2. 精密空调(风冷)厂验测试项目
2. Precision air conditioning (air-cooled) factory inspection test items
2.1. 外观检查
2.1. Visual inspection
1. 依据确认过的设备生产结构图确认设备外观尺寸、颜色、冷凝水排水接管位置、配电接线位置、出风 方式、冷媒管接管规格等符合设计要求;
1. According to the confirmed equipment production structure drawing, confirm that the appearance size, color, condensate drainage pipe location, distribution wiring location, air outlet mode, refrigerant pipe pipe pipe specification, etc. meet the design requirements;
2. 表面、丝印、标识:检查产品无明显凹痕、划伤、裂隙、变形、脏污、色差。标识内容和位置正确, 符合公司产品外观检验标准。
2. Surface, silk screen printing, identification: check that the product has no obvious dents, scratches, cracks, deformation, dirt, and color difference. The content and position of the logo are correct, in line with the company's product appearance inspection standards.
3. 结构件:各结构件外观良好,连接良好,各活动门开关正常符合工艺文件要求;
3. Structural parts: each structural part has a good appearance and good connection, and the movable door switch normally meets the requirements of the process documents;
4. 配线工艺:各连接电缆连接紧固,走线符合工艺要求。
4. Wiring process: each connecting cable is connected and fastened, and the wiring meets the process requirements.
2.2. 器件核对
2.2. Device checking
重要器件配置检验依据各个品牌配置清单进行核对,各部件的品牌型号、数量必须与对应的配置单、 招标要求一致。
The configuration inspection of important components is checked according to the configuration list of each brand, and the brand, model and quantity of each component must be consistent with the corresponding configuration list and bidding requirements.
2.3. 机组测试
2.3. Unit testing
2.3.1.测试环境检查
2.3.1. Test environment check
1. 检查风机风道确保内无异物,风机无擦轮现象
1. Check the air duct of the fan to ensure that there is no foreign matter in the fan and that there is no wiping wheel phenomenon in the fan
2. 检查空调的风机入风口需有防护网;
2. Check that the fan inlet of the air conditioner needs to have a protective net;
3. 检查实验室的空调出风的风量传感器是否正常;
3. Check whether the air volume sensor of the air conditioner outlet in the laboratory is normal;
4. 检查实验室干球温度和湿球温度表是否按照正确方式安装;
4. Check whether the dry-bulb temperature and wet-bulb thermometers in the laboratory are installed in the correct way;