9 |
58 | Isolating switch box
| 1. Name: (Isolator switch box, used in conjunction with the hybrid mixer button box)
2. Feature: 0.75KW
3. Dimensions: 600*200
4. Reference drawing number: ADD18-2053-DD-1000-E-01-030
5.Installation method: Wall-mounted installation
6.Configuration Description: Built-in isolating switch
| 2200-MXR-001A~F-INS | MWC-CPM-ENGD-2015-SES-12 | 台 | 6 |
59 | Isolating switch box
| 1. Name: (Isolation Switch Box, used with the flocculation mixer button box)
2. Feature: 1.48KW
3. Dimensions: 600*200
4.Reference drawing number: ADD18-2053-DD-1000-E-01-018
5.Installation method: Wall-mounted installation
6.Configuration Description: Built-in isolating switch
| 2200-MXR-002A~004A 002~004B, 002~004C, 002~004D-INS
| MWC-CPM-ENGD-2015-SES-12 | 台 | 18 |
60 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.37KW
3.Size: 300*250*250
4.Reference drawing number: ADD18-2053-DD-1000-E-01-018
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2200-MGV-001A~F-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 6 |
61 | Sludge discharge system
Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 0.37KW
3.Size: 300*250*250
4.Reference drawing number: ADD18-2053-DD-1000-E-01-018
5. Installation Method:
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2200-MGV-002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
62 | Sludge discharge system
Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 0.37KW
3.Size: 300*250*250
4.Reference drawing number: ADD18-2053-DD-1000-E-01-018
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2200-MBT-001~002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
63 | Electric control butterfly valve control box
| 1. Name: Electric control butterfly valve control box
2. Feature: 2.0KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the electric mechanism of the valve body)
Primary circuit power supply: AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 1000-MBT-007-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
64 | Electric control butterfly valve control box
| 1. Name: Electric control butterfly valve control box
2. Feature: 2.0KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 1000-MBT-008, 009-LCP
| MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
65 | Sampling pump control box
| 1. Name: Sampling pump control box
2. Feature: 0.75KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-023
5.Installation method: -
6. Configuration description: Function: Sampling pump control box
AC contactor start-stop, equipped with on-off fault light, start-stop button, and selector switch.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2200-SMP-001~003-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
66 | Control box for electric gate valve of venting system
| 1.Name: Control box for electric gate valve of venting system
2.Feature: 2.22KW
3.Size: 300*250*250
4.Reference drawing number: ADD18-2053-DD-1000-E-01-018
5.Installation method: -
| 2200-MGV-003-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
67 | Sampling pump control box
| 1. Name: Sampling pump control box
2. Feature: 0.75KW
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-063
5.Installation method: -
6. Configuration description: Function: Sampling pump control box
AC contactor start-stop, equipped with on-off fault light, start-stop button, and selector switch.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2300-SMP-001~002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
68 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.75KW
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-063
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 1000-MBT-004~006-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
69 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.75KW
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-063
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 1000-MBT-012~013-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
70 | Load Switch
| 1. Name: Electric Hoist Control Box
2. Feature: 1.7KW
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-063
5.Installation method: -
6.Configuration Description: Built-in isolating switch
| 2300-HST-001~002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
71 | Lighting distribution box
| 1. Name: Lighting distribution box
2. Feature: Working circuit current 20A
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-063
5.Installation method: Wall-mounted installation
6. Configuration description: Refer to drawing number ADD18-2053-DD-1000-E-01-017 for load calculation table configuration of the distribution box circuit. Emergency lighting circuit uses a normal charging circuit (lights on when power is off, lights off and charging when power is on).
| LV-LPP-2300-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
72 | Electric Gate Control Box
| 1. Name: Electric valve power supply
2. Feature: 1.5KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-064
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2400-MSG-001A~D-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
73 | Electric Gate Control Box
| 1. Name: Electric valve power supply
2. Feature: 0.37KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-064
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2400-MGV-001A~D-LCP 2400-MGV-002A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 6 |
74 | Submersible pump control box
| 1. Name: Submersible pump control box
2. Feature: 0.75KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-064
5.Installation method: -
6. Configuration Instructions:
Configure the incoming circuit breaker, AC contactor for start-stop protection, thermal protection, open-stop fault light, and start-stop buttons.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2400-SMP-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
75 | Electric ball valve control box
| 1.Name: Electric Ball Valve Control Box
2. Feature: 0.75KW
3.Size: 300*250*250
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-064
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2400-MBV-001,003-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
76 | Blower Power Distribution Cabinet
| 1. Name: Feeder Cabinet
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 600x1000x1600 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5.Installation Method: Floor-mounted Installation
6. Function: Control of Roots blower
Equipped with VFD to control the blower, one controller for one device, communicating with SCADA via Profibus DP. The manufacturer should select and match the VFD according to the pump power and deepen the electrical control once or twice.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2500-ASB-001A~B-MCC | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
77 | Backwash Pump Power Distribution Cabinet
| 1. Name: Feeder Cabinet
2. Features: (0.46KV/0.23KV, 60HZ)
3. Dimensions: 600x1000x1600 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5.Installation Method: Floor-mounted Installation
6. Function: Control backwash water pump
Equipped with VFD to control the water pump, one controller for one pump, communicates with Scada via Profibus DP. The manufacturer should select and match the VFD according to the pump power and deepen the primary and secondary electrical control.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2500-CPP-001A~C-MCC | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
78 | Blower local control box
| 1. Name: Blower local control box
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5.Installation Method: Floor-mounted Installation
6. Function: Remote control box with start/stop fault lights, start/stop buttons, universal transfer switch, and corresponding terminals.
| 2500-ASB-001A~B-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
79 | Backwash Pump Control Box
| 1. Name: Backwash Pump Control Box
2. Specifications: (0.46KV, 60HZ)
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5.Installation Method: Floor-mounted Installation
6. Function: Remote control box with start/stop fault lights, start/stop buttons, universal transfer switch, and corresponding terminals.
| 2500-CPP-001A~C-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
80 | Electric Butterfly Valve Control Box
| 1.Name: Flushing Pump Room 1#, 2#, 3# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5.Installation Method: Floor-mounted Installation
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2500-MBT-001A~C-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
81 | Electric Butterfly Valve Control Box
| 1.Name: Flushing Pump Room 1#, 2#, 3# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5. Installation Method:
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2500-MBT-002A~C-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
82 | Electric Butterfly Valve Control Box
| 1.Name: Flushing Pump Room 1#, 2# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5.Installation method: -
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2500-MBT-004A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
83 | Electric Butterfly Valve Control Box
| 1. Name: Flushing Pump Room 1# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5. Installation Method:
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2500-MBT-003-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
84 | Electric Butterfly Valve Control Box
| 1. Name: Flushing Pump Room 1# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5. Installation Method:
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2500-MSG-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
85 | Electric Butterfly Valve Control Box
| 1. Name: Flushing Pump Room 1# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5. Installation Method:
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 2500-GV-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
86 | Electric Butterfly Valve Control Box
| 1. Name: Flushing Pump Room 1# Electric Butterfly Valve Control Box
2. Feature: 0.75KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5. Installation Method:
6.Configuration description: Control box for power distribution, operation, and protection of integrated valve actuators on-site at the gate.
Content: Including but not limited to: Power distribution switches, surge protectors, protective components, buttons (valve open, valve close), indicator lights (valve fully open, fully closed, valve fault), transfer switch (local box connection/automatic bus communication with valve body), primary and secondary components and accessories, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 2500-GV-002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
87 | Drain pump control box
| 1. Name: Flushing pump room drain pump control box
2. Feature: 1.35KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-084
5. Installation Method:
6. Configuration Instructions:
Configure the incoming circuit breaker, AC contactor for start-stop protection, thermal protection, open-stop fault light, and start-stop buttons.
Primary Circuit AC460V 60HZ
Secondary circuit power supply: AC110V 60HZ
Protection rating: Not less than NEMA3R
| 2500-SPP-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
88 | Load Switch
| 1. Name: Flusher Pump House Electric Hoist Metal Enclosure Switch
2. Feature: 5KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4.Reference drawing number: ADD18-2053-DD-1000-E-01-077
5. Installation Method:
| 2500-MLD-001-ES | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
89 | Lighting distribution box
| 1. Name: Lighting distribution box
2. Feature: Working circuit current 20A
3. Size: -
4.Reference drawing number: ADD18-2053-DD-1000-E-01-077
5.Installation method: Wall-mounted installation
6.Configuration description: Refer to drawing ADD18-2053-DD-1000-E-01-086 load calculation table for configuring the distribution box circuits. Emergency lighting circuits use standard charging circuits (lights turn on when power is off, lights turn off and charge when power is on).
| LV-LPP-2500-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
90 | Isolator switch
| 1.Name: Enclosed switch for electric single-girder suspended crane
2.Feature: 3.1KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4.Reference drawing number: ADD18-2053-DD-1000-E-01-055
5.Installation method: Wall-mounted installation
6.Configuration Description: Built-in isolating switch
| 2600-MLD-001-ES 2600-MLD-002-ES 2600-MLD-003-ES 2600-MLD-004-ES | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
91 | Lighting distribution box
| 1. Name: Lighting distribution box
2. Feature: Working circuit current 20A
3. Size: -
4. Reference drawing number: ADD18-2053-DD-1000-E-01-044
5.Installation method: Wall-mounted installation
6. Configuration instructions: Refer to the load calculation table in drawing ADD18-2053-DD-1000-E-01-060 for configuring the distribution box circuit. The emergency lighting circuit uses a normal charging circuit (light on when power is off, light off and charging when power is on).
| LV-LPP-2600-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
92 | Drain pump control box
| 1. Name: Self-use Pump Room Drainage Pump Control Box
2. Feature: 1.5KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-080
5. Installation Method:
| 2700-SPP-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
93 | Drain pump control box
| 1. Name: Self-use Pump Room Drainage Pump Control Box
2. Feature: 1.5KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-080
5. Installation Method:
| 2700-SPP-002-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
94 | Load Switch
| 1. Name: Self-use Pump Room Electric Hoist Iron Shell Switch
2. Feature: 5KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-080
5. Installation Method:
| 2700-MLD-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
95 | Enclosed switch
| 1. Name: Enclosed switch
2. Features: 0.46KV 5kw
3. Size: -
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation method: Wall-mounted installation
6.Configuration Description: Built-in isolating switch
| 2800-MLD-001-ES | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
96 | Isolating switch box
| 1. Name: Isolating switch
2.Features: 0.46KV, 20A, 2P
3. Size: -
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation method: Wall-mounted installation
6.Configuration Description: Built-in isolating switch
| - | MWC-CPM-ENGD-2015-SES-12 | 台 | 8 |
97 | Lighting distribution box
| 1. Name: Lighting distribution box
2. Feature: Working circuit current 20A
3. Size: -
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation method: Wall-mounted installation
6.Configuration instructions: Refer to the load calculation table in drawing ADD18-2053-DD-1000-E-01-041 for configuring the distribution box circuit. The emergency lighting circuit uses a normal charging circuit (light on when power is off, light off and charging when power is on).
| LV-LPP-2800-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
98 | Mixer Control Box
| 1. Name: Local Mixer Control Box
2.Feature: 2.2KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation method: Pole-mounted installation
6.Configuration instructions: Remote control button box, equipped with start-stop fault light, on-off buttons, and a universal switch. Built-in isolating switch; the equipment power passes through this button box.
| 3100-SMX-001A~B-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
99 | Mixer Control Box
| 1. Name: Local Mixer Control Box
2.Feature: 2.2KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6.Configuration Description: Remote control button box, equipped with start-stop fault light, open-stop button, universal transfer switch, terminal block. Built-in isolation switch, equipment power passes through this button box.
| 3100-SMX-002A~D-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
100 | Submersible sewage pump local control box
| 1.Name: Submersible sewage pump local control box
2.Feature: 10KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-088
5. Installation Method: Local installation
6.Configuration Description: Remote control button box, equipped with start-stop fault light, open-stop button, universal transfer switch, terminal block. Built-in isolation switch, equipment power passes through this button box.
| 3100-SPP-001A~D-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
101 | Submersible sewage pump local control box
| 1.Name: Submersible sewage pump local control box
2.Feature: 10KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6.Configuration Description: Remote control button box, equipped with start-stop fault light, open-stop button, universal transfer switch, terminal block. Built-in isolation switch, equipment power passes through this button box.
| 3100-SPP-002A~C-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
102 | Submersible sewage pump local control box
| 1.Name: Submersible sewage pump local control box
2.Feature: 10KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6.Configuration Description: Remote control button box, equipped with start-stop fault light, open-stop button, universal transfer switch, terminal block. Built-in isolation switch, equipment power passes through this button box.
| 3100-SPP-003A~D-LPB | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
103 | Electric Gate Control Box
| 1.Name: 1~2# Electric gate control box
2.Feature: 2.2KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 3100-MSG-001A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
104 | Electric Gate Control Box
| 1. Name: 1~4# electric gate control box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 3100-MGV-001A~D-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
105 | Electric Gate Control Box
| 1. Name: 1~4# electric gate control box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 3100-MSG-002A~C-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
106 | Electric Gate Control Box
| 1.Name: 6# Electric Gate Control Box
2.Feature: 2.2KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body)
| 3100-MSG-006-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
107 | Electric Gate Control Box
| 1.Name: 1~3# Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MGV-002A~C-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
108 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MSG-003A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
109 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MGV-003A~D-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
110 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MGV-004A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
111 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MSG-004A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
112 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MSG-005A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
113 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MGV-005A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
114 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MBV-001A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
115 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MBV-002~3-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
116 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: 0.55KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3100-MGV-002A~C-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
117 | Load switch box
| 1. Name: 1# Electric Hoist Metal Enclosure Switch
2. Feature: 3.4KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6.Configuration Description: Built-in load switch
| 3100-HST-001-ES | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
118 | Load switch box
| 1.Name: 2# Electric Hoist Iron Shell Switch
2. Feature: 3.4KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5. Installation Method: Local installation
6.Configuration Description: Built-in load switch
| 3100-HST-002-ES | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
119 | Isolating switch box
| 1.Name: Isolation Switch Box
2. Feature: 3.4KW
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-087
5.Installation method: -
6.Configuration Description: Built-in load switch
| | MWC-CPM-ENGD-2015-SES-12 | 台 | 23 |
120 | Electric Gate Control Box
| 1. Name: Electric Gate Control Box
2. Feature: -
3. Dimensions: 300*250*250 (Width x Depth x Height)
4. Reference drawing number: ADD18-2053-DD-1000-E-01-108
5. Installation Method: Local installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3200-MSG-001-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
121 | Electric gate valve control box
| 1.Name: Electric gate valve control box
2. Feature: -
3. Dimensions: 800x1000x2200 (Width x Depth x Height)
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-098
5.Installation method: Bracket installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3200-MGV-003A~B-LCP 3200-MGV-004A~D-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 6 |
122 | Electric gate valve control box
| 1.Name: Electric gate valve control box
2. Feature: -
3. Size: -
3.Reference drawing number: ADD18-2053-DD-1000-E-01-099
5.Installation method: Bracket installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3200-MGV-001A~B-LCP 3200-MGV-002A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
123 | Electric Butterfly Valve Control Box
| 1.Name: Electric Butterfly Valve Control Box
2. Feature: 0.55KW
3. Size: -
3.Reference drawing number: ADD18-2053-DD-1000-E-01-099
5.Installation method: Bracket installation
6. Configuration Description: Distribution switches, surge protectors, protective components, buttons (valve open, close), indicator lights (valve fully open, fully closed, valve fault), transfer switches (local box/manual, valve body connection via automatic bus communication), primary and secondary components, accessories, auxiliary materials, and all mounting brackets and auxiliary materials.
(Remote control button box for electric valves and gates, dry contact I/O connected to the valve body.)
| 3200-MBT-001A~D-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
124 | Mixer Control Box
| 1. Name: Mixer Control Box
2.Feature: 7.5KW
3.Size: 300*250*250
3.Reference drawing number: ADD18-2053-DD-1000-E-01-099
5.Installation method: Bracket installation
6.Configuration Description: Remote control button box, equipped with start-stop fault light, open-stop button, universal transfer switch, terminal block. Built-in isolation switch, equipment power passes through this button box.
| 3200-MXR-001A~B-LCP | MWC-CPM-ENGD-2015-SES-12 | 台 | 2 |
125 | Load switch box
| 1. Name: Electric Single-Girder Bridge Crane Switch Box
2. Feature: (HH10-30/3P 6.732KW)
3. Size: -
4. Reference Drawing Number: ADD18-2053-DD-1000-E-01-095
5.Installation method: Wall-mounted installation
| 3300-MLD-001~004-ES | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
126 | Lighting distribution box
| 1. Name: Lighting distribution box
2. Feature: Working circuit current 20A
3. Size: -
4.Reference Drawing Number: ADD18-2053-DD-1000-E-01-038
5.Installation method: Wall-mounted installation
6. Configuration instructions: Refer to the drawing ADD18-2053-DD-1000-E-01-105 Load Calculation Table for configuring the distribution box circuit. Emergency lighting circuits use a standard charging circuit (lights turn on when power is off, and turn off to charge when power is on).
| LV-LPP-3300-01 | MWC-CPM-ENGD-2015-SES-12 | 台 | 1 |
127 | Lighting distribution box (lighting)
| 1. Name: Lighting distribution box
2. Feature: -
3. Size: 400*250*150
4. Reference drawing number: ADD18-2053-DD-1000-E-01-138
5.Installation method: Wall-mounted installation
| LV-DP-5100-01A~C | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
128 | Lighting distribution box (socket)
| 1. Name: Lighting distribution box
2. Feature: -
3. Size: 400*250*150
4. Reference drawing number: ADD18-2053-DD-1000-E-01-138
5.Installation method: Wall-mounted installation
| LV-LPP-5100-02A~C | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
129 | Lighting distribution box (Air conditioning)
| 1. Name: Lighting distribution box
2. Feature: -
3. Size: 400*250*150
4. Reference drawing number: ADD18-2053-DD-1000-E-01-138
5.Installation method: Wall-mounted installation
| LV-LPP-5100-03A~D | MWC-CPM-ENGD-2015-SES-12 | 台 | 4 |
130 | Emergency lighting centralized power supply(Type A)
| 1. Name: Lighting distribution box
2. Feature: -
3. Size: 400*250*150
4. Reference drawing number: ADD18-2053-DD-1000-E-01-138
5.Installation method: Wall-mounted installation
| LV-DP-5100-02A~C | MWC-CPM-ENGD-2015-SES-12 | 台 | 3 |
131 | ISOLATOR Isolating switch box
| 20A 2P IP66 | | MWC-CPM-ENGD-2015-SES-12 | Suit/Unit
| 45 |
132 | ISOLATOR Isolating switch box
| 20A 2P IP66 | | MWC-CPM-ENGD-2015-SES-12 | Suit/Unit
| 2 |
133 | Electric door control box Electric door control box
| Equipment support
Equipment 配套
| | MWC-CPM-ENGD-2015-SES-12 | Suit/Unit
| 1 |
134 | Lighting distribution box
| XM(H)R-04 | LV-LPP-5200-01 | MWC-CPM-ENGD-2015-SES-12 | Suit/Unit
| 1 |
135 | AC Charging Pile Factory AC charging pile
| ≥IP54(NAME3R) ~230V, 60HZ, 7KW
| LV-CP-01~03 | MWC-CPM-ENGD-2015-SES-12 | Suit/Unit
| 3 |
136 | Factory sewage electric valve control box Factory sewage electric valve control box
| ≥IP54(NAME3R) provided by Valve Brought by the matching valve
| 1000-MGV-018-LCP 1000-MGV-017-LCP | MWC-CPM-ENGD-2015-SES-12 | Suit/Unit
| 2 |