TYPE FLS CATEGORY FLS 类别 NEW BRAND STANDARD. SPECIFICATION
新品牌标准。规格
Standard 标准 Accessible room safety features
无障碍房间安全设施
Accessible Rooms must provide a means of occupants raising alarm to summon assistance in case of emergency.
无障碍房间必须提供在紧急情况下住户报警求助的方式。
Specification 规格 Accessible room safety features
无障碍房间安全设施
Accessible Rooms must have a distress alarm located at the bed head and in the bathroom which is linked to a permanently staffed
无障碍客房必须在床头和浴室安装求救警报器,该警报器与长期有人值守的
Specification 规格 Accessible room safety 无障碍房间的安全 All distress alarms must connect to an on-site location that is
所有遇险警报都必须连接到现场的一个位置,该位置必须是
Specification 规格 Accessible room safety features
无障碍房间安全设施
Accessible Rooms are required to be equipped with an emergency communication system or a telephone that is readily
无障碍房间必须配备紧急通信系统或电话,以便在紧急情况下使用。
Standard 标准 Slip risk 滑倒风险 Guest bathrooms must have anti-slip measures that reduce slip
客房浴室必须有防滑措施,以减少滑倒
Specification 规格 Slip risk 滑倒风险 Hotels must implement one of the following anti-slip measures in all bathtubs; a slip resistant bathtub, a slip resistant impervious
酒店必须在所有浴缸中采取以下防滑措施之一:防滑浴缸、防滑不透水浴缸、防滑浴缸、防滑不透水浴缸、防滑不透水浴缸、防滑不透水浴缸、防滑不透水浴缸。
Specification 规格 Slip risk 滑倒风险 Showers and bathroom floors must have a Slip Resistant finish.
淋浴间和浴室的地面必须有防滑涂层。
Standard 标准 Baby cot/crib safety 婴儿床/婴儿床安全 Baby cots/cribs must have measures or features for addressing
婴儿床/婴儿床必须有解决以下问题的措施或功能
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 Bars must be no less than 2.5 cm (1in) and no more than 6 cm ( 23 / 8 6 cm ( 23 / 8 6cm(23//86 \mathrm{~cm}(23 / 8
横杆不得小于 2.5 厘米(1 英寸),不得大于 6 cm ( 23 / 8 6 cm ( 23 / 8 6cm(23//86 \mathrm{~cm}(23 / 8 .
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 Drop down rail locking mechanism must be unreachable by the
下拉式导轨锁定装置必须无法触及
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 No corner posts extensions, steps, footholds or decorative cutouts
无角柱延伸、台阶、支脚或装饰性切口
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 No removable plastic coverings
无可拆卸塑料外罩
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 No rotating hinge in the centre of the top rails and top rail
顶轨和顶轨中央无旋转铰链
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 Self-locking feature on folding cots / cribs
折叠床/婴儿床的自锁功能
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 Snug fitting mattress 舒适的床垫
Specification 规格 Baby cot/crib safety 婴儿床/婴儿床安全 The mesh weave must be less than 6 mm ( 1 / 4 in 1 / 4 in 1//4in1 / 4 \mathrm{in} )
网眼编织必须小于 6 毫米 ( 1 / 4 in 1 / 4 in 1//4in1 / 4 \mathrm{in} )
Standard 标准 Fall from height risk 高空坠落风险 Balconies, balustrades or similar, must have measures for managing the risk of falling, particularly considering children or
阳台、栏杆或类似设施必须有控制坠落风险的措施,特别是考虑到儿童或青少年的安全。
Specification 规格 Fall from height risk 高空坠落风险 Barriers to the fall risk must be at least 1.1 m (3ft 6 in ) high, with all
防止坠落风险的障碍物必须至少有 1.1 米(3 英尺 6 英寸)高,并且所有
Specification 规格 Fall from height risk 高空坠落风险 Barriers to the fall risk must be at least 0.9 m (2ft 9 in ) high, with all
防止坠落风险的障碍物必须至少有 0.9 米(2 英尺 9 英寸)高,且所有
Specification 规格 Fall from height risk 高空坠落风险 Barriers must be Non-Climbable.
障碍物必须是不可攀爬的。
Specification 规格 Fall from height risk 高空坠落风险 Doors that open onto a balcony area must have a secondary device fitted to limit the initial opening of the balcony door.
通向阳台的门必须安装辅助装置,以限制阳台门的首次开启。
Specification 规格 Fall from height risk 高空坠落风险 Where secondary door locks are Prohibited - a sign, in the local language(s) and English, posted on the balcony door providing a
在禁止使用辅助门锁的情况下 - 在阳台门上张贴用当地语言和英语书写的标牌,以提供以下信息
Specification 规格 Fall from height risk 高空坠落风险 For existing balcony constructions with no permanent barrier to prevent risk of falling - where secondary door locks are Prohibited - a sign, in the local language(s) and English, posted on the
对于没有防止坠落风险的永久性屏障的现有阳台建筑,在禁止使用辅助门锁的情况下,应在阳台上张贴用当地语言和英语书写的标志。
Guideline 指导原则 Fall from height risk 高空坠落风险 An example of a warning sign is 'Attention! The balcony door in this room can open fully and guests with young children should
例如,"请注意!此房间的阳台门可以完全打开,带小孩的客人应
It is recommended that secondary locking device on doors
建议在门上安装辅助锁定装置
uidelin Fall from height risk 高空坠落风险 opening onto balconies should be located at a minimum height of
阳台的最低高度应为
Standard 标准 Fall from height risk 高空坠落风险 Measures must be implemented to manage the risk of falling from
必须采取措施管理从以下地点坠落的风险
Specification 规格 Fall from height risk 高空坠落风险 Where there is a fall from height risk; window opening should be
如果存在从高处坠落的风险,开窗时应
Specification 规格 Fall from height risk 高空坠落风险 Where window stops are Prohibited, a warning sign in the local language(s) and English must be mounted on or near the window.
在禁止使用窗挡的地方,必须在窗户上或附近安装用当地语言和英语书写的警告牌。
Guideline 指导原则 Fall from height risk 高空坠落风险 An example of a warning sign is 'Attention! The windows in this room can open fully and guests with young children should
例如,"请注意!此房间的窗户可以完全打开,带小孩的客人应
Life Safety Systems and 生命安全系统和 Detection and alarm systems must provide prompt warning in
探测和警报系统必须在下列情况下及时发出警报
Standard 标准 Equipment 设备 case of carbon monoxide accumulation/leakage to enable
一氧化碳积聚/泄漏的情况,以便能够
Specification 规格 Life Safety Systems and Equipment
生命安全系统和设备
Carbon monoxide detectors must be supervised by the fire alarm panel, and incorporated a local sounding alarm.
一氧化碳探测器必须由火警面板监控,并配有本地警报器。
Specification 规格 Life Safety Systems and Equipment
生命安全系统和设备
Carbon monoxide detectors are permitted to be single or multiple station (interconnected), incorporating a local sounding alarm.
一氧化碳探测器可以是单站或多站(相互连接)的,并配有本地警报器。
Specification 规格 Life Safety Systems and Equipment
生命安全系统和设备
Carbon monoxide detectors must be installed in rooms where there is a Fuel Burning Appliance.
有燃料燃烧设备的房间必须安装一氧化碳探测器。
Life Safety Systems and 生命安全系统和 Carbon monoxide detectors must be installed in each room,
每个房间都必须安装一氧化碳探测器、
Specification 规格 Equipment 设备 corridor, or area adjacent to a room where there is a Fuel Burning
走廊,或与有燃料燃烧装置的房间相邻的区域
Standard 标准 Life Safety Systems and Equipment
生命安全系统和设备
Life Safety Systems must be installed, commissioned, tested and maintained by a Qualified Person in accordance with
生命安全系统必须由合格人员按照以下规定进行安装、调试、测试和维护
Standard 标准 Passenger lift safety 乘客电梯安全 Passenger lifts must include features which manage the risk of entrapment, - including in case of hotel fire - mitigating associated
乘客电梯必须具有管理被困风险的功能,包括在酒店发生火灾的情况下,减轻相关风险。
TYPE FLS CATEGORY NEW BRAND STANDARD. SPECIFICATION Standard Accessible room safety features Accessible Rooms must provide a means of occupants raising alarm to summon assistance in case of emergency. Specification Accessible room safety features Accessible Rooms must have a distress alarm located at the bed head and in the bathroom which is linked to a permanently staffed Specification Accessible room safety All distress alarms must connect to an on-site location that is Specification Accessible room safety features Accessible Rooms are required to be equipped with an emergency communication system or a telephone that is readily Standard Slip risk Guest bathrooms must have anti-slip measures that reduce slip Specification Slip risk Hotels must implement one of the following anti-slip measures in all bathtubs; a slip resistant bathtub, a slip resistant impervious Specification Slip risk Showers and bathroom floors must have a Slip Resistant finish. Standard Baby cot/crib safety Baby cots/cribs must have measures or features for addressing Specification Baby cot/crib safety Bars must be no less than 2.5 cm (1in) and no more than 6cm(23//8 Specification Baby cot/crib safety Drop down rail locking mechanism must be unreachable by the Specification Baby cot/crib safety No corner posts extensions, steps, footholds or decorative cutouts Specification Baby cot/crib safety No removable plastic coverings Specification Baby cot/crib safety No rotating hinge in the centre of the top rails and top rail Specification Baby cot/crib safety Self-locking feature on folding cots / cribs Specification Baby cot/crib safety Snug fitting mattress Specification Baby cot/crib safety The mesh weave must be less than 6 mm ( 1//4in ) Standard Fall from height risk Balconies, balustrades or similar, must have measures for managing the risk of falling, particularly considering children or Specification Fall from height risk Barriers to the fall risk must be at least 1.1 m (3ft 6 in ) high, with all Specification Fall from height risk Barriers to the fall risk must be at least 0.9 m (2ft 9 in ) high, with all Specification Fall from height risk Barriers must be Non-Climbable. Specification Fall from height risk Doors that open onto a balcony area must have a secondary device fitted to limit the initial opening of the balcony door. Specification Fall from height risk Where secondary door locks are Prohibited - a sign, in the local language(s) and English, posted on the balcony door providing a Specification Fall from height risk For existing balcony constructions with no permanent barrier to prevent risk of falling - where secondary door locks are Prohibited - a sign, in the local language(s) and English, posted on the Guideline Fall from height risk An example of a warning sign is 'Attention! The balcony door in this room can open fully and guests with young children should It is recommended that secondary locking device on doors uidelin Fall from height risk opening onto balconies should be located at a minimum height of Standard Fall from height risk Measures must be implemented to manage the risk of falling from Specification Fall from height risk Where there is a fall from height risk; window opening should be Specification Fall from height risk Where window stops are Prohibited, a warning sign in the local language(s) and English must be mounted on or near the window. Guideline Fall from height risk An example of a warning sign is 'Attention! The windows in this room can open fully and guests with young children should Life Safety Systems and Detection and alarm systems must provide prompt warning in Standard Equipment case of carbon monoxide accumulation/leakage to enable Specification Life Safety Systems and Equipment Carbon monoxide detectors must be supervised by the fire alarm panel, and incorporated a local sounding alarm. Specification Life Safety Systems and Equipment Carbon monoxide detectors are permitted to be single or multiple station (interconnected), incorporating a local sounding alarm. Specification Life Safety Systems and Equipment Carbon monoxide detectors must be installed in rooms where there is a Fuel Burning Appliance. Life Safety Systems and Carbon monoxide detectors must be installed in each room, Specification Equipment corridor, or area adjacent to a room where there is a Fuel Burning Standard Life Safety Systems and Equipment Life Safety Systems must be installed, commissioned, tested and maintained by a Qualified Person in accordance with Standard Passenger lift safety Passenger lifts must include features which manage the risk of entrapment, - including in case of hotel fire - mitigating associated| TYPE | FLS CATEGORY | NEW BRAND STANDARD. SPECIFICATION | | :---: | :---: | :---: | | Standard | Accessible room safety features | Accessible Rooms must provide a means of occupants raising alarm to summon assistance in case of emergency. | | Specification | Accessible room safety features | Accessible Rooms must have a distress alarm located at the bed head and in the bathroom which is linked to a permanently staffed | | Specification | Accessible room safety | All distress alarms must connect to an on-site location that is | | Specification | Accessible room safety features | Accessible Rooms are required to be equipped with an emergency communication system or a telephone that is readily | | Standard | Slip risk | Guest bathrooms must have anti-slip measures that reduce slip | | Specification | Slip risk | Hotels must implement one of the following anti-slip measures in all bathtubs; a slip resistant bathtub, a slip resistant impervious | | Specification | Slip risk | Showers and bathroom floors must have a Slip Resistant finish. | | Standard | Baby cot/crib safety | Baby cots/cribs must have measures or features for addressing | | Specification | Baby cot/crib safety | Bars must be no less than 2.5 cm (1in) and no more than $6 \mathrm{~cm}(23 / 8$ | | Specification | Baby cot/crib safety | Drop down rail locking mechanism must be unreachable by the | | Specification | Baby cot/crib safety | No corner posts extensions, steps, footholds or decorative cutouts | | Specification | Baby cot/crib safety | No removable plastic coverings | | Specification | Baby cot/crib safety | No rotating hinge in the centre of the top rails and top rail | | Specification | Baby cot/crib safety | Self-locking feature on folding cots / cribs | | Specification | Baby cot/crib safety | Snug fitting mattress | | Specification | Baby cot/crib safety | The mesh weave must be less than 6 mm ( $1 / 4 \mathrm{in}$ ) | | Standard | Fall from height risk | Balconies, balustrades or similar, must have measures for managing the risk of falling, particularly considering children or | | Specification | Fall from height risk | Barriers to the fall risk must be at least 1.1 m (3ft 6 in ) high, with all | | Specification | Fall from height risk | Barriers to the fall risk must be at least 0.9 m (2ft 9 in ) high, with all | | Specification | Fall from height risk | Barriers must be Non-Climbable. | | Specification | Fall from height risk | Doors that open onto a balcony area must have a secondary device fitted to limit the initial opening of the balcony door. | | Specification | Fall from height risk | Where secondary door locks are Prohibited - a sign, in the local language(s) and English, posted on the balcony door providing a | | Specification | Fall from height risk | For existing balcony constructions with no permanent barrier to prevent risk of falling - where secondary door locks are Prohibited - a sign, in the local language(s) and English, posted on the | | Guideline | Fall from height risk | An example of a warning sign is 'Attention! The balcony door in this room can open fully and guests with young children should | | | | It is recommended that secondary locking device on doors | | uidelin | Fall from height risk | opening onto balconies should be located at a minimum height of | | Standard | Fall from height risk | Measures must be implemented to manage the risk of falling from | | Specification | Fall from height risk | Where there is a fall from height risk; window opening should be | | Specification | Fall from height risk | Where window stops are Prohibited, a warning sign in the local language(s) and English must be mounted on or near the window. | | Guideline | Fall from height risk | An example of a warning sign is 'Attention! The windows in this room can open fully and guests with young children should | | | Life Safety Systems and | Detection and alarm systems must provide prompt warning in | | Standard | Equipment | case of carbon monoxide accumulation/leakage to enable | | Specification | Life Safety Systems and Equipment | Carbon monoxide detectors must be supervised by the fire alarm panel, and incorporated a local sounding alarm. | | Specification | Life Safety Systems and Equipment | Carbon monoxide detectors are permitted to be single or multiple station (interconnected), incorporating a local sounding alarm. | | Specification | Life Safety Systems and Equipment | Carbon monoxide detectors must be installed in rooms where there is a Fuel Burning Appliance. | | | Life Safety Systems and | Carbon monoxide detectors must be installed in each room, | | Specification | Equipment | corridor, or area adjacent to a room where there is a Fuel Burning | | Standard | Life Safety Systems and Equipment | Life Safety Systems must be installed, commissioned, tested and maintained by a Qualified Person in accordance with | | Standard | Passenger lift safety | Passenger lifts must include features which manage the risk of entrapment, - including in case of hotel fire - mitigating associated |
Specification 规格 Passenger lift safety 乘客电梯安全 In the event of a fire alarm being activated, lifts must automatically go to the Designated Floor Level and doors must open
如果火警警报响起,电梯必须自动升至指定楼层,门必须打开
Specification 规格 Passenger lift safety 乘客电梯安全 A sign must be provided adjacent to the call button(s) in lift lobbies that gives a clear warning against the use of lifts in the event of
必须在电梯厅呼叫按钮旁设置标志,明确警告在下列情况下不得使用电梯
Specification 规格 Passenger lift safety 乘客电梯安全 Lifts must be provided with an alternative power supply which must be available immediately in the event of the normal power
必须为升降机提供备用电源,一旦正常供电中断,备用电源必须立即可用。
Specification 规格 Passenger lift safety 乘客电梯安全 If the lift is not provided with an alternative power supply a contract must be in place with a lift maintenance company to
如果升降机没有提供替代电源,则必须与升降机维护公司签订合同,以便
Specification 规格 Passenger lift safety 乘客电梯安全 Emergency lighting must be provided in the lift car.
电梯轿厢内必须配备应急照明。
Specification 规格 Passenger lift safety 乘客电梯安全 Each lift is required to have a house telephone or intercom which connects directly to a permanently staffed location.
每部电梯都必须安装室内电话或对讲机,直接连接到长期有人值守的地点。
Guideline 指导原则 Passenger lift safety 乘客电梯安全 A permanently staffed location includes a lift maintenance company with a facility to deal with emergencies 24 hours, seven
一个长期配备人员的地点包括一家电梯维护公司,该公司拥有 24 小时全天候处理紧急情况的设施。
Standard 标准 trical sa  Electrical appliances/outlets that may become exposed to water must include safety measures to address the risk of electrocution.
可能会接触到水的电器/插座必须包括安全措施,以应对触电风险。
Specification 规格 Electrical safety 电气安全 Electrical outlets or appliances that are connected to electrical outlets Adjacent to Sources of Water or in areas that may be exposed to weather must be protected by Ground Fault Circuit
与电源插座相连的电源插座或电器毗邻水源或位于可能暴露在天气中的区域,必须使用接地故障电路保护。
Standard 标准 Water hygiene 水卫生 The property must ensure a Water Quality Assessment is conducted by a Qualified Person to identify and manage the risk
物业必须确保由合格人员进行水质评估,以确定和管理风险
Specification 规格 Water hygiene 用水卫生 A documented Water Safety Management Plan outlining measures to ensure water remains safe must be implemented in
必须在以下地点实施记录在案的水安全管理计划,概述确保水安全的措施
Specification 规格 Water hygiene 水卫生 Water Quality Assessment(s) must be reviewed at least every two
水质评估必须至少每两年审查一次。
The hotel's Food Safety Management system must be evaluated
必须对酒店的食品安全管理系统进行评估
Standard 标准 Food hygiene 食品卫生 by a Qualified Person on a recurring basis, providing independent
由合格人员定期进行,提供独立的
Specification 规格 Food hygiene 食品卫生 months for properties: undertaking cook / chill, sous vide, outdoor catering, large-sized Buffet and Banqueting Operations and
个月的物业:承办烹饪/冷藏、苏式烹调、室外餐饮、大型自助餐和宴会业务,以及
Specification 规格 Food hygiene 食品卫生 Independent evaluation must be completed at least once every 18 months for properties: preparing/cooking raw foods for immediate
必须至少每 18 个月完成一次独立评估,评估内容包括:准备/烹饪生鲜食品,以便立即食用
Specification 规格 Food hygiene 食品卫生 Independent evaluation must be completed at least once every 24 months for properties: warming of pre-prepared meals for
必须至少每 24 个月完成一次独立评估,评估内容包括:预制膳食的保暖,以备不时之需。
Specification 规格 Food hygiene 食品卫生 The Qualified Person must be independent from the organisation
合格人员必须独立于组织之外
Standard 标准 Food hygiene 食品卫生 The hotel must establish a food safety management system to mitigate risks associated with food borne illness, contamination
酒店必须建立食品安全管理系统,以降低与食源性疾病、污染相关的风险
Specification 规格 Food hygiene 食品卫生 Food satety management systems must be based on the principles of Hazard Analysis & Critical Control Points (HACCP) or Hazard Analysis & Risk-Based Preventive Controls (HARCP),
食品安全管理系统必须以危害分析和关键控制点(HACCP)或危害分析和基于风险的预防控制(HARCP)原则为基础、
Standard 标准 Access and key control 门禁和钥匙控制 Hotel access controls must manage the potential of unauthorised individuals from gaining access to guest room corridors, and Back of House Areas, from Public Areas, including car parks and
酒店门禁系统必须管理未经授权人员从公共区域(包括停车场和停车场)进入客房走廊和后厨区域的可能性。
Specification 规格 Access and key control 门禁和钥匙控制 Access control is required at all doors and lifts used by guests from public access areas, including car park and basement, into
客人从停车场和地下室等公共入口进入的所有门和电梯都必须安装门禁系统。
Specification 规格 Access and key control 门禁和钥匙控制 Access control is required at all doors and lifts used by employees from public access areas, including car park and basement, into Back of House Areas
员工从停车场和地下室等公共入口进入后厨区的所有门和电梯都必须安装门禁系统
Guideline 指导原则 Access and key control 门禁和钥匙控制 that is monitored 24 hours a day, seven days a week combined with key card access control in lift car controlling access to the guest floors, or key card access control fitted to all doors leading from all basement car park levels towards the lift lobbies or access point(s) from basement car parking levels towards the lift lobbies, or permanently staffed by Hotel Security or the lift stopping and
每周 7 天、每天 24 小时受到监控,并在电梯轿厢内安装钥匙卡门禁系统,以控制客人楼层的进出,或在地下室停车场各层通往电梯厅的所有门上安装钥匙卡门禁系统,或在地下室停车场各层通往电梯厅的出入口安装钥匙卡门禁系统,或由酒店保安人员或电梯停靠人员长期值守,以及
Standard 标准 Guest and building security
访客和建筑安全
to address the risk of criminal activities (e.g. hostile surveillance, theft, arson, assault).
应对犯罪活动的风险(如恶意监视、盗窃、纵火、袭击)。
Specification Passenger lift safety In the event of a fire alarm being activated, lifts must automatically go to the Designated Floor Level and doors must open Specification Passenger lift safety A sign must be provided adjacent to the call button(s) in lift lobbies that gives a clear warning against the use of lifts in the event of Specification Passenger lift safety Lifts must be provided with an alternative power supply which must be available immediately in the event of the normal power Specification Passenger lift safety If the lift is not provided with an alternative power supply a contract must be in place with a lift maintenance company to Specification Passenger lift safety Emergency lighting must be provided in the lift car. Specification Passenger lift safety Each lift is required to have a house telephone or intercom which connects directly to a permanently staffed location. Guideline Passenger lift safety A permanently staffed location includes a lift maintenance company with a facility to deal with emergencies 24 hours, seven Standard trical sa Electrical appliances/outlets that may become exposed to water must include safety measures to address the risk of electrocution. Specification Electrical safety Electrical outlets or appliances that are connected to electrical outlets Adjacent to Sources of Water or in areas that may be exposed to weather must be protected by Ground Fault Circuit Standard Water hygiene The property must ensure a Water Quality Assessment is conducted by a Qualified Person to identify and manage the risk Specification Water hygiene A documented Water Safety Management Plan outlining measures to ensure water remains safe must be implemented in Specification Water hygiene Water Quality Assessment(s) must be reviewed at least every two The hotel's Food Safety Management system must be evaluated Standard Food hygiene by a Qualified Person on a recurring basis, providing independent Specification Food hygiene months for properties: undertaking cook / chill, sous vide, outdoor catering, large-sized Buffet and Banqueting Operations and Specification Food hygiene Independent evaluation must be completed at least once every 18 months for properties: preparing/cooking raw foods for immediate Specification Food hygiene Independent evaluation must be completed at least once every 24 months for properties: warming of pre-prepared meals for Specification Food hygiene The Qualified Person must be independent from the organisation Standard Food hygiene The hotel must establish a food safety management system to mitigate risks associated with food borne illness, contamination Specification Food hygiene Food satety management systems must be based on the principles of Hazard Analysis & Critical Control Points (HACCP) or Hazard Analysis & Risk-Based Preventive Controls (HARCP), Standard Access and key control Hotel access controls must manage the potential of unauthorised individuals from gaining access to guest room corridors, and Back of House Areas, from Public Areas, including car parks and Specification Access and key control Access control is required at all doors and lifts used by guests from public access areas, including car park and basement, into Specification Access and key control Access control is required at all doors and lifts used by employees from public access areas, including car park and basement, into Back of House Areas Guideline Access and key control that is monitored 24 hours a day, seven days a week combined with key card access control in lift car controlling access to the guest floors, or key card access control fitted to all doors leading from all basement car park levels towards the lift lobbies or access point(s) from basement car parking levels towards the lift lobbies, or permanently staffed by Hotel Security or the lift stopping and Standard Guest and building security https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-02.jpg?height=37&width=1043&top_left_y=2352&top_left_x=857 to address the risk of criminal activities (e.g. hostile surveillance, theft, arson, assault).| Specification | Passenger lift safety | In the event of a fire alarm being activated, lifts must automatically go to the Designated Floor Level and doors must open | | :---: | :---: | :---: | | Specification | Passenger lift safety | A sign must be provided adjacent to the call button(s) in lift lobbies that gives a clear warning against the use of lifts in the event of | | Specification | Passenger lift safety | Lifts must be provided with an alternative power supply which must be available immediately in the event of the normal power | | Specification | Passenger lift safety | If the lift is not provided with an alternative power supply a contract must be in place with a lift maintenance company to | | Specification | Passenger lift safety | Emergency lighting must be provided in the lift car. | | Specification | Passenger lift safety | Each lift is required to have a house telephone or intercom which connects directly to a permanently staffed location. | | Guideline | Passenger lift safety | A permanently staffed location includes a lift maintenance company with a facility to deal with emergencies 24 hours, seven | | Standard | trical sa | Electrical appliances/outlets that may become exposed to water must include safety measures to address the risk of electrocution. | | Specification | Electrical safety | Electrical outlets or appliances that are connected to electrical outlets Adjacent to Sources of Water or in areas that may be exposed to weather must be protected by Ground Fault Circuit | | Standard | Water hygiene | The property must ensure a Water Quality Assessment is conducted by a Qualified Person to identify and manage the risk | | Specification | Water hygiene | A documented Water Safety Management Plan outlining measures to ensure water remains safe must be implemented in | | Specification | Water hygiene | Water Quality Assessment(s) must be reviewed at least every two | | | | The hotel's Food Safety Management system must be evaluated | | Standard | Food hygiene | by a Qualified Person on a recurring basis, providing independent | | Specification | Food hygiene | months for properties: undertaking cook / chill, sous vide, outdoor catering, large-sized Buffet and Banqueting Operations and | | Specification | Food hygiene | Independent evaluation must be completed at least once every 18 months for properties: preparing/cooking raw foods for immediate | | Specification | Food hygiene | Independent evaluation must be completed at least once every 24 months for properties: warming of pre-prepared meals for | | Specification | Food hygiene | The Qualified Person must be independent from the organisation | | Standard | Food hygiene | The hotel must establish a food safety management system to mitigate risks associated with food borne illness, contamination | | Specification | Food hygiene | Food satety management systems must be based on the principles of Hazard Analysis & Critical Control Points (HACCP) or Hazard Analysis & Risk-Based Preventive Controls (HARCP), | | Standard | Access and key control | Hotel access controls must manage the potential of unauthorised individuals from gaining access to guest room corridors, and Back of House Areas, from Public Areas, including car parks and | | Specification | Access and key control | Access control is required at all doors and lifts used by guests from public access areas, including car park and basement, into | | Specification | Access and key control | Access control is required at all doors and lifts used by employees from public access areas, including car park and basement, into Back of House Areas | | Guideline | Access and key control | that is monitored 24 hours a day, seven days a week combined with key card access control in lift car controlling access to the guest floors, or key card access control fitted to all doors leading from all basement car park levels towards the lift lobbies or access point(s) from basement car parking levels towards the lift lobbies, or permanently staffed by Hotel Security or the lift stopping and | | Standard | Guest and building security | ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-02.jpg?height=37&width=1043&top_left_y=2352&top_left_x=857) to address the risk of criminal activities (e.g. hostile surveillance, theft, arson, assault). |
Specification 规格 Guest and building security
访客和建筑安全
Areas to be illuminated include - but are not limited to - entrance doors, parkings areas, courtyards, driveways and steps.
需要照明的区域包括但不限于入口大门、停车场、庭院、车道和台阶。
Standard 标准 Guest and building 客人和建筑 Guest laundry and vending areas must include design features to
客用洗衣房和自动售货机区必须包括以下设计特点
Specification 规格 Guest and building security
访客和建筑安全
Doors leading into guest vending and laundry rooms must include a view window with a minimum area of 645 cm 2 ( 100 in 2 ) 645 cm 2 100 in 2 645cm^(2)(100in^(2))645 \mathrm{~cm}^{2}\left(100 \mathrm{in}^{2}\right).
通向客人自动售货机室和洗衣房的门必须包括一个最小面积为 645 cm 2 ( 100 in 2 ) 645 cm 2 100 in 2 645cm^(2)(100in^(2))645 \mathrm{~cm}^{2}\left(100 \mathrm{in}^{2}\right) 的视窗。
Specification 规格 Guest and building security
访客和建筑安全
Lighting in guest vending and laundry rooms must remain on or automatically illuminate upon entrance into the room.
宾客自动售货室和洗衣房的照明灯必须保持亮着,或在进入房间时自动点亮。
Standard 标准 Guest and building 客人和建筑 Guest Room doors must include security features to deter
客房门必须具有安全功能,以防止
Specification 规格 Guest and building security
访客和建筑安全
All Guest Room entrance doors must be fitted with an IHGapproved Electronic Door Lock capable of being deadlocked, and
所有客房入口处的门都必须安装 IHG 认可的电子门锁,且门锁必须能够锁死,以及
Specification 规格 Guest and building 客人和建筑 All Guest Room entrance doors must be fitted with a One-way
所有客房入口的门都必须安装单向安全门。
Specification 规格 Guest and building security
访客和建筑安全
Where Guest Room entrance doors are not fitted with a One-way view port, the secondary non-keyed locking device must allow
如果客房入口门没有安装单向观察孔,则辅助无钥匙锁定装置必须允许
Specification 规格 Guest and building security
访客和建筑安全
Where secondary locks are prohibited, Guest Room doors must be fitted with a one-way viewport and Guest Room corridor must
在禁止使用辅助门锁的情况下,客房门必须安装单向视窗,客房走廊必须
Specification 规格 Guest and building security
访客和建筑安全
Connecting Guest Room door locks must Include a mortice lock with a minimum 2 cm ( 3 / 4 in ) 2 cm ( 3 / 4 in ) 2cm(3//4in)2 \mathrm{~cm}(3 / 4 \mathrm{in}) throw thumb-turn deadbolt, thumb-turn lock operation on the guest room side of the door, fixed knob or
连接客房的门锁必须包括带最小 2 cm ( 3 / 4 in ) 2 cm ( 3 / 4 in ) 2cm(3//4in)2 \mathrm{~cm}(3 / 4 \mathrm{in}) 拇指旋转死锁的插芯锁、客房一侧的拇指旋转门锁、固定旋钮或拇指旋转门锁。
Standard 标准 Access and key control 门禁和钥匙控制 Replacement Guest Room keys must only be issued to registered guests following positive identification to manage the risk of unauthorised individuals gaining access to, and perpetrating
更换客房钥匙必须在确认身份后才能发给已登记的客人,以控制未经授权的个人进入客房并实施以下行为的风险
Specification 规格 Access and key control 门禁和钥匙控制 Positive physical identification must be requested and provided before a replacement Guest Room key is issued.
在补发客房钥匙之前,必须要求提供真实的身份证明。
Guideline 指导原则 Access and key control 门禁和钥匙控制 Positive identification includes physical photo identification;
正面身份证明包括带照片的实物身份证明;
Guideline 指导原则 Where the guest cannot provide positive physical identification the quest should be accompanied to their room to retrieve evidence of
如果客人无法提供正面的实物身份证明,则应陪同客人回房间取回以下证据
Standard 标准 ss A system of key control must be in place across the hotel to prevent unauthorised individuals from gaining access to secure
必须在整个酒店建立钥匙控制系统,以防止未经授权的个人进入安全区域。
Specification 规格 Access and key control 门禁和钥匙控制 A system of key control must include secure management of Grand Master Keys, Master Keys and Sub-master keys
钥匙控制系统必须包括总钥匙、主钥匙和副主钥匙的安全管理
General Managers should consider the guidelines in IHG's
总经理应考虑国际酒店集团的指导原则。
Guideline 指导原则 Access and key control 门禁和钥匙控制 Responsible Business Site on Merlin when implementing a system
梅林负责任企业网站在实施系统时
andard  ent 参赛者 An Emergency Evacuation Plan is required to ensure the hotel is
酒店必须制定紧急疏散计划,以确保
Specification 规格 Crisis and Incident 危机和事件 The plan must consider the requirements of people with
计划必须考虑残疾人的要求
Specification 规格 Crisis and Incident 危机和事件 Emergency response training must be given to all staff with duties
必须对所有履行职责的工作人员进行应急培训
Specification 规格 Crisis and Incident 危机和事件 Evacuation Drills must be held at least once every six months and
必须至少每六个月举行一次疏散演习,并且
Specification 规格 Crisis and Incident 危机和事件 Every 12 months, the Evacuation Drill must involve the use of the
每 12 个月,疏散演习必须使用
Standard 标准 Crisis and Incident 危机和事件 A Crisis Management Plan must be prepared and practiced, enabling the hotel to effectively respond to forcasted crisis types
必须制定危机管理计划并付诸实践,使酒店能够有效应对预测的危机类型
Specification 规格 Crisis and Incident 危机和事件 The Crisis Managemnt Plan must be reviewed at least annually
危机管理计划必须至少每年审查一次
Specification 规格 Crisis and Incident 危机和事件 The Crisis Ivanagement Pian must include a Security Inreat and Incident Management section stating the hotel's current Threat Category and Alert State, and the advisory security measures
危机管理计划必须包括安全威胁和事件管理部分,说明酒店当前的威胁类别和警戒状态,以及建议采取的安全措施
Guideline 指导原则 Crisis and Incident 危机和事件 Hotels should consider the templates, flow diagrams and
酒店应考虑模板、流程图和
Guideline 指导原则 Crisis and Incident 危机和事件 Records of testing should be maintained.
应保留检测记录。
Guideline 指导原则 Crisis and Incident 危机和事件 Testing of the Crisis Management Plan by Crisis Management
危机管理部门测试危机管理计划
Guideline 指导原则 Crisis and Incident 危机和事件 The contact details of the Crisis Management Team and one or more Emergency Response Teams, suppliers and service
危机管理小组和一个或多个应急小组、供应商和服务机构的详细联系信息
Standard 标准 Crisis and Incident 危机和事件 First ald resources must be provided to be used, it appropriate, in supporting initial response to injury, pending arrival of emergency services, providing opportunity to lessen or stabilise the
在急救服务到达之前,必须提供急救资源,以便在适当情况下用于支持对伤害的初步应对,为减轻或稳定伤情提供机会。
Specification 规格 Crisis and Incident 危机和事件 At least one colleague trained in first aid must be on duty in the
必须至少有一名受过急救培训的同事在现场值班。
First aid kits must be provided.
必须提供急救箱。
Guideline 指导原则 Crisis and Incident 危机和事件 Kits should be provided in but are not limited to the following areas: front desk; kitchen; housekeeping; laundry; maintenance, engineering areas, chemical storage areas, security office, and/or
应在但不限于以下区域提供工具包:前台、厨房、内务、洗衣房、维护、工程区、化学品储存区、安保办公室和/或
Specification Guest and building security Areas to be illuminated include - but are not limited to - entrance doors, parkings areas, courtyards, driveways and steps. Standard Guest and building Guest laundry and vending areas must include design features to Specification Guest and building security Doors leading into guest vending and laundry rooms must include a view window with a minimum area of 645cm^(2)(100in^(2)). Specification Guest and building security Lighting in guest vending and laundry rooms must remain on or automatically illuminate upon entrance into the room. Standard Guest and building Guest Room doors must include security features to deter Specification Guest and building security All Guest Room entrance doors must be fitted with an IHGapproved Electronic Door Lock capable of being deadlocked, and Specification Guest and building All Guest Room entrance doors must be fitted with a One-way Specification Guest and building security Where Guest Room entrance doors are not fitted with a One-way view port, the secondary non-keyed locking device must allow Specification Guest and building security Where secondary locks are prohibited, Guest Room doors must be fitted with a one-way viewport and Guest Room corridor must Specification Guest and building security Connecting Guest Room door locks must Include a mortice lock with a minimum 2cm(3//4in) throw thumb-turn deadbolt, thumb-turn lock operation on the guest room side of the door, fixed knob or Standard Access and key control Replacement Guest Room keys must only be issued to registered guests following positive identification to manage the risk of unauthorised individuals gaining access to, and perpetrating Specification Access and key control Positive physical identification must be requested and provided before a replacement Guest Room key is issued. Guideline Access and key control Positive identification includes physical photo identification; Guideline Where the guest cannot provide positive physical identification the quest should be accompanied to their room to retrieve evidence of Standard ss A system of key control must be in place across the hotel to prevent unauthorised individuals from gaining access to secure Specification Access and key control A system of key control must include secure management of Grand Master Keys, Master Keys and Sub-master keys General Managers should consider the guidelines in IHG's Guideline Access and key control Responsible Business Site on Merlin when implementing a system andard ent An Emergency Evacuation Plan is required to ensure the hotel is Specification Crisis and Incident The plan must consider the requirements of people with Specification Crisis and Incident Emergency response training must be given to all staff with duties Specification Crisis and Incident Evacuation Drills must be held at least once every six months and Specification Crisis and Incident Every 12 months, the Evacuation Drill must involve the use of the Standard Crisis and Incident A Crisis Management Plan must be prepared and practiced, enabling the hotel to effectively respond to forcasted crisis types Specification Crisis and Incident The Crisis Managemnt Plan must be reviewed at least annually Specification Crisis and Incident The Crisis Ivanagement Pian must include a Security Inreat and Incident Management section stating the hotel's current Threat Category and Alert State, and the advisory security measures Guideline Crisis and Incident Hotels should consider the templates, flow diagrams and Guideline Crisis and Incident Records of testing should be maintained. Guideline Crisis and Incident Testing of the Crisis Management Plan by Crisis Management Guideline Crisis and Incident The contact details of the Crisis Management Team and one or more Emergency Response Teams, suppliers and service Standard Crisis and Incident First ald resources must be provided to be used, it appropriate, in supporting initial response to injury, pending arrival of emergency services, providing opportunity to lessen or stabilise the Specification Crisis and Incident At least one colleague trained in first aid must be on duty in the First aid kits must be provided. Guideline Crisis and Incident Kits should be provided in but are not limited to the following areas: front desk; kitchen; housekeeping; laundry; maintenance, engineering areas, chemical storage areas, security office, and/or| Specification | Guest and building security | Areas to be illuminated include - but are not limited to - entrance doors, parkings areas, courtyards, driveways and steps. | | :---: | :---: | :---: | | Standard | Guest and building | Guest laundry and vending areas must include design features to | | Specification | Guest and building security | Doors leading into guest vending and laundry rooms must include a view window with a minimum area of $645 \mathrm{~cm}^{2}\left(100 \mathrm{in}^{2}\right)$. | | Specification | Guest and building security | Lighting in guest vending and laundry rooms must remain on or automatically illuminate upon entrance into the room. | | Standard | Guest and building | Guest Room doors must include security features to deter | | Specification | Guest and building security | All Guest Room entrance doors must be fitted with an IHGapproved Electronic Door Lock capable of being deadlocked, and | | Specification | Guest and building | All Guest Room entrance doors must be fitted with a One-way | | Specification | Guest and building security | Where Guest Room entrance doors are not fitted with a One-way view port, the secondary non-keyed locking device must allow | | Specification | Guest and building security | Where secondary locks are prohibited, Guest Room doors must be fitted with a one-way viewport and Guest Room corridor must | | Specification | Guest and building security | Connecting Guest Room door locks must Include a mortice lock with a minimum $2 \mathrm{~cm}(3 / 4 \mathrm{in})$ throw thumb-turn deadbolt, thumb-turn lock operation on the guest room side of the door, fixed knob or | | Standard | Access and key control | Replacement Guest Room keys must only be issued to registered guests following positive identification to manage the risk of unauthorised individuals gaining access to, and perpetrating | | Specification | Access and key control | Positive physical identification must be requested and provided before a replacement Guest Room key is issued. | | Guideline | Access and key control | Positive identification includes physical photo identification; | | Guideline | | Where the guest cannot provide positive physical identification the quest should be accompanied to their room to retrieve evidence of | | Standard | ss | A system of key control must be in place across the hotel to prevent unauthorised individuals from gaining access to secure | | Specification | Access and key control | A system of key control must include secure management of Grand Master Keys, Master Keys and Sub-master keys | | | | General Managers should consider the guidelines in IHG's | | Guideline | Access and key control | Responsible Business Site on Merlin when implementing a system | | andard | ent | An Emergency Evacuation Plan is required to ensure the hotel is | | Specification | Crisis and Incident | The plan must consider the requirements of people with | | Specification | Crisis and Incident | Emergency response training must be given to all staff with duties | | Specification | Crisis and Incident | Evacuation Drills must be held at least once every six months and | | Specification | Crisis and Incident | Every 12 months, the Evacuation Drill must involve the use of the | | Standard | Crisis and Incident | A Crisis Management Plan must be prepared and practiced, enabling the hotel to effectively respond to forcasted crisis types | | Specification | Crisis and Incident | The Crisis Managemnt Plan must be reviewed at least annually | | Specification | Crisis and Incident | The Crisis Ivanagement Pian must include a Security Inreat and Incident Management section stating the hotel's current Threat Category and Alert State, and the advisory security measures | | Guideline | Crisis and Incident | Hotels should consider the templates, flow diagrams and | | Guideline | Crisis and Incident | Records of testing should be maintained. | | Guideline | Crisis and Incident | Testing of the Crisis Management Plan by Crisis Management | | Guideline | Crisis and Incident | The contact details of the Crisis Management Team and one or more Emergency Response Teams, suppliers and service | | Standard | Crisis and Incident | First ald resources must be provided to be used, it appropriate, in supporting initial response to injury, pending arrival of emergency services, providing opportunity to lessen or stabilise the | | Specification | Crisis and Incident | At least one colleague trained in first aid must be on duty in the | | | | First aid kits must be provided. | | Guideline | Crisis and Incident | Kits should be provided in but are not limited to the following areas: front desk; kitchen; housekeeping; laundry; maintenance, engineering areas, chemical storage areas, security office, and/or |
Guideline 指导原则 Crisis and Incident 危机和事件 Kits should include sterile gauze pads and rolls for covering wounds, medical tape to secure dressings, bandages and band-
工具包应包括用于覆盖伤口的无菌纱布垫和纱布卷、用于固定敷料的医用胶带、绷带和创可贴。
Standard 标准 Leisure facilities safety
休闲设施安全
Access to all Lelisure racilities must be controlled to restrict Inadvertent / accidental / Unauthorised Access during hours of operation, outside of operational hours, and during periods of
必须对所有 Lelisure 场所的进出进行控制,以限制在运营时间内、运营时间外以及在以下情况下的无意/意外/未经授权的进出
Specification 规格 Leisure facilities safety
休闲设施安全
Doors to unsupervised fitness rooms must be secured with an
通往无人看管的健身室的门必须用一个
Specification 规格 Leisure facilities safety
休闲设施安全
Access contro is required at all doors or lifts used to access unsupervised Swimming Pools, Hot Tubs and Water Spas.
所有用于进入无人看管的游泳池、热水浴缸和水疗池的门或升降机都必须安装门禁控制器。
Specification 规格 Leisure facilities safety
休闲设施安全
Where access to Swimming Pools, Hot Iubs and water Spas is controlled by fences/barriers, they must be: i) securely fixed, ii) a minimum height of 1.2 m ( 4 ft ), iii) fitted with self-closing and
如果游泳池、浴缸和水疗池的出入口由围栏/障碍物控制,则围栏/障碍物必须: i) 固定牢靠; ii) 高度至少为 1.2 米(4 英尺); iii) 安装有自动关闭和自动调节装置。
Specification 规格 Leisure facilities safety
休闲设施安全
Where access to Swimming Pools is controlled by means other than a fence/barrier, a Risk Assessment must be completed with
如果进入游泳池的控制方式不是围栏/障碍物,则必须完成风险评估,其中包括
Standard 标准 Leisure facilities safety
休闲设施安全
Leisure Facilities which are not permanently supervised must include a means for users to summon assistance from within the
非长期有人看管的康乐设施必须设有供使用者从设施内求助的装置。
Specification 规格 Leisure facilities safety
休闲设施安全
A distress alarm and/or emergency telephone must be installed in a location that is clearly visible to any person using the Lesiure
遇险报警器和/或紧急电话必须安装在任何使用该停车场的人都能清楚看到的位置。
Specification 规格 Leisure facilities safety
休闲设施安全
All distress alarms and/or emergency telephones must connect to an on-site location that is permanently staffed or enable direct
所有遇险警报和/或紧急电话都必须连接到现场的一个地点,该地点必须长期有人值守,或能够直接连接到该地点。
Emergency rescue equipment appropriate to the nature of the
与救援活动性质相适应的紧急救援设备
Standard 标准 Leisure facilities safety
休闲设施安全
Swimming Pool must be provided to support prompt rescue of
必须提供游泳池,以支持对以下人员的及时救援
Specification 规格 Leisure facilities safety
休闲设施安全
Equipment must be clearly visible and easily accessible.
设备必须清晰可见,便于使用。
Specification 规格 Equipment must enable the prompt rescue of pool users from any location at the pool perimter - i.e. through use of 'safety hooks' or
设备必须能够从泳池周边的任何位置迅速营救泳池使用者--即通过使用 "安全钩 "或 "救生圈"。
Where life safety rings and/or throwing lines are used they must
在使用救生圈和/或投掷绳时,它们必须
in 
Standard 标准 Leisure facilities safety
休闲设施安全
design, managing the risk of users becoming trapped underwater.
设计,控制用户被困在水下的风险。
Specification 规格 Leisure facilities safety
休闲设施安全
A minimum of two drains are required in all Swimming Pools and
所有游泳池和水池必须至少有两个排水口。
All Swimming Pools and Hot Iubs must be equipped with antientrapment drain covers in accordance with ANSI/ASME
所有游泳池和热水池都必须配备符合 ANSI/ASME 标准的防排水盖。
Specification 规格 Leisure facilities safety
休闲设施安全
A112.19.8-2007 or ANSI/APSP-16 2011, unless the drain cover
A112.19.8-2007 或 ANSI/APSP-16 2011,除非排水管盖
Specification 规格 Leisure facilities safety
休闲设施安全
Swimming pools and Hot Tubs with a single drain must be
单排水口的游泳池和热水浴缸必须
Standard 标准 Leisure facilities safety
休闲设施安全
Swimming pool design must include features that enable safe entry and exit for all users to address the risk of injury and/or
游泳池的设计必须包括能让所有使用者安全进出的功能,以应对受伤和/或受伤的风险。
Specification 规格 Leisure facilities safety
休闲设施安全
Access/exit points comprising any combination of steps/stairs, ladders, grab rails with recessed treads, ramps, beach entries or
出入口包括台阶/楼梯、梯子、带凹槽的扶手、坡道、沙滩入口或其他任何组合。
Sp Leisure facilities safety
休闲设施安全
In Swimming Pools where neither the width nor length is more than 9 m (29ft): At least one access/exit point must be provided.
宽度和长度均不超过 9 米(29 英尺)的游泳池:必须至少提供一个出入口。
In Swimming Pools with a width or length of 9 m (29ft) or more: At least two access/exit points must be provided at opposite lengths.
宽度或长度为 9 米(29 英尺)或以上的游泳池:必须在相对长度处提供至少两个出入口。
Specification 规格 Leisure facilities safety
休闲设施安全
Means of access/exit must be Corrosion Resistant.
出入口必须耐腐蚀。
Specification 规格 Leisure facilities safety
休闲设施安全
The Swimming Pool deck must be Slip Resistant.
游泳池甲板必须防滑。
Standard 标准 Leisure facilities safety
休闲设施安全
Swimming Pool design must address the risk of drowning, and facilitate the identification of users who may be in distress and
游泳池的设计必须考虑到溺水的风险,并便于识别可能处于困境中的使用者,以及
Specification 规格 Leisure facilities safety
休闲设施安全
All areas of the bottom of the pool must be clearly seen.
必须清楚地看到池底的所有区域。
Specific 具体内容 Le Water depth for Swimming Pools provided solely for use by children under the age of six years must not be more than 60 cm
专供六岁以下儿童使用的游泳池水深不得超过 60 厘米
Specification 规格 Leisure facilities safety
休闲设施安全
A minimum clear deck space, or travel distance created by a physical barrier, of 3 m (10ft) must be provided at any perimeter separating designated Children's Swimming Pools from any other
在指定的儿童游泳池与任何其他儿童游泳池之间,必须留出至少 3 米(10 英尺)的净甲板空间,或由物理屏障形成的移动距离。
Specification 规格 Leisure facilities safety
休闲设施安全
Features or equipment such as water slides, splash pads, water playgrounds, lazy rivers etc. must be professionally designed and
滑水道、水花喷溅区、水上游乐场、懒人河等设施或设备必须经过专业设计,并符合以下要求
Leisure facilities safety
休闲设施安全
Where provided, features or equipment such as water slides, splash pads, water playgrounds, lazy rivers etc. must be subject to
在提供滑水道、水花喷溅区、水上游乐场、懒人河等设施或设备时,必须符合以下要求
Specification 规格 Leisure facilities safety
休闲设施安全
A minimum of 1.2 m (4ft) of clear deck space must be provided at any perimeter where sitting, standing or walking is intended.
在任何需要坐、站或行走的周边,都必须留出至少 1.2 米(4 英尺)的甲板净空。
Specification 规格 Leisure facilities safety
休闲设施安全
Diving boards, diving platforms, and/or trampolines are not
跳水板、跳水台和/或蹦床不得
Guideline Crisis and Incident Kits should include sterile gauze pads and rolls for covering wounds, medical tape to secure dressings, bandages and band- Standard Leisure facilities safety Access to all Lelisure racilities must be controlled to restrict Inadvertent / accidental / Unauthorised Access during hours of operation, outside of operational hours, and during periods of Specification Leisure facilities safety Doors to unsupervised fitness rooms must be secured with an Specification Leisure facilities safety Access contro is required at all doors or lifts used to access unsupervised Swimming Pools, Hot Tubs and Water Spas. Specification Leisure facilities safety Where access to Swimming Pools, Hot Iubs and water Spas is controlled by fences/barriers, they must be: i) securely fixed, ii) a minimum height of 1.2 m ( 4 ft ), iii) fitted with self-closing and Specification Leisure facilities safety Where access to Swimming Pools is controlled by means other than a fence/barrier, a Risk Assessment must be completed with Standard Leisure facilities safety Leisure Facilities which are not permanently supervised must include a means for users to summon assistance from within the Specification Leisure facilities safety A distress alarm and/or emergency telephone must be installed in a location that is clearly visible to any person using the Lesiure Specification Leisure facilities safety All distress alarms and/or emergency telephones must connect to an on-site location that is permanently staffed or enable direct Emergency rescue equipment appropriate to the nature of the Standard Leisure facilities safety Swimming Pool must be provided to support prompt rescue of Specification Leisure facilities safety Equipment must be clearly visible and easily accessible. Specification Equipment must enable the prompt rescue of pool users from any location at the pool perimter - i.e. through use of 'safety hooks' or Where life safety rings and/or throwing lines are used they must in Standard Leisure facilities safety design, managing the risk of users becoming trapped underwater. Specification Leisure facilities safety A minimum of two drains are required in all Swimming Pools and All Swimming Pools and Hot Iubs must be equipped with antientrapment drain covers in accordance with ANSI/ASME Specification Leisure facilities safety A112.19.8-2007 or ANSI/APSP-16 2011, unless the drain cover Specification Leisure facilities safety Swimming pools and Hot Tubs with a single drain must be Standard Leisure facilities safety Swimming pool design must include features that enable safe entry and exit for all users to address the risk of injury and/or Specification Leisure facilities safety Access/exit points comprising any combination of steps/stairs, ladders, grab rails with recessed treads, ramps, beach entries or Sp Leisure facilities safety In Swimming Pools where neither the width nor length is more than 9 m (29ft): At least one access/exit point must be provided. In Swimming Pools with a width or length of 9 m (29ft) or more: At least two access/exit points must be provided at opposite lengths. Specification Leisure facilities safety Means of access/exit must be Corrosion Resistant. Specification Leisure facilities safety The Swimming Pool deck must be Slip Resistant. Standard Leisure facilities safety Swimming Pool design must address the risk of drowning, and facilitate the identification of users who may be in distress and Specification Leisure facilities safety All areas of the bottom of the pool must be clearly seen. Specific Le Water depth for Swimming Pools provided solely for use by children under the age of six years must not be more than 60 cm Specification Leisure facilities safety A minimum clear deck space, or travel distance created by a physical barrier, of 3 m (10ft) must be provided at any perimeter separating designated Children's Swimming Pools from any other Specification Leisure facilities safety Features or equipment such as water slides, splash pads, water playgrounds, lazy rivers etc. must be professionally designed and Leisure facilities safety Where provided, features or equipment such as water slides, splash pads, water playgrounds, lazy rivers etc. must be subject to Specification Leisure facilities safety A minimum of 1.2 m (4ft) of clear deck space must be provided at any perimeter where sitting, standing or walking is intended. Specification Leisure facilities safety Diving boards, diving platforms, and/or trampolines are not| Guideline | Crisis and Incident | Kits should include sterile gauze pads and rolls for covering wounds, medical tape to secure dressings, bandages and band- | | :---: | :---: | :---: | | Standard | Leisure facilities safety | Access to all Lelisure racilities must be controlled to restrict Inadvertent / accidental / Unauthorised Access during hours of operation, outside of operational hours, and during periods of | | Specification | Leisure facilities safety | Doors to unsupervised fitness rooms must be secured with an | | Specification | Leisure facilities safety | Access contro is required at all doors or lifts used to access unsupervised Swimming Pools, Hot Tubs and Water Spas. | | Specification | Leisure facilities safety | Where access to Swimming Pools, Hot Iubs and water Spas is controlled by fences/barriers, they must be: i) securely fixed, ii) a minimum height of 1.2 m ( 4 ft ), iii) fitted with self-closing and | | Specification | Leisure facilities safety | Where access to Swimming Pools is controlled by means other than a fence/barrier, a Risk Assessment must be completed with | | Standard | Leisure facilities safety | Leisure Facilities which are not permanently supervised must include a means for users to summon assistance from within the | | Specification | Leisure facilities safety | A distress alarm and/or emergency telephone must be installed in a location that is clearly visible to any person using the Lesiure | | Specification | Leisure facilities safety | All distress alarms and/or emergency telephones must connect to an on-site location that is permanently staffed or enable direct | | | | Emergency rescue equipment appropriate to the nature of the | | Standard | Leisure facilities safety | Swimming Pool must be provided to support prompt rescue of | | Specification | Leisure facilities safety | Equipment must be clearly visible and easily accessible. | | Specification | | Equipment must enable the prompt rescue of pool users from any location at the pool perimter - i.e. through use of 'safety hooks' or | | | | Where life safety rings and/or throwing lines are used they must | | | | in | | Standard | Leisure facilities safety | design, managing the risk of users becoming trapped underwater. | | Specification | Leisure facilities safety | A minimum of two drains are required in all Swimming Pools and | | | | All Swimming Pools and Hot Iubs must be equipped with antientrapment drain covers in accordance with ANSI/ASME | | Specification | Leisure facilities safety | A112.19.8-2007 or ANSI/APSP-16 2011, unless the drain cover | | Specification | Leisure facilities safety | Swimming pools and Hot Tubs with a single drain must be | | Standard | Leisure facilities safety | Swimming pool design must include features that enable safe entry and exit for all users to address the risk of injury and/or | | Specification | Leisure facilities safety | Access/exit points comprising any combination of steps/stairs, ladders, grab rails with recessed treads, ramps, beach entries or | | Sp | Leisure facilities safety | In Swimming Pools where neither the width nor length is more than 9 m (29ft): At least one access/exit point must be provided. | | | | In Swimming Pools with a width or length of 9 m (29ft) or more: At least two access/exit points must be provided at opposite lengths. | | Specification | Leisure facilities safety | Means of access/exit must be Corrosion Resistant. | | Specification | Leisure facilities safety | The Swimming Pool deck must be Slip Resistant. | | Standard | Leisure facilities safety | Swimming Pool design must address the risk of drowning, and facilitate the identification of users who may be in distress and | | Specification | Leisure facilities safety | All areas of the bottom of the pool must be clearly seen. | | Specific | Le | Water depth for Swimming Pools provided solely for use by children under the age of six years must not be more than 60 cm | | Specification | Leisure facilities safety | A minimum clear deck space, or travel distance created by a physical barrier, of 3 m (10ft) must be provided at any perimeter separating designated Children's Swimming Pools from any other | | Specification | Leisure facilities safety | Features or equipment such as water slides, splash pads, water playgrounds, lazy rivers etc. must be professionally designed and | | | Leisure facilities safety | Where provided, features or equipment such as water slides, splash pads, water playgrounds, lazy rivers etc. must be subject to | | Specification | Leisure facilities safety | A minimum of 1.2 m (4ft) of clear deck space must be provided at any perimeter where sitting, standing or walking is intended. | | Specification | Leisure facilities safety | Diving boards, diving platforms, and/or trampolines are not |
Standard 标准 Leisure facilities safety
休闲设施安全
User information must be displayed adjacent to the Swimming Pool, to ensure safe use of the facility within one's ability, such as
游泳池旁必须展示用户信息,以确保在个人能力范围内安全使用设施,例如
Specification 规格 Leisure facilities safety
休闲设施安全
Depth markings - shown in both feet and metres - must be displayed near entry points to the swimming pool, on all sides of
必须在游泳池入口处附近、池边和池底的所有位置标明水深(以英尺和米为单位)。
Specification 规格 Leisure facilities safety
休闲设施安全
Professionally fabricated and permanently installed signage in the local language(s) and English must state i) local rules of
用当地语言和英语制作并永久性安装的标牌必须说明 i) 当地的《公约》规则; ii) 《公约》的适用范围; iii) 《公约》的适用范围; iv) 《公约》的适用范围; v) 《公约》的适用范围。
Guideline 指导原则 Leisure facilities safety
休闲设施安全
Beach entry and zero depth type swimming pools should display a sign indicating 'shallow water' at shallow water entrance point.
海滩式游泳池和零深度式游泳池应在浅水入口处设置 "浅水 "标志。
Standard 标准 Leisure facilities safety
休闲设施安全
Hot tub controls must include safety features to address the risk of injury or drowning, and, to aid identification and removal of users
热水浴缸控制装置必须包括安全功能,以应对受伤或溺水风险,并帮助识别和移除使用者
Specification 规格 Leisure facilities safety
休闲设施安全
Hot tub features (i.e. jets) must be fitted with a timer which ensures continuous operation for not longer than 15 -minutes.
热水浴缸功能(如喷射器)必须安装计时器,以确保连续运行不超过 15 分钟。
Specification 规格 Leisure facilities safety
休闲设施安全
A clearly labelled manual shut-off control mechanism for the water circulation pump located either within 3 m ( 10 ft ) of the edge of the
水循环泵的手动关闭控制装置要有明确的标签,该装置应位于距离水池边缘 3 米(10 英尺)的范围内。
Specification 规格 Leisure facilities safety
休闲设施安全
Water depth markings must be in both feet and meters, and be
水深标记必须以英尺和米为单位,并且必须
Specification 规格 Leisure facilities safety
休闲设施安全
User safety signage must be displayed in the locallanguage(s) and English, including the international 'No Diving' symbol.
必须使用当地语言和英语显示用户安全标识,包括国际 "禁止潜水 "符号。
Standard 标准 Fire detection and alarm 火灾探测和警报 An automatic detection and alarm system must be provided throughout the building to give immediate warning of a fire to occupants in the room or zone of fire origin, and raise a General Alarm for prompt evacuation.
整栋楼必须安装自动探测和报警系统,以便在发生火灾时立即向房间内或起火区域内的人员发出警报,并发出一般警报以便迅速疏散。
Specification 规格 Fire detection and alarm 火灾探测和警报 The automatic detection and alarm svstem must be desianed and
必须对自动探测和警报系统进行设计,并且
Specification 规格 Fire detection and alarm 火灾探测和警报 The automatic fire detection and alarm svstem must be Permanentlv
火灾自动探测和警报系统必须是永久性的
Specification 规格 Fire detection and alarm 火灾探测和警报 The automatic fire detection svstem must be addressable.
自动火灾探测系统必须可寻址。
Specification 规格 Fire detection and alarm 火灾探测和警报 Smoke detectors must be supervised by the fire alarm panel
烟雾探测器必须由火警面板监控
Specification 规格 Fire detection and alarm 火灾探测和警报 Zoned detectors are permitted in Low-Rise and Medium-Rise buildings.
低层和中层建筑可安装分区探测器。
Specification 规格 Fire detection and alarm 火灾探测和警报 Hardwired (non-Zoned) detectors are permitted in Guest Rooms in buildinas with a Fixed Fire Suboression Svstem throughout._oroviding
在配有固定消防子系统的建筑中,客房内可使用硬接线(非分区)探测器。
Specification 规格 Fire detection and alarm 火灾探测和警报 When a Zoned or Hardwired detector is being replaced at the end of the detector's life thev must be reolaced with like for like detectors. If the
当分区探测器或硬线探测器的使用寿命结束后需要更换时,必须重新配对同类探测器。如果
Specification 规格 Fire detection and alarm 火灾探测和警报 Standalone guest villas (e.g. in a resort) of Non-Combustible construction or separated from any other villa or building by 3 m are permitted with a
非易燃建筑或与任何其他别墅或建筑相隔 3 米的独立客用别墅(如度假村内的客用 别墅),可在以下情况下使用
Specification 规格 Fire detection and alarm 火灾探测和警报 Attics without a fixed fire suppresion system must be provided with
没有固定灭火系统的阁楼必须配备
Specification 规格 Fire detection and alarm 火灾探测和警报 manual call point (pull station) must be provided at a permanently
手动呼叫点(拉力站)必须设置在一个永久性的
Specification 规格 Fire detection and alarm 火灾探测和警报 Manual call points (pull stations) must be provided in Back of House
后院必须设置手动呼叫点(拉力站
Specification 规格 detection and ala 检测和分析 The general fire alarm must provide a minimum sound level of 65 dB
一般火警警报的最低音量必须为 65 分贝
Specification 规格 Fire detection and alarm 火灾探测和警报 An alarm device must be located in all Guest Rooms.
所有客房都必须安装报警装置。
Specification 规格 Fire detection and alarm 火灾探测和警报 Where the building is protected throughout by an Addressable fire detection svstem the sustem fire alarm device located in the Guest
如果整个建筑都由可寻址火灾探测系统提供保护,则位于客房内的系统火灾报警装置
Specification 规格 Fire detection and alarm 火灾探测和警报 Where Zoned or Hardwired detectors are permitted in Guest Rooms, the fire alarm device must achieve 75 dBA at the bed head in the Guest
在客房内允许使用分区或硬线探测器的情况下,火灾报警装置必须在客房床头处达到 75 分贝。
Specification 规格 Fire detection and alarm 火灾探测和警报 Visual fire alarm (e.q. strobes) must be located in all Public Areas.
所有公共区域必须安装可视火灾报警器(如频闪灯)。
Specification 规格 Fire detection and alarm 火灾探测和警报 Visual fire alarm (e.a. strobes) must be located in all Guest Rooms
所有客房必须安装可视火灾报警器(如频闪器
Specification 规格 Fire detection and alarm 火灾探测和警报 In High-rise and Super High-rise properties where evacuation must be phased, the automatic fire alarm system must incorporate a broadcast
在必须分阶段疏散的高层和超高层物业中,火灾自动报警系统必须包括一个广播系统
Specification 规格 Fire detection and alarm 火灾探测和警报 The automatic detection and fire alarm system must have an automatic emeroency nower sunnlv for a minimum of 24 hours oneration
自动探测和火灾报警系统必须有至少 24 小时运行的自动应急电源。
Standard 标准 Fire detection and alarm 火灾探测和警报 Fire alarm systems must be programmed to enable immediate fire alarm notificaton upon smoke or fire detection, prompt investigation of a notential fire and activation of the fire alarm when needed for timelv
火灾报警系统的程序必须能够在探测到烟雾或火灾时立即发出火警通知,迅速调查潜在火灾,并在需要时及时启动火警。
Specification 规格 Fire detection and alarm 火灾探测和警报 Upon activation, system detectors must sound an alarm without delav at
启动时,系统探测器必须在以下位置发出警报声,而不发出声音
Specification 规格 Fire detection and alarm 火灾探测和警报 An alarm must sound without delav in the Guest Room where the smoke
客房内的烟雾报警器必须响起而不发出声音。
Specification 规格 Fire detection and alarm 火灾探测和警报 A General Alarm must sound upon activation of two Addressable smoke
两个可寻址烟雾警报器启动时必须发出一般警报。
Specification 规格 Fire detection and alarm 火灾探测和警报 Where the building is protected by an Addressable fire detection system then an investigation period is permitted after first detector activation and before the General Alarm is activated. The General Alarm must sound
如果建筑物受到可寻址火灾探测系统的保护,则在探测器首次启动后和一般警报启动前允许有一段调查时间。一般警报必须响起
Specification 规格 Fire detection and alarm 火灾探测和警报 A General Alarm must sound upon activation of a heat detector.
热探测器启动时必须发出一般警报。
Specification 规格 Fire detection and alarm 火灾探测和警报 A General Alarm must sound upon activation of a Fixed Fire Suppression
固定灭火装置启动时必须发出一般警报。
Specification 规格 Fire detection and alarm 火灾探测和警报 A General Alarm must sound upon activation of manual call points (pull
手动呼叫点(拉绳)启动时必须发出一般警报。
Standard Leisure facilities safety User information must be displayed adjacent to the Swimming Pool, to ensure safe use of the facility within one's ability, such as Specification Leisure facilities safety Depth markings - shown in both feet and metres - must be displayed near entry points to the swimming pool, on all sides of Specification Leisure facilities safety Professionally fabricated and permanently installed signage in the local language(s) and English must state i) local rules of Guideline Leisure facilities safety Beach entry and zero depth type swimming pools should display a sign indicating 'shallow water' at shallow water entrance point. Standard Leisure facilities safety Hot tub controls must include safety features to address the risk of injury or drowning, and, to aid identification and removal of users Specification Leisure facilities safety Hot tub features (i.e. jets) must be fitted with a timer which ensures continuous operation for not longer than 15 -minutes. Specification Leisure facilities safety A clearly labelled manual shut-off control mechanism for the water circulation pump located either within 3 m ( 10 ft ) of the edge of the Specification Leisure facilities safety Water depth markings must be in both feet and meters, and be Specification Leisure facilities safety User safety signage must be displayed in the locallanguage(s) and English, including the international 'No Diving' symbol. Standard Fire detection and alarm An automatic detection and alarm system must be provided throughout the building to give immediate warning of a fire to occupants in the room or zone of fire origin, and raise a General Alarm for prompt evacuation. Specification Fire detection and alarm The automatic detection and alarm svstem must be desianed and Specification Fire detection and alarm The automatic fire detection and alarm svstem must be Permanentlv Specification Fire detection and alarm The automatic fire detection svstem must be addressable. Specification Fire detection and alarm Smoke detectors must be supervised by the fire alarm panel Specification Fire detection and alarm Zoned detectors are permitted in Low-Rise and Medium-Rise buildings. Specification Fire detection and alarm Hardwired (non-Zoned) detectors are permitted in Guest Rooms in buildinas with a Fixed Fire Suboression Svstem throughout._oroviding Specification Fire detection and alarm When a Zoned or Hardwired detector is being replaced at the end of the detector's life thev must be reolaced with like for like detectors. If the Specification Fire detection and alarm Standalone guest villas (e.g. in a resort) of Non-Combustible construction or separated from any other villa or building by 3 m are permitted with a Specification Fire detection and alarm Attics without a fixed fire suppresion system must be provided with Specification Fire detection and alarm manual call point (pull station) must be provided at a permanently Specification Fire detection and alarm Manual call points (pull stations) must be provided in Back of House Specification detection and ala The general fire alarm must provide a minimum sound level of 65 dB Specification Fire detection and alarm An alarm device must be located in all Guest Rooms. Specification Fire detection and alarm Where the building is protected throughout by an Addressable fire detection svstem the sustem fire alarm device located in the Guest Specification Fire detection and alarm Where Zoned or Hardwired detectors are permitted in Guest Rooms, the fire alarm device must achieve 75 dBA at the bed head in the Guest Specification Fire detection and alarm Visual fire alarm (e.q. strobes) must be located in all Public Areas. Specification Fire detection and alarm Visual fire alarm (e.a. strobes) must be located in all Guest Rooms Specification Fire detection and alarm In High-rise and Super High-rise properties where evacuation must be phased, the automatic fire alarm system must incorporate a broadcast Specification Fire detection and alarm The automatic detection and fire alarm system must have an automatic emeroency nower sunnlv for a minimum of 24 hours oneration Standard Fire detection and alarm Fire alarm systems must be programmed to enable immediate fire alarm notificaton upon smoke or fire detection, prompt investigation of a notential fire and activation of the fire alarm when needed for timelv Specification Fire detection and alarm Upon activation, system detectors must sound an alarm without delav at Specification Fire detection and alarm An alarm must sound without delav in the Guest Room where the smoke Specification Fire detection and alarm A General Alarm must sound upon activation of two Addressable smoke Specification Fire detection and alarm Where the building is protected by an Addressable fire detection system then an investigation period is permitted after first detector activation and before the General Alarm is activated. The General Alarm must sound Specification Fire detection and alarm A General Alarm must sound upon activation of a heat detector. Specification Fire detection and alarm A General Alarm must sound upon activation of a Fixed Fire Suppression Specification Fire detection and alarm A General Alarm must sound upon activation of manual call points (pull| Standard | Leisure facilities safety | User information must be displayed adjacent to the Swimming Pool, to ensure safe use of the facility within one's ability, such as | | :---: | :---: | :---: | | Specification | Leisure facilities safety | Depth markings - shown in both feet and metres - must be displayed near entry points to the swimming pool, on all sides of | | Specification | Leisure facilities safety | Professionally fabricated and permanently installed signage in the local language(s) and English must state i) local rules of | | Guideline | Leisure facilities safety | Beach entry and zero depth type swimming pools should display a sign indicating 'shallow water' at shallow water entrance point. | | Standard | Leisure facilities safety | Hot tub controls must include safety features to address the risk of injury or drowning, and, to aid identification and removal of users | | Specification | Leisure facilities safety | Hot tub features (i.e. jets) must be fitted with a timer which ensures continuous operation for not longer than 15 -minutes. | | Specification | Leisure facilities safety | A clearly labelled manual shut-off control mechanism for the water circulation pump located either within 3 m ( 10 ft ) of the edge of the | | Specification | Leisure facilities safety | Water depth markings must be in both feet and meters, and be | | Specification | Leisure facilities safety | User safety signage must be displayed in the locallanguage(s) and English, including the international 'No Diving' symbol. | | Standard | Fire detection and alarm | An automatic detection and alarm system must be provided throughout the building to give immediate warning of a fire to occupants in the room or zone of fire origin, and raise a General Alarm for prompt evacuation. | | Specification | Fire detection and alarm | The automatic detection and alarm svstem must be desianed and | | Specification | Fire detection and alarm | The automatic fire detection and alarm svstem must be Permanentlv | | Specification | Fire detection and alarm | The automatic fire detection svstem must be addressable. | | Specification | Fire detection and alarm | Smoke detectors must be supervised by the fire alarm panel | | Specification | Fire detection and alarm | Zoned detectors are permitted in Low-Rise and Medium-Rise buildings. | | Specification | Fire detection and alarm | Hardwired (non-Zoned) detectors are permitted in Guest Rooms in buildinas with a Fixed Fire Suboression Svstem throughout._oroviding | | Specification | Fire detection and alarm | When a Zoned or Hardwired detector is being replaced at the end of the detector's life thev must be reolaced with like for like detectors. If the | | Specification | Fire detection and alarm | Standalone guest villas (e.g. in a resort) of Non-Combustible construction or separated from any other villa or building by 3 m are permitted with a | | Specification | Fire detection and alarm | Attics without a fixed fire suppresion system must be provided with | | Specification | Fire detection and alarm | manual call point (pull station) must be provided at a permanently | | Specification | Fire detection and alarm | Manual call points (pull stations) must be provided in Back of House | | Specification | detection and ala | The general fire alarm must provide a minimum sound level of 65 dB | | Specification | Fire detection and alarm | An alarm device must be located in all Guest Rooms. | | Specification | Fire detection and alarm | Where the building is protected throughout by an Addressable fire detection svstem the sustem fire alarm device located in the Guest | | Specification | Fire detection and alarm | Where Zoned or Hardwired detectors are permitted in Guest Rooms, the fire alarm device must achieve 75 dBA at the bed head in the Guest | | Specification | Fire detection and alarm | Visual fire alarm (e.q. strobes) must be located in all Public Areas. | | Specification | Fire detection and alarm | Visual fire alarm (e.a. strobes) must be located in all Guest Rooms | | Specification | Fire detection and alarm | In High-rise and Super High-rise properties where evacuation must be phased, the automatic fire alarm system must incorporate a broadcast | | Specification | Fire detection and alarm | The automatic detection and fire alarm system must have an automatic emeroency nower sunnlv for a minimum of 24 hours oneration | | Standard | Fire detection and alarm | Fire alarm systems must be programmed to enable immediate fire alarm notificaton upon smoke or fire detection, prompt investigation of a notential fire and activation of the fire alarm when needed for timelv | | Specification | Fire detection and alarm | Upon activation, system detectors must sound an alarm without delav at | | Specification | Fire detection and alarm | An alarm must sound without delav in the Guest Room where the smoke | | Specification | Fire detection and alarm | A General Alarm must sound upon activation of two Addressable smoke | | Specification | Fire detection and alarm | Where the building is protected by an Addressable fire detection system then an investigation period is permitted after first detector activation and before the General Alarm is activated. The General Alarm must sound | | Specification | Fire detection and alarm | A General Alarm must sound upon activation of a heat detector. | | Specification | Fire detection and alarm | A General Alarm must sound upon activation of a Fixed Fire Suppression | | Specification | Fire detection and alarm | A General Alarm must sound upon activation of manual call points (pull |
Specification 规格 Fire detection and alarm 火灾探测和警报 A General Alarm must sound upon activation of a single non-addressable
单个不可寻址的警报器启动时必须发出一般警报。
Specification 规格 Fire detection and alarm 火灾探测和警报 In High-rise and Super High-rise properties where evacuation must be phased the fire alarm must cascade from the initial fire alarm to a
在必须分阶段疏散的高层和超高层物业中,火警警报必须从最初的火警警报级联到
Standard 标准 Egress 出口 Egress routes throughout the building must lead to a Final Exit and Place of Safetv at the exterior of the buildina in case of fire or emeraencv
在发生火灾或紧急情况时,整个建筑的逃生通道必须通向建筑外部的最终出口和安全地点。
Specification 规格 Egress 出口 A minimum of two Remote Exits must be provided on each floor.
每个楼层必须至少有两个远程出口。
Specification 规格 Egress 出口 A minimum of two Remote Exits must be provided on each floor, except for Low-rise or Medium-rise buildinas which onlv have a single Exit Stair
每层必须至少有两个远程出口,但低层或中层建筑除外,它们只有一个出口楼梯。
Specification 规格 Egress 出口 In buildings without a Fixed Fire Suppression System and where an Earess route includes travel down an oben stair. the Travel Distance to a
在没有固定灭火系统的建筑物中,如果逃生路线包括下楼梯,则到消防水龙头的行程距离应为: 1.
Specification 规格 Egress 出口 In buildings with a Fixed Fire Suppression System and where an Egress route includes travel down an open stair. the Travel Distance to a Final
在装有固定灭火系统的建筑物中,如果逃生路线包括走下敞开式楼梯。
Specification 规格 Egress 出口 The- Common Path of Travel from any area, excluding from within Guest Rooms, must not exceed 23 m ( 75 ft ) except where the building is
从任何区域(不包括客房内)出发的共同通行路径不得超过 23 米(75 英尺),除非建筑物是
Specification 规格 Egress 出口 Exit Stairs must lead to a Final Exit or Fire Rated corridor leadina to a
出口楼梯必须通向最终出口或防火走廊,通向
Specification 规格 Egress 出口 Exit Stairs and Fire rated corridors leading to a Final Exit must be kept
通往最后出口的出口楼梯和防火走廊必须保持畅通。
Specification 规格 Egress 出口 Final Exits must discharge to a Place of Safety.
最后出口必须通往安全地点。
Specification 规格 Egress 出口 Final Exits must not discharge into an enclosed space (e.g. internal
最后出口不得排入封闭空间(如内部空间)。
Specification 规格 Egress 出口 In Buildings with a Fixed Fire Suppression System, up to 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area within sight of the Final Exit.
在装有固定灭火系统的建筑物中,允许最多 50%的出口楼梯在最后出口的视线范围内通向前厅循环区。
Specification 规格 Egress 出口 In Low-rise and Medium-rise properties, 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area within sight of the Final Evit
在低层和中层物业中,允许 50%的出口楼梯通向最终出口视线范围内的楼前循环区。
Specification 规格 Egress 出口 In Low-rise and Medium-rise properties, 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area without sight of the Final Exit if there are two directions of escape from the Exit Stair into two distinct Fire Rated compartments. The Exit Doors from the Exit Stair
在低层和中层物业中,如果出口楼梯有两个逃生方向,分别通向两个不同的防火隔间,则允许 50%的出口楼梯通向前厅循环区,而看不到最终出口。出口楼梯的出口门
Specification 规格 Egress 出口 In Low-rise and Medium-rise properties. at least 50 % 50 % 50%50 \% of all Exit Stairs
在低层和中层物业中,所有出口楼梯至少 50 % 50 % 50%50 \%
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must include a fire alarm that sounds simultaneously on the fire affected floor to alert
只有一个出口楼梯的低层或中层建筑必须安装一个火警警报器,在受火灾影响的楼层同时响起,以发出警报
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must include a fire alarm that sounds simultaneouslv throughout the building upon
只有一个出口楼梯的低层或中层建筑必须安装一个火警警报器,一旦发生火灾,警报器会在整个建筑内同时响起。
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must include Stairwell and Stairwell access doors that are at least 60-minutes Fire
仅有一个出口楼梯的低层或中层建筑必须包括楼梯间和楼梯间出入口至少 60 分钟耐火等级的门。
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must
低层或中层建筑,如果只有一个出口楼梯,则必须
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must include Earess corridors and doors openino into Earess corridors, that are at least
设有单一出口楼梯的低层或中层建筑必须包括出口走廊和通向出口走廊的门,其高度至少为
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must have a Smoke Manacement Svstem to orotect the Exit Stair from smoke
只有一个出口楼梯的低层或中层建筑必须安装烟雾报警系统,以防止出口楼梯受到烟雾的影响。
Specification 规格 Egress 出口 Low-rise or Medium-rise buildings, with a single Exit Stair, must not have rooms that open directlv into the Stairwell there must be a 60 -minute
只有一个出口楼梯的低层或中层建筑不得有直接通向楼梯井的房间。
Standard 标准 Egress 出口 Corridors must include features to address the risk of entrapment in case
走廊必须包括在发生以下情况时解决被困风险的功能
Specification 规格 Egress 出口 Dead-end corridor must not exceed 20 m ( 66 ft ) in Back of House areas.
后宅区的死角走廊不得超过 20 米(66 英尺)。
Specification 规格 Egress 出口 Dead-end corridor-must not exceed 15m (49ft) in Front of House areas.
死角走廊--在房前区不得超过 15 米(49 英尺)。
Specification 规格 Egress 出口 Dead-end corridor must not exceed 15m (49ft) in Front of House areas excent where all "Dead-end corridor Snecifications" contained within this
在本手册所包含的所有 "死角走廊要求 "之外,住宅前区的死角走廊不得超过 15 米(49 英尺)。
Specification 规格 Egress 出口 Dead-end corridors between 15 m (49ft) and 20 m ( 66 ft ) must have at least 30-minutes Fire Rated construction with 30-minute Fire Rated-doors
15 米(49 英尺)和 20 米(66 英尺)之间的死角走廊必须至少有 30 分钟耐火等级的建筑和 30 分钟耐火等级的门。
Specification 规格 Egress 出口 Dead-end corridors between 15 m (49ft) and 20 m ( 66 ft ) must have a cross corridor Fire Rated Door olaced after the first stair to separate the
15 米(49 英尺)至 20 米(66 英尺)之间的死角走廊必须在第一级楼梯之后安装一扇跨走廊防火门,以分隔两个楼梯。
Specification 规格 Egress 出口 Dead-end corridors between 15 m (49ftt) and 20 m ( 66 ft ) must have an immediate fire alarm (no delav) that sounds in all rooms alono the Dead-
15 米(49 英尺)至 20 米(66 英尺)之间的死角走廊必须安装即时火警警报器(无延时),在死角走廊的所有房间内响起。
Specification 规格 Egress 出口 A Dead-end corridor areater than 20 m ( 66 ft ) mav be permitted subiect to
在以下情况下,可允许使用长于 20 米(66 英尺)的死胡同走廊
Standard 标准 Egress 出口 Egress routes from Places of Assembly must have capacity proportionate to the occumant load in order to facilitate evacuation in case of
集会场所出口通道的容量必须与集会人数成比例,以便在发生以下情况时便于疏散
Specification 规格 Egress 出口 A single Exit is acceptable where the occupant load is less than 60
如果住户人数少于 60 人,可以使用单个出口。
Specification 规格 Egress 出口 A single Exit is acceptable where the there is a management procedure to maintain the cccumant load to less than 60 neonle and the maximum
如果有管理程序将污染物负荷保持在 60 neonle 以下,且最大值为 0.5 neonle,则可接受单一出口。
Specification 规格 Egress 出口 At least two Remote Exits for 60 to 500 people.
至少有两个可容纳 60 至 500 人的远程出口。
Specification Fire detection and alarm A General Alarm must sound upon activation of a single non-addressable Specification Fire detection and alarm In High-rise and Super High-rise properties where evacuation must be phased the fire alarm must cascade from the initial fire alarm to a Standard Egress Egress routes throughout the building must lead to a Final Exit and Place of Safetv at the exterior of the buildina in case of fire or emeraencv Specification Egress A minimum of two Remote Exits must be provided on each floor. Specification Egress A minimum of two Remote Exits must be provided on each floor, except for Low-rise or Medium-rise buildinas which onlv have a single Exit Stair Specification Egress In buildings without a Fixed Fire Suppression System and where an Earess route includes travel down an oben stair. the Travel Distance to a Specification Egress In buildings with a Fixed Fire Suppression System and where an Egress route includes travel down an open stair. the Travel Distance to a Final Specification Egress The- Common Path of Travel from any area, excluding from within Guest Rooms, must not exceed 23 m ( 75 ft ) except where the building is Specification Egress Exit Stairs must lead to a Final Exit or Fire Rated corridor leadina to a Specification Egress Exit Stairs and Fire rated corridors leading to a Final Exit must be kept Specification Egress Final Exits must discharge to a Place of Safety. Specification Egress Final Exits must not discharge into an enclosed space (e.g. internal Specification Egress In Buildings with a Fixed Fire Suppression System, up to 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area within sight of the Final Exit. Specification Egress In Low-rise and Medium-rise properties, 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area within sight of the Final Evit Specification Egress In Low-rise and Medium-rise properties, 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area without sight of the Final Exit if there are two directions of escape from the Exit Stair into two distinct Fire Rated compartments. The Exit Doors from the Exit Stair Specification Egress In Low-rise and Medium-rise properties. at least 50% of all Exit Stairs Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must include a fire alarm that sounds simultaneously on the fire affected floor to alert Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must include a fire alarm that sounds simultaneouslv throughout the building upon Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must include Stairwell and Stairwell access doors that are at least 60-minutes Fire Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must include Earess corridors and doors openino into Earess corridors, that are at least Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must have a Smoke Manacement Svstem to orotect the Exit Stair from smoke Specification Egress Low-rise or Medium-rise buildings, with a single Exit Stair, must not have rooms that open directlv into the Stairwell there must be a 60 -minute Standard Egress Corridors must include features to address the risk of entrapment in case Specification Egress Dead-end corridor must not exceed 20 m ( 66 ft ) in Back of House areas. Specification Egress Dead-end corridor-must not exceed 15m (49ft) in Front of House areas. Specification Egress Dead-end corridor must not exceed 15m (49ft) in Front of House areas excent where all "Dead-end corridor Snecifications" contained within this Specification Egress Dead-end corridors between 15 m (49ft) and 20 m ( 66 ft ) must have at least 30-minutes Fire Rated construction with 30-minute Fire Rated-doors Specification Egress Dead-end corridors between 15 m (49ft) and 20 m ( 66 ft ) must have a cross corridor Fire Rated Door olaced after the first stair to separate the Specification Egress Dead-end corridors between 15 m (49ftt) and 20 m ( 66 ft ) must have an immediate fire alarm (no delav) that sounds in all rooms alono the Dead- Specification Egress A Dead-end corridor areater than 20 m ( 66 ft ) mav be permitted subiect to Standard Egress Egress routes from Places of Assembly must have capacity proportionate to the occumant load in order to facilitate evacuation in case of Specification Egress A single Exit is acceptable where the occupant load is less than 60 Specification Egress A single Exit is acceptable where the there is a management procedure to maintain the cccumant load to less than 60 neonle and the maximum Specification Egress At least two Remote Exits for 60 to 500 people.| Specification | Fire detection and alarm | A General Alarm must sound upon activation of a single non-addressable | | :---: | :---: | :---: | | Specification | Fire detection and alarm | In High-rise and Super High-rise properties where evacuation must be phased the fire alarm must cascade from the initial fire alarm to a | | Standard | Egress | Egress routes throughout the building must lead to a Final Exit and Place of Safetv at the exterior of the buildina in case of fire or emeraencv | | Specification | Egress | A minimum of two Remote Exits must be provided on each floor. | | Specification | Egress | A minimum of two Remote Exits must be provided on each floor, except for Low-rise or Medium-rise buildinas which onlv have a single Exit Stair | | Specification | Egress | In buildings without a Fixed Fire Suppression System and where an Earess route includes travel down an oben stair. the Travel Distance to a | | Specification | Egress | In buildings with a Fixed Fire Suppression System and where an Egress route includes travel down an open stair. the Travel Distance to a Final | | Specification | Egress | The- Common Path of Travel from any area, excluding from within Guest Rooms, must not exceed 23 m ( 75 ft ) except where the building is | | Specification | Egress | Exit Stairs must lead to a Final Exit or Fire Rated corridor leadina to a | | Specification | Egress | Exit Stairs and Fire rated corridors leading to a Final Exit must be kept | | Specification | Egress | Final Exits must discharge to a Place of Safety. | | Specification | Egress | Final Exits must not discharge into an enclosed space (e.g. internal | | Specification | Egress | In Buildings with a Fixed Fire Suppression System, up to 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area within sight of the Final Exit. | | Specification | Egress | In Low-rise and Medium-rise properties, 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area within sight of the Final Evit | | Specification | Egress | In Low-rise and Medium-rise properties, 50% of Exit Stairs are permitted to discharge to a Front of House Circulation area without sight of the Final Exit if there are two directions of escape from the Exit Stair into two distinct Fire Rated compartments. The Exit Doors from the Exit Stair | | Specification | Egress | In Low-rise and Medium-rise properties. at least $50 \%$ of all Exit Stairs | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must include a fire alarm that sounds simultaneously on the fire affected floor to alert | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must include a fire alarm that sounds simultaneouslv throughout the building upon | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must include Stairwell and Stairwell access doors that are at least 60-minutes Fire | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must include Earess corridors and doors openino into Earess corridors, that are at least | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must have a Smoke Manacement Svstem to orotect the Exit Stair from smoke | | Specification | Egress | Low-rise or Medium-rise buildings, with a single Exit Stair, must not have rooms that open directlv into the Stairwell there must be a 60 -minute | | Standard | Egress | Corridors must include features to address the risk of entrapment in case | | Specification | Egress | Dead-end corridor must not exceed 20 m ( 66 ft ) in Back of House areas. | | Specification | Egress | Dead-end corridor-must not exceed 15m (49ft) in Front of House areas. | | Specification | Egress | Dead-end corridor must not exceed 15m (49ft) in Front of House areas excent where all "Dead-end corridor Snecifications" contained within this | | Specification | Egress | Dead-end corridors between 15 m (49ft) and 20 m ( 66 ft ) must have at least 30-minutes Fire Rated construction with 30-minute Fire Rated-doors | | Specification | Egress | Dead-end corridors between 15 m (49ft) and 20 m ( 66 ft ) must have a cross corridor Fire Rated Door olaced after the first stair to separate the | | Specification | Egress | Dead-end corridors between 15 m (49ftt) and 20 m ( 66 ft ) must have an immediate fire alarm (no delav) that sounds in all rooms alono the Dead- | | Specification | Egress | A Dead-end corridor areater than 20 m ( 66 ft ) mav be permitted subiect to | | Standard | Egress | Egress routes from Places of Assembly must have capacity proportionate to the occumant load in order to facilitate evacuation in case of | | Specification | Egress | A single Exit is acceptable where the occupant load is less than 60 | | Specification | Egress | A single Exit is acceptable where the there is a management procedure to maintain the cccumant load to less than 60 neonle and the maximum | | Specification | Egress | At least two Remote Exits for 60 to 500 people. |
Specification 规格 Egress 出口 At least three Remote Exits for 501 to 1000 people.
至少有三个远程出口,可容纳 501 到 1000 人。
Specification 规格 Egress 出口 1001 or more people, minimum of four Remote Exits, to be validated by
1001 人或以上,至少四个远程出口,由
Specification 规格 Egress 出口 Two Remote Exits are permitted for up to 1000 people provided they are hoth sized at 5 mm / 5 mm / 5mm//5 \mathrm{~mm} / nerson ( 0 . 2 inches/nerson) and thev are Remote
允许最多容纳 1000 人的两个远程出口,条件是它们的大小为 5 mm / 5 mm / 5mm//5 \mathrm{~mm} / 人(0 .
Specification 规格 Egress 出口 Occupant loads in Places of Assembly must be calculated based on 1.4
集会场所的乘员负荷必须根据 1.4 计算。
Specification 规格 Egress 出口 All Exit Doors from Places of Assembly must open in the direction of
集会场所的所有出口门必须朝以下方向开启
Standard 标准 Egress 出口 Exit doors throughout the building must be openable at all times in case of emercencv or power loss to avoid the risk of entraoment.
在紧急情况下或停电时,整栋大楼的出口门必须随时可以打开,以避免人员被困的危险。
Specification 规格 Egress 出口 Exit Doors into Exit Stairs and Final Exit Doors must open in the direction
进入疏散楼梯的出口门和最终出口门必须朝以下方向开启
Specification 规格 Egress 出口 Exit Doors into Exit Stairs must be openable from both sides in the event of a fire alarm to allow occupants to leave the stair if conditions are not
进入疏散楼梯的出口门必须能在火警发生时从两侧打开,以便在条件不允许时让住户离开楼梯。
Specification 规格 Egress 出口 Exit Door hardware must allow occupants to open the door in one motion (e a nanic hardware fire exit hardware dor hardware that overrides a
出口门硬件必须能让居住者在一个动作中打开门(例如,一个纳米硬件,一个防火出口硬件,或一个能覆盖防火门的硬件)。
Specification 规格 Egress 出口 Exit Doors that are fitted with access control or Electronic Door Lock must automatically release unon actuation of the fire alarm and detection
装有门禁控制装置或电子门锁的出口门必须在火警和探测装置启动时自动打开。
Guideline 指导原则 Egress 出口 Depending on the location of the the Exit Doors, consideration should be given to whether green 'break glass' points should be installed to allow building occupants egress in case of emergency prior to fire alarm
根据出口门的位置,应考虑是否应安装绿色 "碎玻璃 "点,以便在火灾警报响起前的紧急情况下让楼内人员逃生。
Standard 标准 Egress 出口 Exit Stairwells throughout the building must be Fire Rated to provide occunants a protected Earess route to a Final Exit in case of fire.
整个建筑的出口楼梯间必须达到防火等级,以便在发生火灾时为人员提供一条通往最终出口的受保护通道。
Specification 规格 Egress 出口 Exit Stairwells in Low-rise and Medium-rise buildings must be at least 60-
低层和中层建筑的出口楼梯间必须至少有 60-
Specification 规格 Egress 出口 Exit Stairwells in a High-rise building must be at least 90-minutes Fire
高层建筑的出口楼梯间必须至少有 90 分钟的消防时间。
Specification 规格 Egress 出口 Exit Stairwells in a Super High-rise building must be at least 120-minutes
超高层建筑的出口楼梯间必须至少为 120 分钟
Specification 规格 Egress 出口 Exterior Exit Stairs must be protected from fire exposure from a fire
室外出口楼梯必须采取保护措施,以防火灾时受到火势影响
Specification 规格 Egress 出口 Where the Fire Resistance of an Exit Stairwell (Shaft) is unknown then visual inspections must confirm they are of solid (no obvious Unprotected
如果出口楼梯间(竖井)的耐火性能不明,则必须进行目视检查,以确认它们是坚固的(没有明显的无保护层)。
Standard 标准 Egress 出口 Exit Stairs throughout the building must include provisions which address the risk of occubants triboing or falling durina emercencv Earess.
整个建筑的逃生梯必须包括解决紧急情况下人员摔倒或坠落风险的规定。
Specification 规格 Egress 出口 A handrail must be provided on both sides of the staircase. For staircases that are wider than 1.8 m (5.9ft) a handrail must be available within
楼梯两侧必须有扶手。宽度超过 1.8 米(5.9 英尺)的楼梯必须在以下范围内安装扶手
Specification 规格 Egress 出口 A handrail or combined guard/handrail must be provided at a useable height and on at least one side of the stair. For staircases that are wider
必须在楼梯至少一边的可使用高度上设置扶手或组合护栏/扶手。对于较宽的楼梯
Specification 规格 Egress 出口 Stairs must be continuously illuminated or immediately illuminate upon
楼梯必须持续照明,或在发生下列情况时立即照明
Specification 规格 Egress 出口 Exit Stairs must have landings at floor levels, intermediate floor levels
出口楼梯必须在楼层和中间楼层设有楼梯平台
Specification 规格 Egress 出口 Stair-risers and stair treads must be dimensionally uniform within the
楼梯扶手和楼梯踏步的尺寸必须在以下范围内保持一致
Specification 规格 Egress 出口 The tolerance between the largest and smallest riser height or between the largest and smallest tread denth must not exceed 10mm (0 4in) in
最大和最小立管高度之间或最大和最小胎面深度之间的公差不得超过 10 毫米(0.4 英寸)。
Specification 规格 Egress 出口 Where the tolerance between the largest and smallest tread depth exceeds 10 mm ( 0 4in) then warning signage and foor markinos must he
如果最大和最小胎面深度之间的误差超过 10 毫米(0.4 英寸),则必须设置警告标志和路面标记。
Specification 规格 Egress 出口 Exterior Exit Stairs must be of Slip-Resistant construction.
室外出口楼梯必须采用防滑结构。
Specification 规格 Egress 出口 Spiral or curved stairs are permitted as a Fire Escape provided all treads are identical tread denth is at least 190 mm / 7 190 mm / 7 190mm//7190 \mathrm{~mm} / 7 5in L at a noint 303 mm
允许将螺旋楼梯或弧形楼梯作为消防通道,但所有踏板必须完全相同,踏板间距至少 190 mm / 7 190 mm / 7 190mm//7190 \mathrm{~mm} / 7 5 英寸长(303 毫米)。
Specification 规格 Egress 出口 Existing External Fire Escape Ladders must be approved bv a Qualified
现有的室外消防梯必须由合格的消防工程师批准。
Standard 标准 Egress 出口 Exit Stairwells throughout High-rise and Super High-rise buildings must include numbered floor level signage to orientate Exit Stair users, to facilitate evacuation and efficient firefighting response in case of
高层和超高层建筑的出口楼梯间必须有编号的楼层指示牌,为出口楼梯的使用者指明方向,以便在发生以下情况时进行疏散和有效的消防响应
Specification 规格 Egress 出口 Numbers must be at least 150 mm ( 6 in ) hiah.
数字必须至少 150 毫米(6 英寸)高。
Specification 规格 Egress 出口 Numbers must have a reflective finish that contrasts with the
数字必须具有反光效果,与
Specification 规格 Egress 出口 Numbers must be located 1.5 m (5ft) above the floor landing.
编号必须位于地面以上 1.5 米(5 英尺)处。
Specification 规格 Egress 出口 Numbers must be positioned to be clearlv visible when the
数字的位置必须清晰可见。
Specification 规格 Egress 出口 Existing labelling can be accepted if the intent of the OBS is achieved
如果实现了开放式保税仓库的目的,现有的标签可以接受
Standard 标准 Egress 出口 Exit Stairwells in High-rise and Super High-rise buildings must have protection adainst smoke ingress to support safe Earess in case of fire
高层和超高层建筑的出口楼梯间必须有防止烟雾进入的保护措施,以便在发生火灾时支持安全出口
Specification 规格 Egress 出口 Smoke ingress into the Exit Stairwell must be-minimized by one of the
必须采取以下措施之一,尽量减少烟雾进入出口楼梯井
Specification 规格 Egress 出口 Mechanical Exit Stairwell pressurisation.
机械出口楼梯间加压。
Specification 规格 Egress 出口 Access to the Exit Stairwell through a Fire Lobby protected by a mechanical Smoke Management Svstem. The Fire Lobbv is required at
通过由机械烟雾管理系统保护的消防通道进入出口楼梯井。消防通道必须位于
Specification 规格 Egress 出口 Access to the Exit Stairwell via a Fire Rated corridor protected by a mechanical Smoke Management Svstem. The Fire Rated corridor is
通过由机械烟雾管理系统保护的防火走廊进入出口楼梯井。防火走廊是
Specification 规格 Egress 出口 Access to the Exit Stairwell through an open exterior lobby or balcony.
通过开放式室外大厅或阳台进入出口楼梯井。
Specification Egress At least three Remote Exits for 501 to 1000 people. Specification Egress 1001 or more people, minimum of four Remote Exits, to be validated by Specification Egress Two Remote Exits are permitted for up to 1000 people provided they are hoth sized at 5mm// nerson ( 0 . 2 inches/nerson) and thev are Remote Specification Egress Occupant loads in Places of Assembly must be calculated based on 1.4 Specification Egress All Exit Doors from Places of Assembly must open in the direction of Standard Egress Exit doors throughout the building must be openable at all times in case of emercencv or power loss to avoid the risk of entraoment. Specification Egress Exit Doors into Exit Stairs and Final Exit Doors must open in the direction Specification Egress Exit Doors into Exit Stairs must be openable from both sides in the event of a fire alarm to allow occupants to leave the stair if conditions are not Specification Egress Exit Door hardware must allow occupants to open the door in one motion (e a nanic hardware fire exit hardware dor hardware that overrides a Specification Egress Exit Doors that are fitted with access control or Electronic Door Lock must automatically release unon actuation of the fire alarm and detection Guideline Egress Depending on the location of the the Exit Doors, consideration should be given to whether green 'break glass' points should be installed to allow building occupants egress in case of emergency prior to fire alarm Standard Egress Exit Stairwells throughout the building must be Fire Rated to provide occunants a protected Earess route to a Final Exit in case of fire. Specification Egress Exit Stairwells in Low-rise and Medium-rise buildings must be at least 60- Specification Egress Exit Stairwells in a High-rise building must be at least 90-minutes Fire Specification Egress Exit Stairwells in a Super High-rise building must be at least 120-minutes Specification Egress Exterior Exit Stairs must be protected from fire exposure from a fire Specification Egress Where the Fire Resistance of an Exit Stairwell (Shaft) is unknown then visual inspections must confirm they are of solid (no obvious Unprotected Standard Egress Exit Stairs throughout the building must include provisions which address the risk of occubants triboing or falling durina emercencv Earess. Specification Egress A handrail must be provided on both sides of the staircase. For staircases that are wider than 1.8 m (5.9ft) a handrail must be available within Specification Egress A handrail or combined guard/handrail must be provided at a useable height and on at least one side of the stair. For staircases that are wider Specification Egress Stairs must be continuously illuminated or immediately illuminate upon Specification Egress Exit Stairs must have landings at floor levels, intermediate floor levels Specification Egress Stair-risers and stair treads must be dimensionally uniform within the Specification Egress The tolerance between the largest and smallest riser height or between the largest and smallest tread denth must not exceed 10mm (0 4in) in Specification Egress Where the tolerance between the largest and smallest tread depth exceeds 10 mm ( 0 4in) then warning signage and foor markinos must he Specification Egress Exterior Exit Stairs must be of Slip-Resistant construction. Specification Egress Spiral or curved stairs are permitted as a Fire Escape provided all treads are identical tread denth is at least 190mm//7 5in L at a noint 303 mm Specification Egress Existing External Fire Escape Ladders must be approved bv a Qualified Standard Egress Exit Stairwells throughout High-rise and Super High-rise buildings must include numbered floor level signage to orientate Exit Stair users, to facilitate evacuation and efficient firefighting response in case of Specification Egress Numbers must be at least 150 mm ( 6 in ) hiah. Specification Egress Numbers must have a reflective finish that contrasts with the Specification Egress Numbers must be located 1.5 m (5ft) above the floor landing. Specification Egress Numbers must be positioned to be clearlv visible when the Specification Egress Existing labelling can be accepted if the intent of the OBS is achieved Standard Egress Exit Stairwells in High-rise and Super High-rise buildings must have protection adainst smoke ingress to support safe Earess in case of fire Specification Egress Smoke ingress into the Exit Stairwell must be-minimized by one of the Specification Egress Mechanical Exit Stairwell pressurisation. Specification Egress Access to the Exit Stairwell through a Fire Lobby protected by a mechanical Smoke Management Svstem. The Fire Lobbv is required at Specification Egress Access to the Exit Stairwell via a Fire Rated corridor protected by a mechanical Smoke Management Svstem. The Fire Rated corridor is Specification Egress Access to the Exit Stairwell through an open exterior lobby or balcony.| Specification | Egress | At least three Remote Exits for 501 to 1000 people. | | :---: | :---: | :---: | | Specification | Egress | 1001 or more people, minimum of four Remote Exits, to be validated by | | Specification | Egress | Two Remote Exits are permitted for up to 1000 people provided they are hoth sized at $5 \mathrm{~mm} /$ nerson ( 0 . 2 inches/nerson) and thev are Remote | | Specification | Egress | Occupant loads in Places of Assembly must be calculated based on 1.4 | | Specification | Egress | All Exit Doors from Places of Assembly must open in the direction of | | Standard | Egress | Exit doors throughout the building must be openable at all times in case of emercencv or power loss to avoid the risk of entraoment. | | Specification | Egress | Exit Doors into Exit Stairs and Final Exit Doors must open in the direction | | Specification | Egress | Exit Doors into Exit Stairs must be openable from both sides in the event of a fire alarm to allow occupants to leave the stair if conditions are not | | Specification | Egress | Exit Door hardware must allow occupants to open the door in one motion (e a nanic hardware fire exit hardware dor hardware that overrides a | | Specification | Egress | Exit Doors that are fitted with access control or Electronic Door Lock must automatically release unon actuation of the fire alarm and detection | | Guideline | Egress | Depending on the location of the the Exit Doors, consideration should be given to whether green 'break glass' points should be installed to allow building occupants egress in case of emergency prior to fire alarm | | Standard | Egress | Exit Stairwells throughout the building must be Fire Rated to provide occunants a protected Earess route to a Final Exit in case of fire. | | Specification | Egress | Exit Stairwells in Low-rise and Medium-rise buildings must be at least 60- | | Specification | Egress | Exit Stairwells in a High-rise building must be at least 90-minutes Fire | | Specification | Egress | Exit Stairwells in a Super High-rise building must be at least 120-minutes | | Specification | Egress | Exterior Exit Stairs must be protected from fire exposure from a fire | | Specification | Egress | Where the Fire Resistance of an Exit Stairwell (Shaft) is unknown then visual inspections must confirm they are of solid (no obvious Unprotected | | Standard | Egress | Exit Stairs throughout the building must include provisions which address the risk of occubants triboing or falling durina emercencv Earess. | | Specification | Egress | A handrail must be provided on both sides of the staircase. For staircases that are wider than 1.8 m (5.9ft) a handrail must be available within | | Specification | Egress | A handrail or combined guard/handrail must be provided at a useable height and on at least one side of the stair. For staircases that are wider | | Specification | Egress | Stairs must be continuously illuminated or immediately illuminate upon | | Specification | Egress | Exit Stairs must have landings at floor levels, intermediate floor levels | | Specification | Egress | Stair-risers and stair treads must be dimensionally uniform within the | | Specification | Egress | The tolerance between the largest and smallest riser height or between the largest and smallest tread denth must not exceed 10mm (0 4in) in | | Specification | Egress | Where the tolerance between the largest and smallest tread depth exceeds 10 mm ( 0 4in) then warning signage and foor markinos must he | | Specification | Egress | Exterior Exit Stairs must be of Slip-Resistant construction. | | Specification | Egress | Spiral or curved stairs are permitted as a Fire Escape provided all treads are identical tread denth is at least $190 \mathrm{~mm} / 7$ 5in L at a noint 303 mm | | Specification | Egress | Existing External Fire Escape Ladders must be approved bv a Qualified | | Standard | Egress | Exit Stairwells throughout High-rise and Super High-rise buildings must include numbered floor level signage to orientate Exit Stair users, to facilitate evacuation and efficient firefighting response in case of | | Specification | Egress | Numbers must be at least 150 mm ( 6 in ) hiah. | | Specification | Egress | Numbers must have a reflective finish that contrasts with the | | Specification | Egress | Numbers must be located 1.5 m (5ft) above the floor landing. | | Specification | Egress | Numbers must be positioned to be clearlv visible when the | | Specification | Egress | Existing labelling can be accepted if the intent of the OBS is achieved | | Standard | Egress | Exit Stairwells in High-rise and Super High-rise buildings must have protection adainst smoke ingress to support safe Earess in case of fire | | Specification | Egress | Smoke ingress into the Exit Stairwell must be-minimized by one of the | | Specification | Egress | Mechanical Exit Stairwell pressurisation. | | Specification | Egress | Access to the Exit Stairwell through a Fire Lobby protected by a mechanical Smoke Management Svstem. The Fire Lobbv is required at | | Specification | Egress | Access to the Exit Stairwell via a Fire Rated corridor protected by a mechanical Smoke Management Svstem. The Fire Rated corridor is | | Specification | Egress | Access to the Exit Stairwell through an open exterior lobby or balcony. |
Specification 规格 Egress 出口 Access to the Exit Stairwell through a naturally ventilated lobby. Operable windows would need to open automatically upon fire alarm activation The Jobby is reawired at everv flom level
通过自然通风的大厅进入出口楼梯井。可操作窗户需要在火警启动时自动打开。
Standard 标准 Egress 出口 Egress routes throughout the building must be illuminated-to allow
整个建筑的逃生通道必须有照明,以便
Specification 规格 Egress 出口 Automatic Emergency Lighting must be provided along Egress routes.
逃生通道上必须安装自动应急照明。
Specification 规格 Egress 出口 Automatic Emergencv Liahting must be provided in anv area where there
必须在有以下设施的区域提供自动应急联络系统
Specification 规格 Egress 出口 Automatic Emergencv Liahtina must be provided in Public Areas.
公共区域必须配备自动紧急联络器。
Specification 规格 Egress 出口 Automatic Emergency Lighting must be provided in Back of House areas
后院区域必须提供自动应急照明
Specification 规格 Egress 出口 Automatic Emergency Lighting must provide an average of 10 lux (1 foot candle) at flor level and a minimum of 1 lux ( 1 - font candle) at anv
自动应急照明必须在水平面平均提供 10 勒克斯(1 英尺烛光),在垂直面至少提供 1 勒克斯(1-字体烛光)。
Standard 标准 Egress 出口 Exit signage must be provided throughout the building to guide occupants to the Final Exits in case of emergency.
必须在整个建筑内设置出口指示牌,以便在紧急情况下引导住户前往最终出口。
Specification 规格 Egress 出口
A diagram/map showing the Egress route to the nearest Exit Stair or
显示通往最近的出口楼梯或通道的出口路线的图表/地图。
A diagram/map showing the Egress route to the nearest Exit Stair or https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-08.jpg?height=33&width=1024&top_left_y=696&top_left_x=861| A diagram/map showing the Egress route to the nearest Exit Stair or | | :--- | | ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-08.jpg?height=33&width=1024&top_left_y=696&top_left_x=861) |
Specification 规格 Egress 出口 Guest Room doors which discharge directly to Exterior Egress routes (up to 3 storevs) do not reawire an exit diadram/man on the room side of the
直接通向室外出口通道的客房门(最多 3 层)不需要在房间一侧重新布线出口指示灯/指示人。
Specification 规格 Egress 出口 Exit signs are required at each Exit Stair and the Final Exit.
每个出口楼梯和最后出口都需要出口标志。
Specification 规格 Egress 出口 Directional exit signage must be provided when the Exit is not
当出口不属于以下情况时,必须设置出口指示牌
Specification 规格 Egress 出口 Exit signage, except within Guest Rooms, must be backlit or illuminated bv normal and Fmeraencv Liahtina that automatically comes on when the
除客房内的出口指示牌外,其他出口指示牌必须为背光或正常照明,并在发生火灾时自动亮起。
Specification 规格 Egress 出口 Emergency power must be provided to illuminate signage for a minimum
必须提供应急电源,以照亮标识牌至少
Specification 规格 Egress 出口 Exit signs are not required in any non-Guest Room, with one door.
只有一扇门的非客房不需要出口标志。
Specification 规格 Egress 出口 All exit signs must be in the local language(s) and English, or as a
所有出口指示牌都必须使用当地语言和英语,或以"...... "的形式出现。
Standard 标准 Egress 出口 Fire safety provisions in High-rise and Super-high rise buildings must include measures which address the extended evacuation periods associated with such hurldinos (comnared to لمlow or medium rise
高层和超高层建筑的消防安全规定必须包括一些措施,以解决与此类飓风(与 لم 低层或中层建筑相比)相关的疏散时间延长的问题。
Specification 规格 Egress 出口 A Fire Strateav developed by a Qualified Person is required for Super
超级消防站需要有合格人员制定的消防策略。
Specification 规格 Egress 出口

高层和超高层建筑必须由固定式防火系统提供全面保护,该系统的设计和安装必须符合以下标准
High-rise and Super High-rise buildings must be protected throughout by
a Fixed Fire Sunnression Svstem desianed and installed to an
High-rise and Super High-rise buildings must be protected throughout by a Fixed Fire Sunnression Svstem desianed and installed to an| High-rise and Super High-rise buildings must be protected throughout by | | :--- | | a Fixed Fire Sunnression Svstem desianed and installed to an |
Specification 规格 Egress 出口 Hiah-rise and Super Hiah-rise buildings must be protected throughout by
高层和超高层建筑必须通过以下措施提供全面保护
Specification 规格 Egress 出口 A Lift serving all occupied floors must be provided in High-rise and Super High-rise for use in fire-fighting operations and for evacuation of persons with rodured mohility Rocian of the lift and aconciatod Chaft/lobhbe muct
高层建筑和超高层建筑必须为所有有人居住的楼层配备一部电梯,用于消防作业和疏散有残疾的人员。
Standard 标准 Fire spread - linings 火灾蔓延 - 衬里 The-wall and ceiling linings in corridors and Exit Stairwells must include measures for resisting oronagation of fire and smoke-to orotect Earess
走廊和出口楼梯间的墙壁和天花板衬里必须包括防止火灾和烟雾扩散到出口的措施。
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Wall and ceiling linings must be painted gypsum, plaster or similar NonCombustible material or walloaver thickness must not exceed 0.9 mm .
墙壁和天花板内衬必须是油漆石膏、灰泥或类似的不燃材料,或墙纸厚度不得超过 0.9 毫米。
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Wallpaper thickness in corridors and Exit Stairwells must not exceed
走廊和出口楼梯间的壁纸厚度不得超过
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Any other ceiling/wall lining material must be fire tested to an
任何其他天花板/墙壁衬里材料都必须经过防火测试,达到
Standard 标准 Fire spread - linings 火灾蔓延 - 衬里 The wall and celiling linings in Places of Assembly with more than 500 occupants must include measures for resisting propagation of fire and smoke to manage the risk of fire and smoke snread overwhelmina the
居住人数超过 500 人的集会场所的墙壁和天花板衬里必须包括抵御火灾和烟雾传播的措施, 以控制火灾和烟雾蔓延的风险a
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Wall and ceiling liningsmust be painted gypsum, plaster or similar NonCombustible material or wallpaper thickness must not exceed 0.9 mm .
墙壁和天花板衬里必须是油漆石膏、石膏或类似的不燃材料,或墙纸厚度不得超过 0.9 毫米。
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Wallpaper thickness in Places of Assembly with more than 500
超过 500 个集会场所的壁纸厚度
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Any other ceiling/wall lining material must be fire tested to an
任何其他天花板/墙壁衬里材料都必须经过防火测试,达到
Specification 规格 Fire spread - linings 火灾蔓延 - 衬里 Combustible linings are permitted without fire testing up to a maximum
允许使用可燃衬里,无需进行防火测试,但最高不得超过
Standard 标准 Fire spread - suppression
火灾蔓延 - 抑制
Commercial Cooking Ranges in kitchens must have measures to adress the risk of kitchen fires soreadina ravidlv and impeding or obstructina
厨房中的商用灶具必须采取措施应对厨房火灾的风险,并防止妨碍或阻碍厨房的正常运作。
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
Commercial Cookina Ranges must have a Fixed Fire Suppression
商用炉灶必须配备固定灭火装置
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
The Fixed Fire Suppression Svstem must be operated automaticallv with
固定式灭火系统必须在下列情况下自动运行
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
Activation of the Fixed Fire Suppression Svstem must automatically turn
固定灭火系统启动后必须自动转为自动灭火系统。
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
The Fixed Fire Suppression System must-require manual reset after it has activated in order to restore fuel subolv to cookind equipment.
固定灭火系统启动后必须手动复位,以恢复烹饪设备的燃料。
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
The Fixed Fire Suppression Svstem must be connected to the fire alarm
固定灭火系统必须与火警系统相连接。
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
A third partv tested and certified automatic Fixed Fire Suppression
第三部分v 经过测试和认证的自动固定灭火系统
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
Where the Commercial Cooking Range is in a separate Low-rise building with no Guest Roms then a Fixed Fire Sunnression Svstem is not
如果商用灶台位于单独的低层建筑内,且没有客房,则不需要固定式防火系统。
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
To prevent grease build-up in commercial kitchen hoods a contract must he in nlace for reaular snecialist cleanind of the kitchen extractor hood (s)
为防止商用厨房抽油烟机油脂积聚,必须签订定期专业清洁厨房抽油烟机的合同。
Standard 标准 Fire spread - suppression
火灾蔓延 - 抑制
Fire extinguishing equipment must be provided throughout the building to allow for extinquishind a fire in its earliest stades. oreventina fire from
必须在整个建筑内配备灭火设备,以便在火灾发生初期将其扑灭。
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
Fire extinquishers must be provided throughout the buildina based on the
必须根据以下情况在整个建筑内配备灭火器
Specification 规格 Fire spread - suppression
火灾蔓延 - 抑制
The maximum travel distance to a fire extinquisher must not exceed 25m
到灭火器的最大距离不得超过 25 米
Specification Egress Access to the Exit Stairwell through a naturally ventilated lobby. Operable windows would need to open automatically upon fire alarm activation The Jobby is reawired at everv flom level Standard Egress Egress routes throughout the building must be illuminated-to allow Specification Egress Automatic Emergency Lighting must be provided along Egress routes. Specification Egress Automatic Emergencv Liahting must be provided in anv area where there Specification Egress Automatic Emergencv Liahtina must be provided in Public Areas. Specification Egress Automatic Emergency Lighting must be provided in Back of House areas Specification Egress Automatic Emergency Lighting must provide an average of 10 lux (1 foot candle) at flor level and a minimum of 1 lux ( 1 - font candle) at anv Standard Egress Exit signage must be provided throughout the building to guide occupants to the Final Exits in case of emergency. Specification Egress "A diagram/map showing the Egress route to the nearest Exit Stair or https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-08.jpg?height=33&width=1024&top_left_y=696&top_left_x=861" Specification Egress Guest Room doors which discharge directly to Exterior Egress routes (up to 3 storevs) do not reawire an exit diadram/man on the room side of the Specification Egress Exit signs are required at each Exit Stair and the Final Exit. Specification Egress Directional exit signage must be provided when the Exit is not Specification Egress Exit signage, except within Guest Rooms, must be backlit or illuminated bv normal and Fmeraencv Liahtina that automatically comes on when the Specification Egress Emergency power must be provided to illuminate signage for a minimum Specification Egress Exit signs are not required in any non-Guest Room, with one door. Specification Egress All exit signs must be in the local language(s) and English, or as a Standard Egress Fire safety provisions in High-rise and Super-high rise buildings must include measures which address the extended evacuation periods associated with such hurldinos (comnared to لمlow or medium rise Specification Egress A Fire Strateav developed by a Qualified Person is required for Super Specification Egress "High-rise and Super High-rise buildings must be protected throughout by a Fixed Fire Sunnression Svstem desianed and installed to an" Specification Egress Hiah-rise and Super Hiah-rise buildings must be protected throughout by Specification Egress A Lift serving all occupied floors must be provided in High-rise and Super High-rise for use in fire-fighting operations and for evacuation of persons with rodured mohility Rocian of the lift and aconciatod Chaft/lobhbe muct Standard Fire spread - linings The-wall and ceiling linings in corridors and Exit Stairwells must include measures for resisting oronagation of fire and smoke-to orotect Earess Specification Fire spread - linings Wall and ceiling linings must be painted gypsum, plaster or similar NonCombustible material or walloaver thickness must not exceed 0.9 mm . Specification Fire spread - linings Wallpaper thickness in corridors and Exit Stairwells must not exceed Specification Fire spread - linings Any other ceiling/wall lining material must be fire tested to an Standard Fire spread - linings The wall and celiling linings in Places of Assembly with more than 500 occupants must include measures for resisting propagation of fire and smoke to manage the risk of fire and smoke snread overwhelmina the Specification Fire spread - linings Wall and ceiling liningsmust be painted gypsum, plaster or similar NonCombustible material or wallpaper thickness must not exceed 0.9 mm . Specification Fire spread - linings Wallpaper thickness in Places of Assembly with more than 500 Specification Fire spread - linings Any other ceiling/wall lining material must be fire tested to an Specification Fire spread - linings Combustible linings are permitted without fire testing up to a maximum Standard Fire spread - suppression Commercial Cooking Ranges in kitchens must have measures to adress the risk of kitchen fires soreadina ravidlv and impeding or obstructina Specification Fire spread - suppression Commercial Cookina Ranges must have a Fixed Fire Suppression Specification Fire spread - suppression The Fixed Fire Suppression Svstem must be operated automaticallv with Specification Fire spread - suppression Activation of the Fixed Fire Suppression Svstem must automatically turn Specification Fire spread - suppression The Fixed Fire Suppression System must-require manual reset after it has activated in order to restore fuel subolv to cookind equipment. Specification Fire spread - suppression The Fixed Fire Suppression Svstem must be connected to the fire alarm Specification Fire spread - suppression A third partv tested and certified automatic Fixed Fire Suppression Specification Fire spread - suppression Where the Commercial Cooking Range is in a separate Low-rise building with no Guest Roms then a Fixed Fire Sunnression Svstem is not Specification Fire spread - suppression To prevent grease build-up in commercial kitchen hoods a contract must he in nlace for reaular snecialist cleanind of the kitchen extractor hood (s) Standard Fire spread - suppression Fire extinguishing equipment must be provided throughout the building to allow for extinquishind a fire in its earliest stades. oreventina fire from Specification Fire spread - suppression Fire extinquishers must be provided throughout the buildina based on the Specification Fire spread - suppression The maximum travel distance to a fire extinquisher must not exceed 25m| Specification | Egress | Access to the Exit Stairwell through a naturally ventilated lobby. Operable windows would need to open automatically upon fire alarm activation The Jobby is reawired at everv flom level | | :---: | :---: | :---: | | Standard | Egress | Egress routes throughout the building must be illuminated-to allow | | Specification | Egress | Automatic Emergency Lighting must be provided along Egress routes. | | Specification | Egress | Automatic Emergencv Liahting must be provided in anv area where there | | Specification | Egress | Automatic Emergencv Liahtina must be provided in Public Areas. | | Specification | Egress | Automatic Emergency Lighting must be provided in Back of House areas | | Specification | Egress | Automatic Emergency Lighting must provide an average of 10 lux (1 foot candle) at flor level and a minimum of 1 lux ( 1 - font candle) at anv | | Standard | Egress | Exit signage must be provided throughout the building to guide occupants to the Final Exits in case of emergency. | | Specification | Egress | A diagram/map showing the Egress route to the nearest Exit Stair or <br> ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-08.jpg?height=33&width=1024&top_left_y=696&top_left_x=861) | | Specification | Egress | Guest Room doors which discharge directly to Exterior Egress routes (up to 3 storevs) do not reawire an exit diadram/man on the room side of the | | Specification | Egress | Exit signs are required at each Exit Stair and the Final Exit. | | Specification | Egress | Directional exit signage must be provided when the Exit is not | | Specification | Egress | Exit signage, except within Guest Rooms, must be backlit or illuminated bv normal and Fmeraencv Liahtina that automatically comes on when the | | Specification | Egress | Emergency power must be provided to illuminate signage for a minimum | | Specification | Egress | Exit signs are not required in any non-Guest Room, with one door. | | Specification | Egress | All exit signs must be in the local language(s) and English, or as a | | Standard | Egress | Fire safety provisions in High-rise and Super-high rise buildings must include measures which address the extended evacuation periods associated with such hurldinos (comnared to لمlow or medium rise | | Specification | Egress | A Fire Strateav developed by a Qualified Person is required for Super | | Specification | Egress | High-rise and Super High-rise buildings must be protected throughout by <br> a Fixed Fire Sunnression Svstem desianed and installed to an | | Specification | Egress | Hiah-rise and Super Hiah-rise buildings must be protected throughout by | | Specification | Egress | A Lift serving all occupied floors must be provided in High-rise and Super High-rise for use in fire-fighting operations and for evacuation of persons with rodured mohility Rocian of the lift and aconciatod Chaft/lobhbe muct | | Standard | Fire spread - linings | The-wall and ceiling linings in corridors and Exit Stairwells must include measures for resisting oronagation of fire and smoke-to orotect Earess | | Specification | Fire spread - linings | Wall and ceiling linings must be painted gypsum, plaster or similar NonCombustible material or walloaver thickness must not exceed 0.9 mm . | | Specification | Fire spread - linings | Wallpaper thickness in corridors and Exit Stairwells must not exceed | | Specification | Fire spread - linings | Any other ceiling/wall lining material must be fire tested to an | | Standard | Fire spread - linings | The wall and celiling linings in Places of Assembly with more than 500 occupants must include measures for resisting propagation of fire and smoke to manage the risk of fire and smoke snread overwhelmina the | | Specification | Fire spread - linings | Wall and ceiling liningsmust be painted gypsum, plaster or similar NonCombustible material or wallpaper thickness must not exceed 0.9 mm . | | Specification | Fire spread - linings | Wallpaper thickness in Places of Assembly with more than 500 | | Specification | Fire spread - linings | Any other ceiling/wall lining material must be fire tested to an | | Specification | Fire spread - linings | Combustible linings are permitted without fire testing up to a maximum | | Standard | Fire spread - suppression | Commercial Cooking Ranges in kitchens must have measures to adress the risk of kitchen fires soreadina ravidlv and impeding or obstructina | | Specification | Fire spread - suppression | Commercial Cookina Ranges must have a Fixed Fire Suppression | | Specification | Fire spread - suppression | The Fixed Fire Suppression Svstem must be operated automaticallv with | | Specification | Fire spread - suppression | Activation of the Fixed Fire Suppression Svstem must automatically turn | | Specification | Fire spread - suppression | The Fixed Fire Suppression System must-require manual reset after it has activated in order to restore fuel subolv to cookind equipment. | | Specification | Fire spread - suppression | The Fixed Fire Suppression Svstem must be connected to the fire alarm | | Specification | Fire spread - suppression | A third partv tested and certified automatic Fixed Fire Suppression | | Specification | Fire spread - suppression | Where the Commercial Cooking Range is in a separate Low-rise building with no Guest Roms then a Fixed Fire Sunnression Svstem is not | | Specification | Fire spread - suppression | To prevent grease build-up in commercial kitchen hoods a contract must he in nlace for reaular snecialist cleanind of the kitchen extractor hood (s) | | Standard | Fire spread - suppression | Fire extinguishing equipment must be provided throughout the building to allow for extinquishind a fire in its earliest stades. oreventina fire from | | Specification | Fire spread - suppression | Fire extinquishers must be provided throughout the buildina based on the | | Specification | Fire spread - suppression | The maximum travel distance to a fire extinquisher must not exceed 25m |
Standard 标准 Fire Resistance 防火性能 The Structure of the building must have adequate Fire Resistance to maintain stabilitv for occupant Earess. to protect firefiahters and to
建筑物的结构必须具有足够的耐火性能,以保持稳定,便于居住、保护消防人员和
Specification 规格 Fire Resistance 防火性能 The Structure of a Low-rise or Medium-rise building must have a
低层或中层建筑的结构必须具有
Specification 规格 Fire Resistance 防火性能 The Structure of a Hiah-rise buildina must have a minimum Fire
高层建筑的结构必须具备最低防火要求。
Specification 规格 Fire Resistance 防火性能 The Structure of a Super Hiah-rise buildina must have a minimum Fire
超高层建筑的结构必须具备最低防火要求。
Specification 规格 Fire Resistance 防火性能
Mass Timber Structure is permitted to be exposed in Low-rise or Medium-rise buildings provided the Fire Resistance of the Mass Timber
允许在低层或中层建筑中外露大体量木结构,但大体量木结构的耐火等级必须满足以下条件
Mass Timber Structure is permitted to be exposed in Low-rise or Medium-rise buildings provided the Fire Resistance of the Mass Timber https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-09.jpg?height=32&width=907&top_left_y=449&top_left_x=862| Mass Timber Structure is permitted to be exposed in Low-rise or Medium-rise buildings provided the Fire Resistance of the Mass Timber | | :--- | | ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-09.jpg?height=32&width=907&top_left_y=449&top_left_x=862) |
Specification 规格 Fire Resistance 防火性能 Fire Resistance of the Structure of a High-rise Mass Timber building must he achieved hv fire notection usinc a Certified Fire Rated hoardina
高层木结构建筑的耐火性能必须通过经认证的防火墙来实现。
Specification 规格 Fire Resistance 防火性能 The Structure of a Super High-rise building must be Non-Combustible.
超高层建筑的结构必须是不可燃的。
Specification 规格 Fire Resistance 防火性能 Modular Construction is permitted for Low-rise and Medium-rise buildings onlv
低层和中层建筑允许采用模块化建筑,但必须符合以下条件
Specification 规格 Fire Resistance 防火性能 A Hiah-Rise building constructed usina Modular Construction mav be
使用模块化建筑技术建造的高层建筑可以是
Specification 规格 Fire Resistance 防火性能 Where the Fire Resistance of a High-rise building Structure is unknown and it is not protected by a Fixed Fire Suppression System then visual
如果高层建筑结构的耐火性能不明,又没有固定灭火系统保护,则可通过目测
Standard 标准 Fire spread combartmentation
火灾蔓延梳理
Fire rated compartmentation must be provided throughout the building including between floors to address the risk of fire spread and to orotect
必须在整个建筑内(包括楼层之间)设置防火隔间,以应对火灾蔓延的风险,并隔离
Specification 规格 Fire spread - 火势蔓延 - Each floor must be a separate fire compartment equal to its Fire
每层楼都必须有一个独立的防火隔间,其防火隔间等同于其防火墙。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Up to two-stories can be interconnected provided they are of the same occupancy type. Guest Room and non-Guest Room floors must not be interconnected, unless this space forms part of an Atrium, in which case
最多可连接两层楼,但必须是相同的客房类型。客房楼层和非客房楼层不得相互连接,除非该空间构成中庭的一部分,在这种情况下
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
A two-storey lobby connected with a Guest Room floor, in a building without Fixed Fire Suppression System throughout the adjoining areas,
一个两层楼的大堂与一层客房相连,但毗邻区域均未安装固定灭火系统、
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
All Attics not protected by a Fixed Fire Suppression System must be subdivided bv draft stons (fire breaks) into areas that do not exceed
所有没有固定灭火系统保护的阁楼都必须通过通风柱(防火隔离带)将其划分为不超过
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Hazardous Rooms must be separated from Front of House areas by at least 60-minute Fire Rated construction — سeness the huildino is nrotected
危险房间必须与前厅区域至少用 60 分钟的防火建筑分隔开来。
Specification 规格 Fire spread - 火势蔓延 - Walls between Guest Rooms must achieve at least 30-minutes Fire
客房之间的墙壁必须达到至少 30 分钟的防火标准
Specification 规格 Fire spread compartmentation
火灾蔓延分隔

如果建筑隔间的耐火性能不明,则必须进行目视检查,确认隔板为实心结构(无明显的未检测到的附着物),捐赠者的防火等级必须为
Where the Fire Resistance of a building compartment is unknown then visual inspections must confirm partitions are of solid (no obvious
Unnotected Oneninas) construction and the fire ratino of the donors must
Where the Fire Resistance of a building compartment is unknown then visual inspections must confirm partitions are of solid (no obvious Unnotected Oneninas) construction and the fire ratino of the donors must| Where the Fire Resistance of a building compartment is unknown then visual inspections must confirm partitions are of solid (no obvious | | :--- | | Unnotected Oneninas) construction and the fire ratino of the donors must |
Standard 标准 Fire spread compartmentation
火灾蔓延分隔
Shafts throughout the building must be completely enclosed in fire rated construction to address the risk of fire spread between floors and to
整个建筑的竖井必须完全封闭在防火建筑中,以解决楼层之间火势蔓延的风险,并确保
Specification 规格 Fire spread - 火势蔓延 - Shafts must be Fire Rated to achieve the same Fire Resistance as the
竖井必须符合防火标准,以达到与建筑物相同的耐火等级。
Specification 规格 Fire spread - 火势蔓延 - Shafts in a Low-rise and Medium-rise building must be enclosed in at
低层和中层建筑的竖井必须用以下材料封闭
Specification 规格 Fire spread - 火势蔓延 - Shafts in a High-rise building must be enclosed in at least a 90-minute
高层建筑中的竖井必须至少封闭 90 分钟。
Specification 规格 Fire spread - 火势蔓延 - Shafts in a Super High-rise building must be enclosed in at least a 120-
超高层建筑中的竖井必须至少用 120-60 米高的围栏围住。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Where the Fire Resistance of a Shaft is unknown then visual inspections must confirm they are of solid (no obvious Unprotected Openings)
如果不知道竖井的耐火性能,则必须进行目视检查,以确认它们是坚固的(没有明显的无保护开口)。
Specification 规格 Fire spread - 火势蔓延 - A rubbish/laundrv chute must terminate in a Fire Rated room equal to the
垃圾/废料槽的终点必须是一个耐火等级相同的房间。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
The terminus room for a rubbish/laundry chute must be less than 20sq.m ( 215 sd ft ) or an automatic fire damner must he fitted to the hase of the
垃圾/洗衣槽的终点室面积必须小于 20 平方米(215 平方英尺),或者必须在垃圾/洗衣槽的底部安装自动防火阀。
Specification 规格 Fire spread - 火势蔓延 - In buildings with a Fixed Fire Suppression Svstem, the chute must also
在装有固定灭火系统的建筑物中,滑道还必须
Specification 规格 Fire spread - 火势蔓延 - Rubbish and laundry chute doors must be self-closing and have a self
垃圾槽和洗衣槽的门必须是自动关闭的,并有一个自锁装置。
Standard 标准 Fire spread compartmentation
火灾蔓延分隔
Corridors-providing Egress routes from the Guest Rooms to an Exit Stair or Final Exit must be constructed from fire resisting construction to address the risk of fire snread and to nrotect Faresc routec in case of fire
从客房通往出口楼梯或最后出口的走廊必须采用耐火结构,以应对火灾风险,并在发生火灾时保护通道c
Specification 规格 Fire spread comnartmentation
火势蔓延
Guest Room corridors must achieve at least 30-minutes Fire Resistance in L ow-rise and Medium-rise nronerties
在高层和中层建筑中,客房走廊必须达到至少 30 分钟的耐火等级
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Guest Room corridors must achieve at least 60-minutes Fire Resistance in High-rise and Super-High-rise properties.
高层和超高层物业的客房走廊必须达到至少 60 分钟的耐火等级。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Where the Fire Resistance of a corridor is unknown then visual inspections must confirm they are of solid construction (no obvious
如果走廊的耐火性能不明,则必须进行目视检查,确认其结构牢固(没有明显的裂缝)。
Standard 标准 Fire spread combartmentation
火灾蔓延梳理
Openings in fire rated construction throughout the building must manage the risk of fire and smoke soread to orotect Earess routes in case of fire.
整个建筑内防火建筑的开口必须控制火灾和烟雾的风险,以便在发生火灾时确保逃生通道畅通。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
To prevent fire spread through Fire Rated construction, all penetrations between and through fire resisting construction must be fire stopped with
为防止火势通过防火建筑蔓延,防火建筑之间和穿过防火建筑的所有贯穿件都必须用以下材料进行防火封堵
Standard Fire Resistance The Structure of the building must have adequate Fire Resistance to maintain stabilitv for occupant Earess. to protect firefiahters and to Specification Fire Resistance The Structure of a Low-rise or Medium-rise building must have a Specification Fire Resistance The Structure of a Hiah-rise buildina must have a minimum Fire Specification Fire Resistance The Structure of a Super Hiah-rise buildina must have a minimum Fire Specification Fire Resistance "Mass Timber Structure is permitted to be exposed in Low-rise or Medium-rise buildings provided the Fire Resistance of the Mass Timber https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-09.jpg?height=32&width=907&top_left_y=449&top_left_x=862" Specification Fire Resistance Fire Resistance of the Structure of a High-rise Mass Timber building must he achieved hv fire notection usinc a Certified Fire Rated hoardina Specification Fire Resistance The Structure of a Super High-rise building must be Non-Combustible. Specification Fire Resistance Modular Construction is permitted for Low-rise and Medium-rise buildings onlv Specification Fire Resistance A Hiah-Rise building constructed usina Modular Construction mav be Specification Fire Resistance Where the Fire Resistance of a High-rise building Structure is unknown and it is not protected by a Fixed Fire Suppression System then visual Standard Fire spread combartmentation Fire rated compartmentation must be provided throughout the building including between floors to address the risk of fire spread and to orotect Specification Fire spread - Each floor must be a separate fire compartment equal to its Fire Specification Fire spread compartmentation Up to two-stories can be interconnected provided they are of the same occupancy type. Guest Room and non-Guest Room floors must not be interconnected, unless this space forms part of an Atrium, in which case Specification Fire spread compartmentation A two-storey lobby connected with a Guest Room floor, in a building without Fixed Fire Suppression System throughout the adjoining areas, Specification Fire spread compartmentation All Attics not protected by a Fixed Fire Suppression System must be subdivided bv draft stons (fire breaks) into areas that do not exceed Specification Fire spread compartmentation Hazardous Rooms must be separated from Front of House areas by at least 60-minute Fire Rated construction — سeness the huildino is nrotected Specification Fire spread - Walls between Guest Rooms must achieve at least 30-minutes Fire Specification Fire spread compartmentation "Where the Fire Resistance of a building compartment is unknown then visual inspections must confirm partitions are of solid (no obvious Unnotected Oneninas) construction and the fire ratino of the donors must" Standard Fire spread compartmentation Shafts throughout the building must be completely enclosed in fire rated construction to address the risk of fire spread between floors and to Specification Fire spread - Shafts must be Fire Rated to achieve the same Fire Resistance as the Specification Fire spread - Shafts in a Low-rise and Medium-rise building must be enclosed in at Specification Fire spread - Shafts in a High-rise building must be enclosed in at least a 90-minute Specification Fire spread - Shafts in a Super High-rise building must be enclosed in at least a 120- Specification Fire spread compartmentation Where the Fire Resistance of a Shaft is unknown then visual inspections must confirm they are of solid (no obvious Unprotected Openings) Specification Fire spread - A rubbish/laundrv chute must terminate in a Fire Rated room equal to the Specification Fire spread compartmentation The terminus room for a rubbish/laundry chute must be less than 20sq.m ( 215 sd ft ) or an automatic fire damner must he fitted to the hase of the Specification Fire spread - In buildings with a Fixed Fire Suppression Svstem, the chute must also Specification Fire spread - Rubbish and laundry chute doors must be self-closing and have a self Standard Fire spread compartmentation Corridors-providing Egress routes from the Guest Rooms to an Exit Stair or Final Exit must be constructed from fire resisting construction to address the risk of fire snread and to nrotect Faresc routec in case of fire Specification Fire spread comnartmentation Guest Room corridors must achieve at least 30-minutes Fire Resistance in L ow-rise and Medium-rise nronerties Specification Fire spread compartmentation Guest Room corridors must achieve at least 60-minutes Fire Resistance in High-rise and Super-High-rise properties. Specification Fire spread compartmentation Where the Fire Resistance of a corridor is unknown then visual inspections must confirm they are of solid construction (no obvious Standard Fire spread combartmentation Openings in fire rated construction throughout the building must manage the risk of fire and smoke soread to orotect Earess routes in case of fire. Specification Fire spread compartmentation To prevent fire spread through Fire Rated construction, all penetrations between and through fire resisting construction must be fire stopped with| Standard | Fire Resistance | The Structure of the building must have adequate Fire Resistance to maintain stabilitv for occupant Earess. to protect firefiahters and to | | :---: | :---: | :---: | | Specification | Fire Resistance | The Structure of a Low-rise or Medium-rise building must have a | | Specification | Fire Resistance | The Structure of a Hiah-rise buildina must have a minimum Fire | | Specification | Fire Resistance | The Structure of a Super Hiah-rise buildina must have a minimum Fire | | Specification | Fire Resistance | Mass Timber Structure is permitted to be exposed in Low-rise or Medium-rise buildings provided the Fire Resistance of the Mass Timber <br> ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-09.jpg?height=32&width=907&top_left_y=449&top_left_x=862) | | Specification | Fire Resistance | Fire Resistance of the Structure of a High-rise Mass Timber building must he achieved hv fire notection usinc a Certified Fire Rated hoardina | | Specification | Fire Resistance | The Structure of a Super High-rise building must be Non-Combustible. | | Specification | Fire Resistance | Modular Construction is permitted for Low-rise and Medium-rise buildings onlv | | Specification | Fire Resistance | A Hiah-Rise building constructed usina Modular Construction mav be | | Specification | Fire Resistance | Where the Fire Resistance of a High-rise building Structure is unknown and it is not protected by a Fixed Fire Suppression System then visual | | Standard | Fire spread combartmentation | Fire rated compartmentation must be provided throughout the building including between floors to address the risk of fire spread and to orotect | | Specification | Fire spread - | Each floor must be a separate fire compartment equal to its Fire | | Specification | Fire spread compartmentation | Up to two-stories can be interconnected provided they are of the same occupancy type. Guest Room and non-Guest Room floors must not be interconnected, unless this space forms part of an Atrium, in which case | | Specification | Fire spread compartmentation | A two-storey lobby connected with a Guest Room floor, in a building without Fixed Fire Suppression System throughout the adjoining areas, | | Specification | Fire spread compartmentation | All Attics not protected by a Fixed Fire Suppression System must be subdivided bv draft stons (fire breaks) into areas that do not exceed | | Specification | Fire spread compartmentation | Hazardous Rooms must be separated from Front of House areas by at least 60-minute Fire Rated construction — سeness the huildino is nrotected | | Specification | Fire spread - | Walls between Guest Rooms must achieve at least 30-minutes Fire | | Specification | Fire spread compartmentation | Where the Fire Resistance of a building compartment is unknown then visual inspections must confirm partitions are of solid (no obvious <br> Unnotected Oneninas) construction and the fire ratino of the donors must | | Standard | Fire spread compartmentation | Shafts throughout the building must be completely enclosed in fire rated construction to address the risk of fire spread between floors and to | | Specification | Fire spread - | Shafts must be Fire Rated to achieve the same Fire Resistance as the | | Specification | Fire spread - | Shafts in a Low-rise and Medium-rise building must be enclosed in at | | Specification | Fire spread - | Shafts in a High-rise building must be enclosed in at least a 90-minute | | Specification | Fire spread - | Shafts in a Super High-rise building must be enclosed in at least a 120- | | Specification | Fire spread compartmentation | Where the Fire Resistance of a Shaft is unknown then visual inspections must confirm they are of solid (no obvious Unprotected Openings) | | Specification | Fire spread - | A rubbish/laundrv chute must terminate in a Fire Rated room equal to the | | Specification | Fire spread compartmentation | The terminus room for a rubbish/laundry chute must be less than 20sq.m ( 215 sd ft ) or an automatic fire damner must he fitted to the hase of the | | Specification | Fire spread - | In buildings with a Fixed Fire Suppression Svstem, the chute must also | | Specification | Fire spread - | Rubbish and laundry chute doors must be self-closing and have a self | | Standard | Fire spread compartmentation | Corridors-providing Egress routes from the Guest Rooms to an Exit Stair or Final Exit must be constructed from fire resisting construction to address the risk of fire snread and to nrotect Faresc routec in case of fire | | Specification | Fire spread comnartmentation | Guest Room corridors must achieve at least 30-minutes Fire Resistance in L ow-rise and Medium-rise nronerties | | Specification | Fire spread compartmentation | Guest Room corridors must achieve at least 60-minutes Fire Resistance in High-rise and Super-High-rise properties. | | Specification | Fire spread compartmentation | Where the Fire Resistance of a corridor is unknown then visual inspections must confirm they are of solid construction (no obvious | | Standard | Fire spread combartmentation | Openings in fire rated construction throughout the building must manage the risk of fire and smoke soread to orotect Earess routes in case of fire. | | Specification | Fire spread compartmentation | To prevent fire spread through Fire Rated construction, all penetrations between and through fire resisting construction must be fire stopped with |
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Guest Room doors, and door frames, must achieve at least 20-minutes Fire Resistance in Low-rise and Medium-rise properties.
在低层和中层物业中,客房门和门框必须达到至少 20 分钟的耐火等级。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Guest Room doors, and door frames, must achieve at least 20-minutes Fire Resistance in Hiah-rise properties protected throughout bv a Fixed
在高层建筑中,客房门和门框必须达到至少 20 分钟的耐火等级。
Specification 规格 Fire spread combartmentation
火灾蔓延梳理
Guest Room doors, and door frames, must achieve at least 45-minutes Fire Resistance in Hiah-rise pronerties without a Fixed Fire Suppression
在没有固定灭火装置的高层建筑中,客房门和门框必须达到至少 45 分钟的耐火等级。
Specification 规格 Fire spread - 火势蔓延 - Guest Room doors, and door frames, must achieve at least 45-minutes
客房门和门框必须至少达到 45 分钟的使用寿命
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Guest Room doors, and door frames, are permitted with 0-minutes Fire Resistance where they open onto an Exterior Egress route except along
客房门和门框在通向室外出口通道时,耐火等级为 0 分钟,但以下情况除外
Specification 规格 Fire spread - 火势蔓延 - Connecting Guest Room doors, and door frames, must achieve at least
连接客房的门和门框必须至少达到
Specification 规格 Fire spread combartmentation
火灾蔓延梳理

除客房门外,30 分钟墙内的所有防火门和门框必须至少达到 20 分钟的耐火等级
Other than Guest Room doors, all Fire Rated doors, and door frames, in
a 30-minute wall must achieve at least 20-minutes Fire Resistance
Other than Guest Room doors, all Fire Rated doors, and door frames, in a 30-minute wall must achieve at least 20-minutes Fire Resistance| Other than Guest Room doors, all Fire Rated doors, and door frames, in | | :--- | | a 30-minute wall must achieve at least 20-minutes Fire Resistance |
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Other than Guest Room doors, all Fire Rated doors, and door frames, in a-60-minute wall must_achieve at least 45 minutes Fire Resistance.
除客房门外,60 分钟防火墙中的所有防火门和门框必须至少达到 45 分钟的耐火等级。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Other than Guest Room doors, all Fire Rated doors, and door frames, in a 120-minute wall must achieve at least 90-minutes Fire Resistance
除客房门外,120 分钟墙内的所有防火门和门框必须至少达到 90 分钟的耐火等级
Specification 规格 Fire spread combartmentation
火灾蔓延梳理
All Fire Rated Doors except for Shaft or connecting Guest Room doors must be equipned with Automatic Door Closers to ensure self-closing and
除竖井或连接客房的门外,所有防火门都必须配备自动闭门器,以确保自动关闭和
Specification 规格 Fire spread - 火势蔓延 - Where these auto-closing Fire Rated Doors are held open, an Automatic
在这些自动关闭防火门保持开启的情况下,自动
Standard 标准 Fire spread combartmentation
火灾蔓延梳理
Egress routes passing through an Atrium must include measures for maintainina Tenable conditions for the duration of the evacuation neriod.
穿过中庭的疏散通道必须包括在疏散期间保持适当条件的措施。
Specification 规格 Fire spread - 火势蔓延 - Egress routes must be separated from the atrium with fire and Smoke
出口通道必须与中庭用防火和防烟设施隔开。
Specification 规格 Fire spread combartmentation
火灾蔓延梳理
A Smoke Resisting enclosure only is permitted in Low-Rise or in an Atrium un to 3 stories provided all levels of the Atrium evacuate
低层建筑或不超过 3 层的中庭只允许使用防烟围护结构,但中庭所有楼层都必须疏散
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
60-minute Fire Resistance of the atrium enclosure can be achieved with fixed glazing (no operable windows) protected by closely spaced
中庭围墙的 60 分钟耐火等级可通过固定玻璃(无可开启窗户)实现,并由紧密间隔的
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
In lieu of fire and smoke separating construction, an automatic engineered Smoke Management System must be provided in the Atrium
中庭必须安装自动工程烟雾管理系统,以代替防火防烟分隔结构
In lieu of fire and smoke separating construction, an automatic engineered Smoke Management System must be provided in the Atrium https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=33&width=1064&top_left_y=1274&top_left_x=861| In lieu of fire and smoke separating construction, an automatic engineered Smoke Management System must be provided in the Atrium | | :--- | | ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=33&width=1064&top_left_y=1274&top_left_x=861) |
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
An 'open to sky' courtyard Atrium comprised of not more than three storeys is acceptable provided all levels of the Atrium evacuate
可以接受不超过三层的 "向天空开放 "的庭院中庭,条件是中庭的所有楼层都能进行疏散
An 'open to sky' courtyard Atrium comprised of not more than three storeys is acceptable provided all levels of the Atrium evacuate https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=42&width=1007&top_left_y=1379&top_left_x=860| An 'open to sky' courtyard Atrium comprised of not more than three storeys is acceptable provided all levels of the Atrium evacuate | | :--- | | ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=42&width=1007&top_left_y=1379&top_left_x=860) |
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Suppression, an Atrium is permitted without a Smoke Management System provided all balconies and the base of the Atrium are maintained free of combustible contents and all Guest Rooms, rooms, shafts and
如果所有阳台和中庭底部均无可燃物,且所有客房、房间、竖井和厨房均无可燃物,则允许中庭不安装烟雾管理系统。
Standard 标准 Fire spread compartmentation
火灾蔓延分隔

与建筑物相连的封闭式停车场,如果没有固定灭火系统的保护,则必须有其他消防安 全规定,以控制火势从停车场蔓延到建筑物其他部分的风险。
Enclosed Car Parks connected to the building, which are not protected by
a Fixed Fire Suppression System, must have other fire safety provisions to manage the risk of fire spreading from the Car Park to the rest of the
Enclosed Car Parks connected to the building, which are not protected by a Fixed Fire Suppression System, must have other fire safety provisions to manage the risk of fire spreading from the Car Park to the rest of the| Enclosed Car Parks connected to the building, which are not protected by | | :--- | | a Fixed Fire Suppression System, must have other fire safety provisions to manage the risk of fire spreading from the Car Park to the rest of the |
Specification 规格 Fire spread combartmentation
火灾蔓延梳理
A Fixed Fire Suppression system must be provided throughout the narkino areas or all of the followind measures must he in nlace.
必须在整个场馆内安装固定灭火系统,或采取以下所有措施。
Specification 规格 Fire spread - 火势蔓延 - Separated from the building with construction providing a Fire Resistance
与建筑物隔开,具有耐火结构
Specification 规格 Fire spread - 火势蔓延 - A Fire Lobby with two 30-minute fire and Smoke Resisting doors at any
消防大厅,在任何位置均设有两扇 30 分钟防火防烟门。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
smoke ventilation with openings of at least 20 % 20 % 20%20 \% of the perimeter wall at each level distributed around at least 40 % 40 % 40%40 \% of the perimeter or uniformly
每层至少有 20 % 20 % 20%20 \% 周墙的开口,围绕至少 40 % 40 % 40%40 \% 周墙分布或均匀分布的排烟口
Specification 规格 Fire spread - 火势蔓延 - A fire alarm and detection svstem linked to the building svstem.
与楼宇系统相连的火灾报警和探测系统。
Specification 规格 Fire spread - 火势蔓延 - Manual pull stations (call points) must be provided at all exit points from
从以下出口的所有出口处必须设置手动拉闸站(呼叫点
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
Where the Fire Resistance of a Car Park floor slab or Fire Lobby is unknown then visual inspections must confirm they are of solid
如果停车场楼板或消防通道的耐火性能不明,则必须通过目测确认它们是实心的
Standard 标准 Fire spread compartmentation
火灾蔓延分隔
Normally Unoccupied Rooms throughout the building must have measures to address the risk of Exit Stairwells becoming blocked due to
整栋楼内通常无人居住的房间必须采取措施,应对出口楼梯井因以下原因而堵塞的风险
Specification 规格 Fire spread - 火势蔓延 - A Fire Lobbv must be provided between the Normally Unoccupied Room
在通常无人居住的房间与房间之间必须设置防火带。
Specification 规格 Fire spread - 火势蔓延 - The Fire Lobbv must have Fire Rated doors with a self-closing
消防车必须安装带有自动关闭功能的防火门。
Specification 规格 Fire spread compartmentation
火灾蔓延分隔
If a Fire Lobby can not be provided then this can be accepted if there are at least two Exit Stairwells serving all levels of the building and a fire in
如果不能提供消防通道,但至少有两个出口楼梯间为建筑物各层提供服务,并且在消防通道内有一个火源,则可以接受。
Specification 规格 Fire spread - 火势蔓延 - Smoke detection must be provided in Normally Unocuppied Rooms.
通常无供应的房间必须安装烟雾探测器。
Standard 标准 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
Exterior Wall Systems of the building must have measures that resist or slow the propagation of fire spread to manage the risk of buildina fire
建筑物的外墙系统必须采取抵御或减缓火势蔓延的措施,以控制建筑火灾的风险
Specification 规格 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
For Medium-rise and High-rise buildings the main component materials of construction (e.a. structure. cladding. insulation) in the exterior wall
对于中层和高层建筑,外墙的主要建筑材料(如结构、覆层、隔热材料)包括
Specification Fire spread compartmentation Guest Room doors, and door frames, must achieve at least 20-minutes Fire Resistance in Low-rise and Medium-rise properties. Specification Fire spread compartmentation Guest Room doors, and door frames, must achieve at least 20-minutes Fire Resistance in Hiah-rise properties protected throughout bv a Fixed Specification Fire spread combartmentation Guest Room doors, and door frames, must achieve at least 45-minutes Fire Resistance in Hiah-rise pronerties without a Fixed Fire Suppression Specification Fire spread - Guest Room doors, and door frames, must achieve at least 45-minutes Specification Fire spread compartmentation Guest Room doors, and door frames, are permitted with 0-minutes Fire Resistance where they open onto an Exterior Egress route except along Specification Fire spread - Connecting Guest Room doors, and door frames, must achieve at least Specification Fire spread combartmentation "Other than Guest Room doors, all Fire Rated doors, and door frames, in a 30-minute wall must achieve at least 20-minutes Fire Resistance" Specification Fire spread compartmentation Other than Guest Room doors, all Fire Rated doors, and door frames, in a-60-minute wall must_achieve at least 45 minutes Fire Resistance. Specification Fire spread compartmentation Other than Guest Room doors, all Fire Rated doors, and door frames, in a 120-minute wall must achieve at least 90-minutes Fire Resistance Specification Fire spread combartmentation All Fire Rated Doors except for Shaft or connecting Guest Room doors must be equipned with Automatic Door Closers to ensure self-closing and Specification Fire spread - Where these auto-closing Fire Rated Doors are held open, an Automatic Standard Fire spread combartmentation Egress routes passing through an Atrium must include measures for maintainina Tenable conditions for the duration of the evacuation neriod. Specification Fire spread - Egress routes must be separated from the atrium with fire and Smoke Specification Fire spread combartmentation A Smoke Resisting enclosure only is permitted in Low-Rise or in an Atrium un to 3 stories provided all levels of the Atrium evacuate Specification Fire spread compartmentation 60-minute Fire Resistance of the atrium enclosure can be achieved with fixed glazing (no operable windows) protected by closely spaced Specification Fire spread compartmentation "In lieu of fire and smoke separating construction, an automatic engineered Smoke Management System must be provided in the Atrium https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=33&width=1064&top_left_y=1274&top_left_x=861" Specification Fire spread compartmentation "An 'open to sky' courtyard Atrium comprised of not more than three storeys is acceptable provided all levels of the Atrium evacuate https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=42&width=1007&top_left_y=1379&top_left_x=860" Specification Fire spread compartmentation Suppression, an Atrium is permitted without a Smoke Management System provided all balconies and the base of the Atrium are maintained free of combustible contents and all Guest Rooms, rooms, shafts and Standard Fire spread compartmentation "Enclosed Car Parks connected to the building, which are not protected by a Fixed Fire Suppression System, must have other fire safety provisions to manage the risk of fire spreading from the Car Park to the rest of the" Specification Fire spread combartmentation A Fixed Fire Suppression system must be provided throughout the narkino areas or all of the followind measures must he in nlace. Specification Fire spread - Separated from the building with construction providing a Fire Resistance Specification Fire spread - A Fire Lobby with two 30-minute fire and Smoke Resisting doors at any Specification Fire spread compartmentation smoke ventilation with openings of at least 20% of the perimeter wall at each level distributed around at least 40% of the perimeter or uniformly Specification Fire spread - A fire alarm and detection svstem linked to the building svstem. Specification Fire spread - Manual pull stations (call points) must be provided at all exit points from Specification Fire spread compartmentation Where the Fire Resistance of a Car Park floor slab or Fire Lobby is unknown then visual inspections must confirm they are of solid Standard Fire spread compartmentation Normally Unoccupied Rooms throughout the building must have measures to address the risk of Exit Stairwells becoming blocked due to Specification Fire spread - A Fire Lobbv must be provided between the Normally Unoccupied Room Specification Fire spread - The Fire Lobbv must have Fire Rated doors with a self-closing Specification Fire spread compartmentation If a Fire Lobby can not be provided then this can be accepted if there are at least two Exit Stairwells serving all levels of the building and a fire in Specification Fire spread - Smoke detection must be provided in Normally Unocuppied Rooms. Standard Fire spread - exterior envelope Exterior Wall Systems of the building must have measures that resist or slow the propagation of fire spread to manage the risk of buildina fire Specification Fire spread - exterior envelope For Medium-rise and High-rise buildings the main component materials of construction (e.a. structure. cladding. insulation) in the exterior wall| Specification | Fire spread compartmentation | Guest Room doors, and door frames, must achieve at least 20-minutes Fire Resistance in Low-rise and Medium-rise properties. | | :---: | :---: | :---: | | Specification | Fire spread compartmentation | Guest Room doors, and door frames, must achieve at least 20-minutes Fire Resistance in Hiah-rise properties protected throughout bv a Fixed | | Specification | Fire spread combartmentation | Guest Room doors, and door frames, must achieve at least 45-minutes Fire Resistance in Hiah-rise pronerties without a Fixed Fire Suppression | | Specification | Fire spread - | Guest Room doors, and door frames, must achieve at least 45-minutes | | Specification | Fire spread compartmentation | Guest Room doors, and door frames, are permitted with 0-minutes Fire Resistance where they open onto an Exterior Egress route except along | | Specification | Fire spread - | Connecting Guest Room doors, and door frames, must achieve at least | | Specification | Fire spread combartmentation | Other than Guest Room doors, all Fire Rated doors, and door frames, in <br> a 30-minute wall must achieve at least 20-minutes Fire Resistance | | Specification | Fire spread compartmentation | Other than Guest Room doors, all Fire Rated doors, and door frames, in a-60-minute wall must_achieve at least 45 minutes Fire Resistance. | | Specification | Fire spread compartmentation | Other than Guest Room doors, all Fire Rated doors, and door frames, in a 120-minute wall must achieve at least 90-minutes Fire Resistance | | Specification | Fire spread combartmentation | All Fire Rated Doors except for Shaft or connecting Guest Room doors must be equipned with Automatic Door Closers to ensure self-closing and | | Specification | Fire spread - | Where these auto-closing Fire Rated Doors are held open, an Automatic | | Standard | Fire spread combartmentation | Egress routes passing through an Atrium must include measures for maintainina Tenable conditions for the duration of the evacuation neriod. | | Specification | Fire spread - | Egress routes must be separated from the atrium with fire and Smoke | | Specification | Fire spread combartmentation | A Smoke Resisting enclosure only is permitted in Low-Rise or in an Atrium un to 3 stories provided all levels of the Atrium evacuate | | Specification | Fire spread compartmentation | 60-minute Fire Resistance of the atrium enclosure can be achieved with fixed glazing (no operable windows) protected by closely spaced | | Specification | Fire spread compartmentation | In lieu of fire and smoke separating construction, an automatic engineered Smoke Management System must be provided in the Atrium <br> ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=33&width=1064&top_left_y=1274&top_left_x=861) | | Specification | Fire spread compartmentation | An 'open to sky' courtyard Atrium comprised of not more than three storeys is acceptable provided all levels of the Atrium evacuate <br> ![](https://cdn.mathpix.com/cropped/2024_11_25_6fddc165251b3eee39c5g-10.jpg?height=42&width=1007&top_left_y=1379&top_left_x=860) | | Specification | Fire spread compartmentation | Suppression, an Atrium is permitted without a Smoke Management System provided all balconies and the base of the Atrium are maintained free of combustible contents and all Guest Rooms, rooms, shafts and | | Standard | Fire spread compartmentation | Enclosed Car Parks connected to the building, which are not protected by <br> a Fixed Fire Suppression System, must have other fire safety provisions to manage the risk of fire spreading from the Car Park to the rest of the | | Specification | Fire spread combartmentation | A Fixed Fire Suppression system must be provided throughout the narkino areas or all of the followind measures must he in nlace. | | Specification | Fire spread - | Separated from the building with construction providing a Fire Resistance | | Specification | Fire spread - | A Fire Lobby with two 30-minute fire and Smoke Resisting doors at any | | Specification | Fire spread compartmentation | smoke ventilation with openings of at least $20 \%$ of the perimeter wall at each level distributed around at least $40 \%$ of the perimeter or uniformly | | Specification | Fire spread - | A fire alarm and detection svstem linked to the building svstem. | | Specification | Fire spread - | Manual pull stations (call points) must be provided at all exit points from | | Specification | Fire spread compartmentation | Where the Fire Resistance of a Car Park floor slab or Fire Lobby is unknown then visual inspections must confirm they are of solid | | Standard | Fire spread compartmentation | Normally Unoccupied Rooms throughout the building must have measures to address the risk of Exit Stairwells becoming blocked due to | | Specification | Fire spread - | A Fire Lobbv must be provided between the Normally Unoccupied Room | | Specification | Fire spread - | The Fire Lobbv must have Fire Rated doors with a self-closing | | Specification | Fire spread compartmentation | If a Fire Lobby can not be provided then this can be accepted if there are at least two Exit Stairwells serving all levels of the building and a fire in | | Specification | Fire spread - | Smoke detection must be provided in Normally Unocuppied Rooms. | | Standard | Fire spread - exterior envelope | Exterior Wall Systems of the building must have measures that resist or slow the propagation of fire spread to manage the risk of buildina fire | | Specification | Fire spread - exterior envelope | For Medium-rise and High-rise buildings the main component materials of construction (e.a. structure. cladding. insulation) in the exterior wall |
Specification 规格 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
For Medium-rise and High-rise buildings each main component (e.g. insulation and cladding) of the Exterior Wall System must be NonCombustible or fire tested to an International Standard Accentable to
对于中层和高层建筑,外墙系统的每个主要组件(如隔热层和覆层)都必须是不可燃的,或经过防火测试,符合以下国际标准
Specification 规格 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
For Medium-rise and High-rise buildings each-Exterior Wall System proposed on the building must be fire tested in a large scale
对于中层和高层建筑,建筑物上建议采用的每种外墙系统都必须经过大规模的防火测试。
Specification 规格 Fire spread - exterior 火灾蔓延 - 外部 Super Hiah-rise buildings must have a Non-Combustible Exterior Wall
超高层建筑必须有不燃烧外墙
Specification 规格 Fire spread - exterior envelope
火灾蔓延 - 外部围护结构
Where the combustibility of the cladding of the Exterior Wall System(s) is unknown and Vertically Connected up part or all of the exterior wall, then a fire Risk Assessment must be carried out bv a Qualified Person.
如果外墙系统覆层的可燃性不明,且垂直连接部分或全部外墙,则必须由合格人员进行火灾风险评估。
Guideline 指导原则 Fire spread - exterior envelope
火灾蔓延 - 外部围护结构
In response to the fire Risk Assessment of the external wall system, the Qualified Person may recommend further actions that are required to manage associated risk, ranging from physical building works to operational controls. These recommendations, and the actions the hotel intends to take, should be shared with IHG for adreement.
针对外墙系统的火灾风险评估,合格人员可能会建议采取进一步行动来管理相关风险,包括实际建筑工程和操作控制。这些建议以及酒店打算采取的行动应与 IHG 共享,以获得同意。
Standard 标准 Fire spread - exterior envelope
火灾蔓延 - 外部围护结构
Exterior Green Wall systems must have measures that resist or slow the propagation of fire spread to adress the risk of building fire safety svstems becoming overwhelmed or Faress routes-becoming
外墙绿化系统必须有抵御或减缓火灾蔓延的措施,以应对建筑消防安全系统不堪重负或消防通道被堵塞的风险。
Specification 规格 Fire spread - exterior 火灾蔓延 - 外部 Vegetation in Green Walls must be kept green via a reliable irrigation
绿墙中的植被必须通过可靠的灌溉系统保持绿色
Specification 规格 Fire spread - exterior 火灾蔓延 - 外部 The Exterior Wall Svstem behind or supportina the Green Wall attached
绿墙背后或支撑绿墙的外墙系统
Specification 规格 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
The containers or backing for the Green Wall attached to a Medium-rise buildino must he Non-Combustible and neat must not he used as a
附着在中层建筑上的绿色墙体的容器或衬底必须是不可燃的,且整齐划一。
Specification 规格 Fire spread - exterior envelone
火势蔓延 - 室外
Any vegetation attached to the Exterior Wall Systems of High-Rise or Swner Hiah-Rise must he J Calised and not Vertically Connected un nart
任何附着在高层建筑或高层住宅外墙系统上的植物必须垂直连接,不得与外墙系统垂直连接。
Standard 标准 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
Exterior Wall Systems incorporating Photovoltaic Panel installations (attached or integrated) must have measures that resist the propagation
安装了光伏板(附着式或集成式)的外墙系统必须采取以下措施,以防止其传播
Specification 规格 Fire spread - exterior 火灾蔓延 - 外部 Integrated or attached Photovoltaic Panel installations must comply with
集成或附带的光伏板装置必须符合以下要求
Specification 规格 Fire spread - exterior envelope
火灾蔓延 - 外围护结构
Integrated or attached Photovoltaic Panels are permitted on the Exterior Wall Svstem(s) of a Hiah-rise hut the Photovoltaic. Panels must he
允许在高层建筑的外墙系统上安装集成式或附着式光伏板,但光伏板必须与外墙系统相连。光伏板必须
Specification 规格 Fire spread - exterior 火灾蔓延 - 外部 Photovoltaic Panels are not permitted on the Exterior Wall Svstem(s) of
不允许在以下建筑的外墙系统上安装光伏板
Specification 规格 Fire spread - exterior 火灾蔓延 - 外部 Photovoltaic Panels on the Exterior Wall System(s) of Super High-rise
超高层建筑外墙系统上的光伏板
Standard 标准 Fire spread - hazard mitiaation
火灾蔓延--减轻危害
Fixed appliances generating significant heat or using controlled combustion must have measures to address the risk of innition/fire
产生大量热量或使用受控燃烧的固定设备必须有措施来应对着火/火灾风险
Specification 规格 Fire spread - hazard mitioation
火灾蔓延--减轻危害
Gas fires must be provided with an automatic ignition source with combustion controls to nrevent als from beincreleased into the rom
燃气壁炉必须配备自动点火源和燃烧控制装置,以防止燃气泄漏到室内。
Specification 规格 Fire spread - hazard mitigation
火灾蔓延--减轻危害
Solid fuel-burning fireplaces are only permitted in Public Areas and only when eauinned with a tempered alass door or other auard and the floor is
公共区域只允许使用固体燃料壁炉,且必须装有钢化玻璃门或其他防护装置,地板必须是
Specification 规格 Fire spread - hazard mitiaation
火灾蔓延--减轻危害
Stove type cooking equipment in Guest Rooms must have a localised dedicated Fixed Fire Sunnression Sustem excent where the Guest Room
客房内的炉灶类烹饪设备必须有一个局部专用的固定式防火防烟装置。
Standard 标准 Fire spread - hazard mitiaation
火灾蔓延--减轻危害
Flammable Materials and combustible gases/liquid - including consumable hotel supolies and bulk storage fuels - must be stored so as
易燃材料和可燃气体/液体--包括酒店消耗品和散装储存燃料--的储存必须做到以下几点
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 Storage of Flammable Materials is not permitted on Guest Room floors
客房楼层禁止存放易燃物品
Specification 规格 Fire spread - hazard mitiaation
火灾蔓延--减轻危害
Flammable Materials in Back of House areas must be kept in lockers or cabinets of a minimum of 30-minutes Fire Resistance.
后厨区域的易燃材料必须存放在至少耐火 30 分钟的储物柜或橱柜中。
Specification 规格 Fire spread - hazard mitioation
火灾蔓延--减轻危害
The bulk storage of combustible liquids or gases (e.g. liquid petroleum das netroleum and noill must he in accordance with the recommendations
可燃液体或气体(如液化石油气和煤油)的散装储存必须符合以下建议
Standard 标准 Fire spread - hazard mitiaation
火灾蔓延--减轻危害
Fire safety provisions must be in place to manage the fire and explosion hazard of Batterv Fnergy Storace Svstems (BFSS) installed inside the
必须制定消防安全规定,以管理安装在舱内的电池储能系统(BFSS)的火灾和爆炸危险。
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 BESS room must be a minimum of 120 -minutes Fire Rated construction
BESS 机房必须是至少 120 分钟的防火建筑
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 BESS room must be protected bv an automatic Fixed Fire Suppression
BESS 机房必须由固定式自动灭火装置提供保护。
Specification 规格 Fire spread - hazard mitigation
火灾蔓延--减轻危害
BESS room must be provided with explosion control/venting as per the manufacturers instructions and approved by a Qualified Person.
BESS 房必须按照制造商的说明提供防爆控制/通风装置,并由合格人员批准。
Specification 规格 Fire spread - hazard mitigation
火灾蔓延--减轻危害
BESS room must be provided with an approved air cooling system to regulate temperature and prevent overheating.
BESS 机房必须配备经批准的空气冷却系统,以调节温度和防止过热。
Specification 规格 Fire spread - hazard mitication
火灾蔓延--减轻危害
Appropriate multi-gas detection and fire detection must be provided for BESS room and must he intearated with alarm ventilation and
必须为 BESS 机房提供适当的多重气体检测和火灾检测,并与警报通风和消防系统相连接。
Specification 规格 Fire spread - hazard mitication
火灾蔓延--减轻危害
BESS must be controlled and monitored by an energy or battery manadement svstem that can cut current and raise the alarm
BESS 必须由能源或电池管理系统控制和监测,该系统可切断电流并发出警报
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 BESS must be desianed to comply with an International Standard
BESS 的设计必须符合国际标准
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 BESS must be certified per an International Standard Acceptable to IHG
BESS 必须按照 IHG 可接受的国际标准进行认证
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 BESS must be installed. commissioned and maintained as per
BESS 必须按照以下要求安装、调试和维护
Guideline 指导原则 Fire spread - hazard 火灾蔓延 - 危险 Air coolina svstem used for BESS rooms must be either Closed Loop
用于 BESS 机房的空气冷却系统必须是闭环式的
Specification Fire spread - exterior envelope For Medium-rise and High-rise buildings each main component (e.g. insulation and cladding) of the Exterior Wall System must be NonCombustible or fire tested to an International Standard Accentable to Specification Fire spread - exterior envelope For Medium-rise and High-rise buildings each-Exterior Wall System proposed on the building must be fire tested in a large scale Specification Fire spread - exterior Super Hiah-rise buildings must have a Non-Combustible Exterior Wall Specification Fire spread - exterior envelope Where the combustibility of the cladding of the Exterior Wall System(s) is unknown and Vertically Connected up part or all of the exterior wall, then a fire Risk Assessment must be carried out bv a Qualified Person. Guideline Fire spread - exterior envelope In response to the fire Risk Assessment of the external wall system, the Qualified Person may recommend further actions that are required to manage associated risk, ranging from physical building works to operational controls. These recommendations, and the actions the hotel intends to take, should be shared with IHG for adreement. Standard Fire spread - exterior envelope Exterior Green Wall systems must have measures that resist or slow the propagation of fire spread to adress the risk of building fire safety svstems becoming overwhelmed or Faress routes-becoming Specification Fire spread - exterior Vegetation in Green Walls must be kept green via a reliable irrigation Specification Fire spread - exterior The Exterior Wall Svstem behind or supportina the Green Wall attached Specification Fire spread - exterior envelope The containers or backing for the Green Wall attached to a Medium-rise buildino must he Non-Combustible and neat must not he used as a Specification Fire spread - exterior envelone Any vegetation attached to the Exterior Wall Systems of High-Rise or Swner Hiah-Rise must he J Calised and not Vertically Connected un nart Standard Fire spread - exterior envelope Exterior Wall Systems incorporating Photovoltaic Panel installations (attached or integrated) must have measures that resist the propagation Specification Fire spread - exterior Integrated or attached Photovoltaic Panel installations must comply with Specification Fire spread - exterior envelope Integrated or attached Photovoltaic Panels are permitted on the Exterior Wall Svstem(s) of a Hiah-rise hut the Photovoltaic. Panels must he Specification Fire spread - exterior Photovoltaic Panels are not permitted on the Exterior Wall Svstem(s) of Specification Fire spread - exterior Photovoltaic Panels on the Exterior Wall System(s) of Super High-rise Standard Fire spread - hazard mitiaation Fixed appliances generating significant heat or using controlled combustion must have measures to address the risk of innition/fire Specification Fire spread - hazard mitioation Gas fires must be provided with an automatic ignition source with combustion controls to nrevent als from beincreleased into the rom Specification Fire spread - hazard mitigation Solid fuel-burning fireplaces are only permitted in Public Areas and only when eauinned with a tempered alass door or other auard and the floor is Specification Fire spread - hazard mitiaation Stove type cooking equipment in Guest Rooms must have a localised dedicated Fixed Fire Sunnression Sustem excent where the Guest Room Standard Fire spread - hazard mitiaation Flammable Materials and combustible gases/liquid - including consumable hotel supolies and bulk storage fuels - must be stored so as Specification Fire spread - hazard Storage of Flammable Materials is not permitted on Guest Room floors Specification Fire spread - hazard mitiaation Flammable Materials in Back of House areas must be kept in lockers or cabinets of a minimum of 30-minutes Fire Resistance. Specification Fire spread - hazard mitioation The bulk storage of combustible liquids or gases (e.g. liquid petroleum das netroleum and noill must he in accordance with the recommendations Standard Fire spread - hazard mitiaation Fire safety provisions must be in place to manage the fire and explosion hazard of Batterv Fnergy Storace Svstems (BFSS) installed inside the Specification Fire spread - hazard BESS room must be a minimum of 120 -minutes Fire Rated construction Specification Fire spread - hazard BESS room must be protected bv an automatic Fixed Fire Suppression Specification Fire spread - hazard mitigation BESS room must be provided with explosion control/venting as per the manufacturers instructions and approved by a Qualified Person. Specification Fire spread - hazard mitigation BESS room must be provided with an approved air cooling system to regulate temperature and prevent overheating. Specification Fire spread - hazard mitication Appropriate multi-gas detection and fire detection must be provided for BESS room and must he intearated with alarm ventilation and Specification Fire spread - hazard mitication BESS must be controlled and monitored by an energy or battery manadement svstem that can cut current and raise the alarm Specification Fire spread - hazard BESS must be desianed to comply with an International Standard Specification Fire spread - hazard BESS must be certified per an International Standard Acceptable to IHG Specification Fire spread - hazard BESS must be installed. commissioned and maintained as per Guideline Fire spread - hazard Air coolina svstem used for BESS rooms must be either Closed Loop| Specification | Fire spread - exterior envelope | For Medium-rise and High-rise buildings each main component (e.g. insulation and cladding) of the Exterior Wall System must be NonCombustible or fire tested to an International Standard Accentable to | | :---: | :---: | :---: | | Specification | Fire spread - exterior envelope | For Medium-rise and High-rise buildings each-Exterior Wall System proposed on the building must be fire tested in a large scale | | Specification | Fire spread - exterior | Super Hiah-rise buildings must have a Non-Combustible Exterior Wall | | Specification | Fire spread - exterior envelope | Where the combustibility of the cladding of the Exterior Wall System(s) is unknown and Vertically Connected up part or all of the exterior wall, then a fire Risk Assessment must be carried out bv a Qualified Person. | | Guideline | Fire spread - exterior envelope | In response to the fire Risk Assessment of the external wall system, the Qualified Person may recommend further actions that are required to manage associated risk, ranging from physical building works to operational controls. These recommendations, and the actions the hotel intends to take, should be shared with IHG for adreement. | | Standard | Fire spread - exterior envelope | Exterior Green Wall systems must have measures that resist or slow the propagation of fire spread to adress the risk of building fire safety svstems becoming overwhelmed or Faress routes-becoming | | Specification | Fire spread - exterior | Vegetation in Green Walls must be kept green via a reliable irrigation | | Specification | Fire spread - exterior | The Exterior Wall Svstem behind or supportina the Green Wall attached | | Specification | Fire spread - exterior envelope | The containers or backing for the Green Wall attached to a Medium-rise buildino must he Non-Combustible and neat must not he used as a | | Specification | Fire spread - exterior envelone | Any vegetation attached to the Exterior Wall Systems of High-Rise or Swner Hiah-Rise must he J Calised and not Vertically Connected un nart | | Standard | Fire spread - exterior envelope | Exterior Wall Systems incorporating Photovoltaic Panel installations (attached or integrated) must have measures that resist the propagation | | Specification | Fire spread - exterior | Integrated or attached Photovoltaic Panel installations must comply with | | Specification | Fire spread - exterior envelope | Integrated or attached Photovoltaic Panels are permitted on the Exterior Wall Svstem(s) of a Hiah-rise hut the Photovoltaic. Panels must he | | Specification | Fire spread - exterior | Photovoltaic Panels are not permitted on the Exterior Wall Svstem(s) of | | Specification | Fire spread - exterior | Photovoltaic Panels on the Exterior Wall System(s) of Super High-rise | | Standard | Fire spread - hazard mitiaation | Fixed appliances generating significant heat or using controlled combustion must have measures to address the risk of innition/fire | | Specification | Fire spread - hazard mitioation | Gas fires must be provided with an automatic ignition source with combustion controls to nrevent als from beincreleased into the rom | | Specification | Fire spread - hazard mitigation | Solid fuel-burning fireplaces are only permitted in Public Areas and only when eauinned with a tempered alass door or other auard and the floor is | | Specification | Fire spread - hazard mitiaation | Stove type cooking equipment in Guest Rooms must have a localised dedicated Fixed Fire Sunnression Sustem excent where the Guest Room | | Standard | Fire spread - hazard mitiaation | Flammable Materials and combustible gases/liquid - including consumable hotel supolies and bulk storage fuels - must be stored so as | | Specification | Fire spread - hazard | Storage of Flammable Materials is not permitted on Guest Room floors | | Specification | Fire spread - hazard mitiaation | Flammable Materials in Back of House areas must be kept in lockers or cabinets of a minimum of 30-minutes Fire Resistance. | | Specification | Fire spread - hazard mitioation | The bulk storage of combustible liquids or gases (e.g. liquid petroleum das netroleum and noill must he in accordance with the recommendations | | Standard | Fire spread - hazard mitiaation | Fire safety provisions must be in place to manage the fire and explosion hazard of Batterv Fnergy Storace Svstems (BFSS) installed inside the | | Specification | Fire spread - hazard | BESS room must be a minimum of 120 -minutes Fire Rated construction | | Specification | Fire spread - hazard | BESS room must be protected bv an automatic Fixed Fire Suppression | | Specification | Fire spread - hazard mitigation | BESS room must be provided with explosion control/venting as per the manufacturers instructions and approved by a Qualified Person. | | Specification | Fire spread - hazard mitigation | BESS room must be provided with an approved air cooling system to regulate temperature and prevent overheating. | | Specification | Fire spread - hazard mitication | Appropriate multi-gas detection and fire detection must be provided for BESS room and must he intearated with alarm ventilation and | | Specification | Fire spread - hazard mitication | BESS must be controlled and monitored by an energy or battery manadement svstem that can cut current and raise the alarm | | Specification | Fire spread - hazard | BESS must be desianed to comply with an International Standard | | Specification | Fire spread - hazard | BESS must be certified per an International Standard Acceptable to IHG | | Specification | Fire spread - hazard | BESS must be installed. commissioned and maintained as per | | Guideline | Fire spread - hazard | Air coolina svstem used for BESS rooms must be either Closed Loop |
Standard 标准 Fire spread - hazard mitioation
火灾蔓延--减轻危害
Electric vehicle (EV) charging stations must include design control measures that manage the potential consequences of fault or fire
电动汽车 (EV) 充电站必须包括设计控制措施,以控制故障或火灾的潜在后果
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 EV charging stations are permitted in an interior parking qarage with
电动汽车充电站可设置在内部停车场,但必须具备以下条件
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 Exterior EV charaing stations must be at least 6 m from the building
室外电动车充电站必须距离建筑物至少 6 米
Specification 规格 Fire spread - hazard mitioation
火灾蔓延--减轻危害
Exterior EV charging stations are permitted on the roof of a Low-rise huildino but must he at least 6 m from the huildino envelone or anv
允许在低层住宅的屋顶上设置室外电动汽车充电站,但必须距离住宅入口或屋顶至少 6 米。
Specification 规格 Fire spread - hazard 火灾蔓延 - 危险 Provide Certified EV charging stations per an International Standard
提供符合国际标准的认证电动汽车充电站
Specification 规格 Fire spread - hazard mitiqation
火灾蔓延--危险评估
Provide a manual isolation switch in the same floor or area, but not directlv adiacent to the FV charoino stations to cut off the nower sunnlv
在同一楼层或区域设置手动隔离开关,但不得直接毗邻 FV 充电器站,以切断电源
Specification 规格 Fire spread - hazard mitioation
火灾蔓延--减轻危害
For-installations, within interior parking garages, the power supply to EV charaina stations must be linked to the fire detection suppression
对于安装在室内停车场内的电动汽车充电桩,其电源必须与火灾探测灭火系统相连接。
Specification 规格 Fire spread - hazard mitication
火灾蔓延--减轻危害
EV charging stations must have an in-built interface to monitor faults within the charoino station and in the event of a fault automatically
电动汽车充电站必须有一个内置接口,以监控充电站内的故障,并在发生故障时自动
Standard 标准 Firefighting 消防 Provisions for Firefighters in High-rise or Super High-rise buildings must
高层或超高层建筑的消防员必须具备以下条件
Specification 规格 Firefighting 消防 An automatic wet standpipe (riser) must be provided in each Hiah-rise
每栋高层住宅必须安装自动湿立管(立管
Specification 规格 Firefighting 消防 As a minimum, a dry-standpipe (riser) must be provided in each High-rise
每栋高层建筑至少必须有一个干式立管(立管)。
Standard 标准 Fire safety management 消防安全管理 Fire Safety Equipment throughout the building must be kept in
整个大楼的消防安全设备必须保持在以下状态
Specification 规格 Fire safety management 消防安全管理 At least once every 12 months testing and maintenance of Fire Safety Equinment must be carried out in accordance with manufacturers
必须按照制造商的规定,至少每 12 个月对消防安全设备进行一次测试和维护。
Standard Fire spread - hazard mitioation Electric vehicle (EV) charging stations must include design control measures that manage the potential consequences of fault or fire Specification Fire spread - hazard EV charging stations are permitted in an interior parking qarage with Specification Fire spread - hazard Exterior EV charaing stations must be at least 6 m from the building Specification Fire spread - hazard mitioation Exterior EV charging stations are permitted on the roof of a Low-rise huildino but must he at least 6 m from the huildino envelone or anv Specification Fire spread - hazard Provide Certified EV charging stations per an International Standard Specification Fire spread - hazard mitiqation Provide a manual isolation switch in the same floor or area, but not directlv adiacent to the FV charoino stations to cut off the nower sunnlv Specification Fire spread - hazard mitioation For-installations, within interior parking garages, the power supply to EV charaina stations must be linked to the fire detection suppression Specification Fire spread - hazard mitication EV charging stations must have an in-built interface to monitor faults within the charoino station and in the event of a fault automatically Standard Firefighting Provisions for Firefighters in High-rise or Super High-rise buildings must Specification Firefighting An automatic wet standpipe (riser) must be provided in each Hiah-rise Specification Firefighting As a minimum, a dry-standpipe (riser) must be provided in each High-rise Standard Fire safety management Fire Safety Equipment throughout the building must be kept in Specification Fire safety management At least once every 12 months testing and maintenance of Fire Safety Equinment must be carried out in accordance with manufacturers| Standard | Fire spread - hazard mitioation | Electric vehicle (EV) charging stations must include design control measures that manage the potential consequences of fault or fire | | :---: | :---: | :---: | | Specification | Fire spread - hazard | EV charging stations are permitted in an interior parking qarage with | | Specification | Fire spread - hazard | Exterior EV charaing stations must be at least 6 m from the building | | Specification | Fire spread - hazard mitioation | Exterior EV charging stations are permitted on the roof of a Low-rise huildino but must he at least 6 m from the huildino envelone or anv | | Specification | Fire spread - hazard | Provide Certified EV charging stations per an International Standard | | Specification | Fire spread - hazard mitiqation | Provide a manual isolation switch in the same floor or area, but not directlv adiacent to the FV charoino stations to cut off the nower sunnlv | | Specification | Fire spread - hazard mitioation | For-installations, within interior parking garages, the power supply to EV charaina stations must be linked to the fire detection suppression | | Specification | Fire spread - hazard mitication | EV charging stations must have an in-built interface to monitor faults within the charoino station and in the event of a fault automatically | | Standard | Firefighting | Provisions for Firefighters in High-rise or Super High-rise buildings must | | Specification | Firefighting | An automatic wet standpipe (riser) must be provided in each Hiah-rise | | Specification | Firefighting | As a minimum, a dry-standpipe (riser) must be provided in each High-rise | | Standard | Fire safety management | Fire Safety Equipment throughout the building must be kept in | | Specification | Fire safety management | At least once every 12 months testing and maintenance of Fire Safety Equinment must be carried out in accordance with manufacturers |