Power On Interface
The Appearance of The Wired Controller
When powering on for the first time, after staying in the dynamic interface for 20 seconds, enter the following main interface according to the motherboard mode.
Power On Interface
The Appearance of The Wired Controller
When powering on for the first time, after staying in the dynamic interface for 20 seconds, enter the following main interface according to the motherboard mode.
Status Icons
Icons | Status | Description | Icons | Status | Description |
Network status | Always on indicates networking | Defrosting | Unit currently operating defrost function | ||
Network status | Blinking display distribution network | Anti-frost | Unit is currently operating with anti-freeze function | ||
Hot water mode | Dynamically indicates power on | Holiday | Unit currently running in holiday mode | ||
Underfloor heating | Dynamically indicates power on | Quiet | The unit is currently running in silent mode | ||
Fault | Unit is faulty | Energy saving | The unit is currently running in energy saving mode | ||
Preheating | Blinking indicates preheating | Capacity test | Unit currently running capacity test | ||
Timer silence | The wire controller turns on the timed mute | Fluoride collection | Unit currently running fluoride collection function | ||
Timer function | The wire controller turns on the timed function | Antibacterial | Unit currently running sterilization function | ||
External heat source | External heat source output | Free electricity | |||
Solar signal | Solar signal input | Valley electricity | |||
Water tank electric heater | Water tank electric heater output | Peak electricity | |||
Auxiliary electric heater | Auxiliary electric heater output |
1.1.1. Single/Dual/Room Temperature Mixing Control
In the closed state, swipe left in the main interface - click "General" - click "Parameters" - enter the password "168" - click "N Parameters" - scroll to page 3 and click N26 to select single and dual zone modes. "2" represents dual zone, "0" represents single zone, "3" represents dual zone water temperature + room temperature mixed control of the line controller, and the main page of the single zone and dual zone wire controller is different. (The above operations need to be set when the online controller is turned off).
Dual-zone water temperature + room temperature mixing control page, in this mode, zone B is room temperature control, set temperature range: 16-30 degrees Celsius.
2.3.6. In-line controller lock/unlock function
On the main interface, press the "
Power on and off
1. When the unit is in the shutdown state, short press "
Setting Mode
At the main interface, short press "
For example, when the unit supports cooling and heating modes, short press the "
Setting Target Temperature
According to the main page display mode status setting, click on the target temperature to set the desired target temperature.
生活热水设置范围:30-75
Domestic hot water setting range: 30-75
制热温度设置范围:30-80
Heating temperature setting range: 30-80
制冷温度设置范围:5-30
Refrigeration temperature setting range: 5-30
Unit of Temp.温度单位设置
Unit of Temp
At the system parameter interface, press “
Each time the temperature unit is switched, the wire controller enters the read parameter interface and re-reads all the advanced parameters, returning to the setting interface after 20s.
语言设置
Language settings
At the system parameter interface, press “
Press "Switch Language" to switch the language.
时间设置
Time setting
At the setting interface, press “
定时设置
Timing settings
Timed ON/OFF Setting
At the setting interface, click "
The switch is turned on, and the week of the week is in red font, indicating that the timer time takes effect during that period
Silent mode
In the settings screen, press "
Mute Level
Mute Mode
Timer Mute
Press “
Mute setting end time
While the mute setting is valid, the background is green; While the mute setting is invalid, the background is gray.
Press MON~SUN to choose which day to be valid for the timer. The day will become red after pressing.
Note:If timed on time is equal to timed off time, the segment cannot take effect.
If timing is not on or the timing on week is not selected, the segment of timing cannot take effect.
If the timings are set to cross, the opening time or end time will be executed according to
版本查询
Version query
At the system parameter interface, press “
Fault record query
At the system parameter interface, press “
System diagram viewing
On the main interface, click
Query of electricity consumption
On the main interface, click
The in-line controller user parameters are entered
User Parameters page
Run the status parameter query
Enter the user parameters page: as shown below
Waterway emptying test run
Manual defrosting
Fluoride collection mode
Go to the steps
1. Enter the customer parameter setting interface; (See details here.)Customer Parameter Setting Interface").
2. Click on the "Refrigerant recovery" button
3. Enter the password "814".
The advanced parameters of the wire controller are entered
The output password is 589, and the parameter settings of T, N, M, O, etc. are mainly distributed meaning,
Parameter | Meaning | Parameter | Meaning |
Para.W | For Protection | Para.M | For Temperature |
Para.N | For Heat Pump System | Para.P | For Water Pump |
Para.F | For Fan | Para.G | For Sterilization |
Para.E | For Valves | Para.C | For Compressor |
Para.D | For Defrost |
Cooling/heating loading and unloading temperature differential setting
For advanced parameter description, find M69-M72 and set it
Built-in electric heating
Built-in electric heating refers to the electric heating of the pipes, which is used in all modes. You can find parameter M39 (Auxiliary Electric Heater) to select 0 Disable/1 Heating only/2 Hot water only/3 Heating & Hot water, 0 means not to use any auxiliary heat source, 1 to use in heating mode, 2 to use only in hot water mode, 3. It can be used in hot water or heating mode.
Introduction and setting of auxiliary heat source operation
Auxiliary heat source refers to an external heat source that is used in heating/hot water/heating + hot water mode. You can find the parameter M40 (External Heat Source) Select 0 Disable/1 Heating only/2 Hot water only/3 Heating & Hot water 0 means do not use any auxiliary heat source, 1 is used in heating mode, 2 can only be used in hot water mode, 3 can be used in hot water or heating mode. There is a system total outlet water temperature probe in the accessory for temperature detection with an auxiliary heat source, if you have it installed, please set it parameter N37 (System Total Outlet Water Temp. Sensor) 0 Disable/1 Enable, select 1, or 0 if you do not want to enable it.
Instructions for pump operation settings
The pump can be set to keep running and intermittent operation after temperature, you can select 0-Keep Running/ 1-Intermittent Operation in parameter P01 Water pump operation mode.
Introduction to the operation of the antifreeze function and activation of settings
Antifreeze temperature: parameter T78 in the board back water temperature, parameter T79 board out water temperature, parameter T80 total water temperature, parameter T06 Upper temperature of buffer tank, parameter T07 Lower temperature of buffer tank, parameter T08 Choose the lowest temperature between the underfloor heating inlet temperature as the "antifreeze temperature". The machine will judge whether the conditions for entering the anti-freezing are met according to the ambient temperature, the non-running time of the machine, and the anti-freezing temperature, and if all of them are met, it will enter the anti-freezing. After entering the anti-freezing, the external circulation pump starts to run, and after 180S, according to the anti-freezing time, ambient temperature, and anti-freezing temperature, it is judged whether the conditions for exiting the anti-freezing are met, and if one condition is met, the anti-freezing is withdrawn. You can choose whether to enable this feature in the parameter W11 Anti-Freeze Setting 0-disable 1-enable parameter.
Description of the climate curve setting
Explanation of the climate curve
The climate curve (high temperature climate curve, low temperature climate curve) of the unit has a corresponding outlet temperature in a specific temperature range, and the high temperature curve or low temperature curve can be selected according to the needs of customers.
After selecting one cooling or heating curve, the outlet water temperature of the unit will be consistent with the temperature set by the curve.
The custom curve of the unit can be set according to the customer's wishes, and the ambient temperature and the corresponding effluent temperature can be set by themselves, and the unit will operate according to a linear relationship.
Heating curve
Heating temperature profile
High temperature climate curves (8 lines), low temperature climate curves (8 lines).
The high and low temperature climate curves are as follows:
Heating Ring Temperature - Target Temperature Gauge (Unit: °C)
| ≤-20 | -19 | -18 | -17 | -16 | -15 | -14 | -13 | -12 | -11 | -10 | -9 | -8 | -7 | -6 | -5 | -4 | -3 | -2 | -1 | 0 |
| 38 | 38 | 38 | 38 | 38 | 37 | 37 | 37 | 37 | 37 | 37 | 36 | 36 | 36 | 36 | 36 | 36 | 35 | 35 | 35 | 35 |
| 37 | 37 | 37 | 37 | 37 | 36 | 36 | 36 | 36 | 36 | 36 | 35 | 35 | 35 | 35 | 35 | 35 | 34 | 34 | 34 | 34 |
| 36 | 36 | 36 | 35 | 35 | 35 | 35 | 35 | 35 | 34 | 34 | 34 | 34 | 34 | 34 | 33 | 33 | 33 | 33 | 33 | 33 |
| 35 | 35 | 35 | 34 | 34 | 34 | 34 | 34 | 34 | 33 | 33 | 33 | 33 | 33 | 33 | 32 | 32 | 32 | 32 | 32 | 32 |
| 34 | 34 | 34 | 33 | 33 | 33 | 33 | 33 | 33 | 32 | 32 | 32 | 32 | 32 | 32 | 31 | 31 | 31 | 31 | 31 | 31 |
| 32 | 32 | 32 | 32 | 31 | 31 | 31 | 31 | 31 | 31 | 31 | 31 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 29 |
| 31 | 31 | 31 | 31 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 29 | 29 | 29 | 29 | 29 | 29 | 29 | 29 | 28 |
| 29 | 29 | 29 | 29 | 28 | 28 | 28 | 28 | 28 | 28 | 28 | 28 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 27 | 26 |
| 55 | 55 | 55 | 55 | 54 | 54 | 54 | 54 | 54 | 54 | 54 | 54 | 53 | 53 | 53 | 53 | 53 | 53 | 53 | 53 | 52 |
| 53 | 53 | 53 | 53 | 52 | 52 | 52 | 52 | 52 | 52 | 52 | 52 | 51 | 51 | 51 | 51 | 51 | 51 | 51 | 51 | 50 |
| 52 | 52 | 52 | 52 | 51 | 51 | 51 | 51 | 51 | 51 | 51 | 51 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 49 |
| 50 | 50 | 50 | 50 | 49 | 49 | 49 | 49 | 49 | 49 | 49 | 49 | 48 | 48 | 48 | 48 | 48 | 48 | 48 | 48 | 47 |
| 48 | 48 | 48 | 48 | 47 | 47 | 47 | 47 | 47 | 47 | 47 | 47 | 46 | 46 | 46 | 46 | 46 | 46 | 46 | 46 | 45 |
| 45 | 45 | 45 | 45 | 44 | 44 | 44 | 44 | 44 | 44 | 44 | 44 | 43 | 43 | 43 | 43 | 43 | 43 | 43 | 43 | 42 |
| 43 | 43 | 43 | 43 | 42 | 42 | 42 | 42 | 42 | 42 | 42 | 42 | 41 | 41 | 41 | 41 | 41 | 41 | 41 | 41 | 40 |
| 40 | 40 | 40 | 40 | 39 | 39 | 39 | 39 | 39 | 39 | 39 | 39 | 38 | 38 | 38 | 38 | 38 | 38 | 38 | 38 | 37 |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | ≥20 | |
| 35 | 35 | 34 | 34 | 34 | 34 | 34 | 34 | 33 | 33 | 33 | 33 | 33 | 33 | 32 | 32 | 32 | 32 | 32 | 32 | |
| 34 | 34 | 33 | 33 | 33 | 33 | 33 | 33 | 32 | 32 | 32 | 32 | 32 | 32 | 31 | 31 | 31 | 31 | 31 | 31 | |
| 32 | 32 | 32 | 32 | 32 | 32 | 31 | 31 | 31 | 31 | 31 | 31 | 30 | 30 | 30 | 30 | 30 | 30 | 29 | 29 | |
| 31 | 31 | 31 | 31 | 31 | 31 | 30 | 30 | 30 | 30 | 30 | 30 | 29 | 29 | 29 | 29 | 29 | 29 | 28 | 28 | |
| 30 | 30 | 30 | 30 | 30 | 30 | 29 | 29 | 29 | 29 | 29 | 29 | 28 | 28 | 28 | 28 | 28 | 28 | 27 | 27 | |
| 29 | 29 | 29 | 29 | 29 | 29 | 28 | 28 | 28 | 28 | 28 | 28 | 27 | 27 | 27 | 27 | 27 | 27 | 26 | 26 | |
| 28 | 28 | 28 | 28 | 28 | 28 | 27 | 27 | 27 | 27 | 27 | 27 | 26 | 26 | 26 | 26 | 26 | 26 | 25 | 25 | |
| 26 | 26 | 26 | 26 | 26 | 26 | 26 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 24 | 24 | 24 | 24 | 24 | |
| 52 | 52 | 52 | 52 | 52 | 52 | 52 | 51 | 51 | 51 | 51 | 51 | 51 | 51 | 51 | 50 | 50 | 50 | 50 | 50 | |
| 50 | 50 | 50 | 50 | 50 | 50 | 50 | 49 | 49 | 49 | 49 | 49 | 49 | 49 | 49 | 48 | 48 | 48 | 48 | 48 | |
| 49 | 49 | 49 | 49 | 49 | 49 | 49 | 48 | 48 | 48 | 48 | 48 | 48 | 48 | 48 | 47 | 47 | 47 | 47 | 47 | |
| 47 | 47 | 47 | 47 | 47 | 47 | 47 | 46 | 46 | 46 | 46 | 46 | 46 | 46 | 46 | 45 | 45 | 45 | 45 | 45 | |
| 45 | 45 | 45 | 45 | 45 | 45 | 45 | 44 | 44 | 44 | 44 | 44 | 44 | 44 | 44 | 43 | 43 | 43 | 43 | 43 | |
| 42 | 42 | 42 | 42 | 42 | 42 | 42 | 41 | 41 | 41 | 41 | 41 | 41 | 41 | 41 | 40 | 40 | 40 | 40 | 40 | |
| 40 | 40 | 40 | 40 | 40 | 40 | 40 | 39 | 39 | 39 | 39 | 39 | 39 | 39 | 39 | 38 | 38 | 38 | 38 | 38 | |
| 37 | 37 | 37 | 37 | 37 | 37 | 37 | 36 | 36 | 36 | 36 | 36 | 36 | 36 | 36 | 35 | 35 | 35 | 35 | 35 |
Refrigeration curves
Refrigeration climate curve
High temperature climate curves (8 lines) and low temperature climate curves (8 lines).
The high and low temperature climate curves are as follows (°C):
Refrigeration Ring Temperature - Target Temperature Gauge (Unit: °C)
| -10≤TA<15 | 15≤TA<22 | 22≤TA<30 | 30≤TA |
| 16 | 11 | 8 | 5 |
| 17 | 12 | 9 | 6 |
| 18 | 13 | 10 | 7 |
| 19 | 14 | 11 | 8 |
| 20 | 15 | 12 | 9 |
| 21 | 16 | 13 | 10 |
| 22 | 17 | 14 | 11 |
| 23 | 18 | 15 | 12 |
| 20 | 18 | 17 | 16 |
| 21 | 19 | 18 | 17 |
| 22 | 20 | 19 | 17 |
| 23 | 21 | 19 | 18 |
| 24 | 21 | 20 | 18 |
| 24 | 22 | 20 | 19 |
| 25 | 22 | 21 | 19 |
| 25 | 23 | 21 | 20 |
Enable the climate curve
Customize curve settings
When the climate curve cannot meet the user's customization needs, the user can set the custom curve through the following methods:
Custom curve (curve 9): The corresponding curve temperature can be set according to the requirements (the end value of the ambient temperature exceeds the range);
The parameters of the refrigeration custom climate curve are as follows: refrigeration ring temperature 1, refrigeration temperature output temperature 1, refrigeration ring temperature 2, and refrigeration temperature 2 (the two points are calculated linearly, and the endpoint value is taken outside the two points, formula: y = kx +b);
Set the relevant customer parameters to M10-M21.
Curve 9 is a linear calculation as follows:
The refrigeration operation follows the following linear diagram:
Among them, Tenv_cl_max: MAX (parameters [M14], [M15]).
Tenv_cl_min: MIN (parameters [M14], [M15]).
TcS_end: MIN (parameters [M16], [M17]).
TcS_start: MAX (parameters [M16], [M17]).
The heating process follows the following linear diagram:
Among them, Tenv_ht_max: MAX ([M18], [M19]).
Tenv_ht_min: MIN(【M18】, 【M19】)
ThS_end: MIN(【M20】, 【M21】)
ThS_start: MAX(【M20】, 【M21】)
Inline controller settings:
Refrigeration curve settings
Parameters [M14], [M15], set the ambient temperature range of the refrigeration curve, parameters [M16] , [M17] sets the temperature range of the refrigeration effluent
Heating curve settings
Parameters [M18], [M19], set the ambient temperature range of the heating curve, parameters [M20], 【M21】Set the temperature range of the heating curve and the outlet water.
Scheduled sterilization run settings
Timing sterilization operation logic:
Prerequisites: Parameter N11 [Hot Water Function] needs to be set to be enabled, and parameter G01 [Timing Sterilization] to be enabled;
Parameter G02 [Sterilization Temperature]: 65°C by default
Parameter G03 [Sterilization Cycle]: 48 hours by default
Sterilization conditions: When the "sterilization time point" of the timed sterilization setting is reached or the sterilization is started in the holiday away mode, the unit will turn on the hot water sterilization;
The first stage: the unit turns on the hot water of the compression mechanism, the temperature of the water tank reaches the target temperature of the hot water, and the compressor is stopped to enter the second stage; If the compressor is in the state of hot water constant temperature shutdown, it will enter the second stage immediately;
The second stage: the unit turns on the auxiliary heat source sterilization and runs the sterilization at a regular time;
After the time set by the auxiliary heat source operation parameter G03 [sterilization cycle], the timed sterilization is withdrawn;
The temperature of the hot water tank THWt is in the high temperature range of sterilization, and the cumulative operating parameter G04 [high temperature time of sterilization] is withdrawn from the timed sterilization;
The temperature of the hot water tank THWt ≥ the sterilization temperature, and the auxiliary heat source is turned off; The temperature of the hot water tank THWt< the sterilization temperature is -2 °C, and the auxiliary heat source is turned on;
Note: 1) The electric heating of the water tank is enabled, and the auxiliary electric heating and external heat source are not turned on; The electric heating of the water tank is not activated, and the auxiliary electric heating or external heat source is turned on (the auxiliary electric heating and the external heat source cannot be enabled at the same time, otherwise it will not be turned on);
During the preheating/drying of floor heating, the timing sterilization function is not performed;
The buffer tank sensor is enabled
The position of the upper and lower sensors of the buffer tank sensor on the motherboard (A12) (A13) at the position of 26,35 on the motherboard (as shown below), after enabling the sensor, the corresponding sensor needs to be plugged in at the corresponding position of the motherboard. Then enter the advanced parameters on the line controller, the upper temperature probe of the N45 buffer water tank, and the lower temperature probe of the N46 buffer water tank to be enabled
The buffer tank sensor is enabled
Instructions for enabling the Solar Temperature Probe Control
If you are using a solar water heater in parallel with our machine, you will need to install the solar temperature probe in the accessory and enable parameter N22 (Solar) 0 Disable/1 Enableparameter N41 (Solar Temp. Sensor) 0 Disable/1 Enable, select 0 if not.
(as shown in the figure above) 30 position, the position on the motherboard (A14) needs to be plugged in with the corresponding sensor after the sensor is enabled. Then go to the advanced parameters on the controller
Solar water pump control
[Solar Temperature Probe] is set to "Disabled", and when a solar signal is detected and the temperature of the hot water tank is less than the set value minus the difference, the sun will be turned on
Turn off the solar pump until the solar signal is disconnected or the temperature of the hot water tank reaches the set value.
[Solar Temperature Probe] is set to "Use", when the solar temperature reaches the allowable opening temperature and the temperature of the hot water tank is less than the set value, the difference is reduced
Turn on the solar pump until the solar temperature is lower than the shutdown temperature or the hot water tank temperature reaches the set value, and turn off the solar pump.
The underfloor heating inlet water temperature sensor is enabled
When the wire controller selects dual zones and needs to install floor heating, you need to set the parameter N36 to 1 to use. At the same time, the sensor needs to be plugged in at the position of the motherboard (AI6C), as shown in the position of the motherboard 29 in the figure above. The operation of the wire controller is as follows
Instructions for the operation and setting of the underfloor heating preheating function
Prerequisites: Parameter N36 floor heating inlet water temperature probe activated
Prerequisites: Parameter N36 floor heating inlet water temperature probe activated.
Logic diagram of floor heating preheating:
F1: Parameter M55 [floor heating preheating interval], generally 30 minutes, can be adjusted and modified
F2: Warm-up shutdown duration, 5 minutes
Parameter M58 [Floor Heating Water Temperature Difference] 5 °C, Parameter M59 [Floor Heating Room Temperature Difference] 1 °C
Running logic description:
When preheating, the running time meets the F1 time, and the compressor stops; When the downtime time reaches F2, the compressor restarts;
Total effluent temperature≥ preheating target + unloading difference, stop the compressor; The total effluent temperature < the preheating target-energy loading difference, and the compressor is turned on
When the temperature of the local heating inlet water is ≥ the preheating target, the three-way valve 3 is closed, and the three-way valve 3 is ON output; When the temperature of the local heating inlet water is < the preheating target - parameter M58 [floor heating water temperature difference] or parameter M59 [floor heating room temperature temperature difference], open the three-way valve 3, and the three-way valve 3 is OFF output;
When the floor heating preheating time reaches [floor heating preheating duration] or manually turns off the floor heating preheating and exits the floor heating preheating;
Note: When the floor heating is preheated, the auxiliary heat source is not turned on, and the timer power on/off, holiday home mode, and holiday away from home mode are invalid
Floor heating preheating can be manually enabled by the online controller, and the user parameter settings can be accessed, and the opening method is as follows:
Meaning of parameter representation:
Underfloor heating preheating temperature (parameter M55): the target temperature of underfloor heating preheating, which is measured by the underfloor heating inlet water temperature probe. The value of this parameter can be modified
Underfloor heating preheating interval (parameter M56): The underfloor heating preheating operation interval, after which the compressor will be shut down for 10 minutes.
Floor heating preheating duration (parameter M57): The total duration of floor heating preheating operation, after the unit reaches the set duration, the floor heating preheating function will be turned off.
Current status: Click the status value to manually turn off or turn on the floor heating preheating function.
Instructions for the operation and setting of the floor heating drying function
Prerequisites: Parameter N36 [Floor Heating Inlet Water Temperature Probe] is activated;
Manually enable floor heating drying, the unit is forced to run the floor heating mode, the control temperature is the floor heating inlet temperature TFLin, the control target is the floor heating drying temperature and the current floor heating drying stage calculation value;
Floor heating drying is divided into three stages: before drying, during drying, and at the end of drying;
Manually turn off the floor heating drying or exit the floor heating drying when the last day of the floor heating drying tail is finished.
Note: When the floor heating is drying, the auxiliary heat source is not turned on, and the timer power on/off, holiday home mode, and holiday away from home mode are invalid.
Floor heating and drying function setting instructions: Enter the user parameter setting
Meaning of parameter representation:
Before floor heating drying (parameter M60): The time required for the completion of the first stage of floor heating drying, and the value unit is the number of days.
Floor heating drying (parameter M61): The time required to complete the second stage of floor heating drying, the value unit is days.
After floor heating drying (parameter M62): the time required for the completion of the third stage of floor heating drying, and the value unit is the number of days. At the end of this stage, the set drying target temperature value can be reached, and the floor heating drying is turned off after completion.
Floor heating drying temperature (parameter M63): the target temperature value of floor heating drying. In the final stage, when the set drying target temperature is reached, the underfloor heating drying function is switched off.
Start time: A certain point in time of the drying start date after the underfloor heating drying function is turned on.
Start Date: The date on which the drying starts after the underfloor heating drying function is turned on
Current Status: The current state of the underfloor heating function, which can be turned on or off.
Activation of the total effluent sensor
The probe is mounted on the water pipe after the outlet temperature of the heat pump unit and the outlet temperature of the auxiliary heat source to detect the total outlet temperature.
Enter the motherboard 32 in the picture above, the position of the motherboard (A15C), if enabled you need to plug in the sensor in the position, and then enter the advanced settings of the remote controller to enable. As shown in the figure below
Timing sterilization operation logic:
Prerequisites: Parameter N11 [Hot Water Function] needs to be set to be enabled, and parameter G01 [Timing Sterilization] to be enabled;
Parameter G02 [Sterilization Temperature]: 65°C by default
Parameter G03 [Sterilization Cycle]: 48 hours by default
Sterilization conditions: When the "sterilization time point" of the timed sterilization setting is reached or the sterilization is started in the holiday away mode, the unit will turn on the hot water sterilization;
The first stage: the unit turns on the hot water of the compression mechanism, the temperature of the water tank reaches the target temperature of the hot water, and the compressor is stopped to enter the second stage; If the compressor is in the state of hot water constant temperature shutdown, it will enter the second stage immediately;
The second stage: the unit turns on the auxiliary heat source sterilization and runs the sterilization at a regular time;
After the time set by the auxiliary heat source operation parameter G03 [sterilization cycle], the timed sterilization is withdrawn;
The temperature of the hot water tank THWt is in the high temperature range of sterilization, and the cumulative operating parameter G04 [high temperature time of sterilization] is withdrawn from the timed sterilization;
The temperature of the hot water tank THWt ≥ the sterilization temperature, and the auxiliary heat source is turned off; The temperature of the hot water tank THWt< the sterilization temperature is -2 °C, and the auxiliary heat source is turned on;
Note: 1) The electric heating of the water tank is enabled, and the auxiliary electric heating and external heat source are not turned on; The electric heating of the water tank is not activated, and the auxiliary electric heating or external heat source is turned on (the auxiliary electric heating and the external heat source cannot be enabled at the same time, otherwise it will not be turned on);
During the preheating/drying of floor heating, the timing sterilization function is not performed;
The enabling operation is shown in the following figure to enter the advanced parameter settings
Holiday mode is on
Holiday away from home mode
Set the start and end dates of the holiday away from home via the wire control During the holiday absence, the unit runs the heating/hot water production at a lower target water temperature,
To meet the needs of waterway anti-freezing and energy saving: if the unit has a regular sterilization function, the unit will only perform a sterilization on the last day of leaving home on the holiday.
When receiving the command to turn off the holiday away from home mode of the wire controller or the holiday away from home mode ends, the unit exits the holiday away from home mode and resumes normal operation.
*Holiday away from home mode and holiday home mode are mutually exclusive and cannot be run at the same time, and holiday away from home mode has a higher priority than holiday home mode
The hot water temperature and heating temperature of the holiday away from home need to enter the advanced parameters (M37 holiday away from home heating) and (M38 holiday away from home heating) to set.
Holiday at home mode
Set the start date, end date and timed period/mode of holiday home mode through the wire controller, and during the holiday home period, the unit will follow the set every day
Timing periods and modes to start and stop the crew at regular intervals.
When receiving the in-line controller holiday home mode shutdown command or holiday home mode ends, the unit exits holiday home mode and resumes normal operation.
*Holiday away from home mode and holiday home mode are mutually exclusive and cannot be run at the same time, and holiday away from home mode has a higher priority than holiday home mode
The smart grid function is turned on
N32 [Smart Grid Function] is set to "Use", and N01 [Power Mode] is set to "Automatic" to enable the smart grid function
Activation and control of the lower return pump
Prerequisite: [Lower Return Pump] is set to "Use"
[Next Return Pump Timing] is set to "Use":
When the time reaches the opening time point of the lower return pump set by the user, the lower return pump is turned on, and it will continue to run for a period of time and then shut down.
[Sterilization of the lower return pump] is set to "Use":
When the unit enters the timed sterilization and the temperature of the hot water tank reaches the sterilization temperature, the difference is reduced (if the unit does not have a water tank for electric heating, the temperature of the hot water tank only needs to be reached
58°C), turn on the lower return pump until the unit exits the regular sterilization or the lower return pump continues to run for a period of time and then turns off the lower return pump. Here's how to enable the settings,
The lower return pump function is turned on
The timing sterilization setting for the lower return pump is enabled
Enabling and disabling the hot water function
Go to the advanced parameter settings, advanced parameter N11, you can enable and disable the hot water function
Setting of the single mode of heat pump cooling/heating
Enter the advanced parameter setting, advanced parameter N02, you can set the cooling and heating functions of the heat pump
Cascade settings
Wiring operation, see the "cascade" interface in the electrical connection diagram, and connect the cascade A1 and B1 communication lines of each module in parallel under the power-off state, that is, A1 and Al, B1 and B1 of each module are connected one by one in order;
DIP operation: address DIP: see the schematic diagram of the electrical connection, in the state of power failure, set the address of each unit module, address 0 is the main module, address 1 is the No. 1 submodule, and so on, and the display screen and network monitoring only need to be connected to the main module.
Cascade DIP wiring diagram
3. Set the number of wire controller modules: enter the advanced parameter N60, change the number to the parameter N60 [number of modules] to the corresponding number of modules, and each module is set to "use" (the corresponding parameter is N64-N71), and the maximum number of cascades is 8.
4. Set the number of hot water modules after cascading:
Prerequisite: When N11 [Hot Water Function] is set to "Use" on the online controller interface, and [Number of Modules] >1, the number of modules that can participate in hot water production is determined by setting N82 [Number of Hot Water Modules];
When the number of hot water modules ≥ the number of modules, all modules can participate in hot water production; The address of the module that can participate in hot water production is: 0 ~ [number of hot water modules] -1.
Force the external heat source to turn on
Prerequisites: [System Total Outlet Water Temperature Probe] is set to "Use", and [External Heat Source] M40 is set to "Heating & Hot Water".
Force on external heat source: Go to Settings,
Forced water tank electric heating on and hot water mode
Prerequisites [Water Tank Electric Heating] N20 is set to "Use", enter the settings,
Forced auxiliary electric heating to be turned on
Prerequisites [Auxiliary Electric Heating] M39 is set to "Heating & Hot Water", and then enter the settings
Adjustment of power mode
Go to advanced parameter N01
Advanced parameter tables
|
|
|
Unit |
Range |
| ||||||||||||||||||||
N | Para.N |
| |||||||||||||||||||||||
N01 |
| Power mode | / | 0~3
|
| ||||||||||||||||||||
N02 |
| Air conditioner type | / | 0~2
|
| ||||||||||||||||||||
N03 |
| Refrigerant setting | / | 0~4 0R22/1R407C/2R410A/3R32/4R290 |
| ||||||||||||||||||||
N04 |
| Four-way valve setting | / | 0~1
|
| ||||||||||||||||||||
N05 |
| Wire control switch type | / | 0~1
|
| ||||||||||||||||||||
N06 |
| Unit start/stop control | / | 0~4
|
| ||||||||||||||||||||
N07 |
| Power down memory switch | / | 0~1
|
| ||||||||||||||||||||
N08 |
| Incoming self-start | / | 0~1
|
| ||||||||||||||||||||
N09 |
| Four-way valve open delay | S | -100~100 |
| ||||||||||||||||||||
N10 |
| Four-way valve off delay | S | -100~100 |
| ||||||||||||||||||||
N11 |
| Hot water function | / | 0~1
|
| ||||||||||||||||||||
N12 |
| Hot water return difference | ℃ | -20.0~20.0 |
| ||||||||||||||||||||
N13 |
| On crankshaft ring Temp. | ℃ | -10~20 |
| ||||||||||||||||||||
N14 |
| Off crankshaft ring Temp. | ℃ | -10~20 |
| ||||||||||||||||||||
N15 |
| Min. preheat power off | S | 0~48 |
| ||||||||||||||||||||
N16 |
| Max. Preheat Power Off | S | 0~96 |
| ||||||||||||||||||||
N17 |
| Min. Preheat Time | Min | 0~999 |
| ||||||||||||||||||||
N18 |
| Max. Preheat Time | Min | 0~999 |
| ||||||||||||||||||||
N19 |
| Hot water mode priority | / | 0~1 0禁止/1使用 | 设置为1-使用时,机组在工作时,会自动优先完成热水的制作。 | ||||||||||||||||||||
N20 | 水箱电热 | Tank electric heating | / | 0~1 0禁止/1使用 | 设置为1-使用时,可以手动打开机组水箱电加热器加热热水。一般在环境温度过低,机组能力不足,或者机组压缩机损坏不能工作时打开。 | ||||||||||||||||||||
N21 |
| Lower return pump | / | 0~1
|
| ||||||||||||||||||||
N22 |
| Solar | / | 0~1
|
| ||||||||||||||||||||
N23 |
| Linkage function setting | / | 0~5
|
| ||||||||||||||||||||
N24 |
| Inverter use setting | / | 0~1 0禁止/1使用 | 默认为1使用 | ||||||||||||||||||||
N25 | 温控器控制 | Thermostat control | / | 0~3 0禁止/1单区模式切换/2双区开关/3双区开关 | 默认为0,接入温控器后不修改设置。 | ||||||||||||||||||||
N26 | 线控器控制 | Wire controller control | / | 0~2
|
| ||||||||||||||||||||
N27 |
| Load correction amplitude | ℃ | 0~10 |
| ||||||||||||||||||||
N28 |
| Load correction time | Min | 0~120 |
| ||||||||||||||||||||
N29 |
| Chassis electric heating mode | / | 0~1
|
| ||||||||||||||||||||
N30 |
| Chassis electric heating ambient Temp. | ℃ | -50~50 |
| ||||||||||||||||||||
N31 |
| Start page type | / | 0~9999 | / | ||||||||||||||||||||
N32 |
| Smart grid function | / | 0~1
|
| ||||||||||||||||||||
N33 |
| Compressor low pressure value | / | 0~1 0常开/1常闭 | 默认1常闭 | ||||||||||||||||||||
N34 | 压机高压 | Compressor low pressure value | / | 0~1
|
| ||||||||||||||||||||
N35 |
| Water flow switch | / | 0~1
|
| ||||||||||||||||||||
N36 |
| Floor heating inlet Temp. probes | / | 0~1
|
| ||||||||||||||||||||
N37 |
| System total outlet water Temp. probe | / | 0~1
|
| ||||||||||||||||||||
N38 |
| EVU PV signal | / | 0~1
|
| ||||||||||||||||||||
N39 |
| SG grid signal | / | 0~1
|
| ||||||||||||||||||||
N40 |
| Temp. probe configuration | / | 0~3
|
| ||||||||||||||||||||
N41 |
| Solar Temp. sensor | / | 0~1
|
| ||||||||||||||||||||
N42 |
| J6 Pressure sensor type | / | ||||||||||||||||||||||
N43 |
| J6 Min. range | Bar | -10~10 |
| ||||||||||||||||||||
N44 |
| J6 Max. range | Bar | 0~100 | 默认20Bar, | ||||||||||||||||||||
N45 | 缓冲水箱上部温度探头 | Buffer tank upper Temp. sensor | / | 0~1 0禁止/1使用 | 用于检测缓冲水箱上部的温度,与参数N45 | ||||||||||||||||||||
N46 |
| Buffer tank lower Temp. sensor | / | 0~1
| |||||||||||||||||||||
N47 |
| Energy saving run time | Min | 0~999 | |||||||||||||||||||||
N48 |
| Zone A cooling end | / | 0~3
|
| ||||||||||||||||||||
N49 |
| Zone A heating end | / | 0~3
|
| ||||||||||||||||||||
N50 |
| Number of ends | / | 0~32 | |||||||||||||||||||||
N51 |
| End start address | / | 1~247 | |||||||||||||||||||||
N52 |
| Host on end | / | 0~1
| |||||||||||||||||||||
N53 |
| Host off end | / | 0~1 0禁用/1使用 | |||||||||||||||||||||
N54 | 末端开启主机 | Ends on host | / | 0~2
| |||||||||||||||||||||
N55 |
| Host-end mode setting | / | 0~3
| |||||||||||||||||||||
N56 |
| End point can be corrected | ℃ | 0~10 | |||||||||||||||||||||
N57 |
| Fluoride collection function setting | / | 0~1
| |||||||||||||||||||||
N58 |
| Fluorine collection main valve steps | P | 0~500 | |||||||||||||||||||||
N59 |
| Fluorine collection low pressure retardation | S | 0~500 | |||||||||||||||||||||
N60 | 模块个数 | Number of modules | / | 1~8 | |||||||||||||||||||||
N61 | BMS数据格式 | BMS data format | / | 0~3 [0]8N1/[1]8N2/[2]8O1/[3]8E1 | |||||||||||||||||||||
N62 |
| BMS baud rate | / | 0~5 [0]2400/[1]4800/[2]9600/[3]19200/[4]38400/[5]57600 | |||||||||||||||||||||
N63 | BMS通讯地址 | BMS communication address | / | 1~247 | |||||||||||||||||||||
N64 |
| 00# Module setting | / | 0~1
| |||||||||||||||||||||
N65 |
| 01# Module setting | / | 0~1
| |||||||||||||||||||||
N66 |
| 02# Module setting | / | 0~1
| |||||||||||||||||||||
N67 |
| 03# Module setting | / | 0~1
| |||||||||||||||||||||
N68 |
| 04# Module setting | / | 0~1
| |||||||||||||||||||||
N69 |
| 05# Module setting | / | 0~1
| |||||||||||||||||||||
N70 |
| 06#Module setting | / | 0~1
| |||||||||||||||||||||
N71 |
| 07#Module setting | / | 0~1
| |||||||||||||||||||||
N72 |
| Whether to enable cooling mode | / | 0~1
| |||||||||||||||||||||
N73 |
| Whether to enable heating mode | / | 0~1
| |||||||||||||||||||||
N74 |
| Pressure sensor configuration | / | 0~2
| |||||||||||||||||||||
N75 |
| J5 Min. range | bar | -10.0~10.0 | |||||||||||||||||||||
N76 |
| J5 Max. range | bar | 0.0~100.0 | |||||||||||||||||||||
N77 |
| Forced frequency reduction ratio | % | 0~100 | |||||||||||||||||||||
N78 |
| Forced frequency reduction cycle | S | 5~300 | |||||||||||||||||||||
N79 |
| Smart grid configuration | 0~1 | ||||||||||||||||||||||
N80 | 变频器初始化 | Inverter initialisation | 0~1(不保存) | ||||||||||||||||||||||
N81 | 系统维护初始化 | System maintenance initialisation | 0~1(不保存) | ||||||||||||||||||||||
N82 | 热水模块数 | Number of hot water modules | 1~8 | ||||||||||||||||||||||
M | 温度参数 | ||||||||||||||||||||||||
M01 | 制冷设定温度 | Cooling setting Temp. | ℃ | 15~35 | |||||||||||||||||||||
M02 | 制热设定温度 | Heating setting Temp. | ℃ | 0~85 | |||||||||||||||||||||
M03 | 热水设定温度 | Hot water setting Temp. | ℃ | 0~80 | |||||||||||||||||||||
M04 |
| Cooling setting room Temp. | ℃ | 16~30 |
| ||||||||||||||||||||
M05 |
| Heating setting room Temp. | ℃ | 16~30 |
| ||||||||||||||||||||
M06 |
| Cooling setting Temp.(B) | ℃ | ||||||||||||||||||||||
M07 |
| Cooling setting room Temp.(B) | ℃ | ||||||||||||||||||||||
M08 | 制热设定温度(B) | Heating setting Temp.(B) | ℃ | 40~60 | |||||||||||||||||||||
M09 | 制热设定室温(B) | Heating setting room Temp.(B) | ℃ | 16~30 | |||||||||||||||||||||
M10 |
| A zone cooling curve | / | 0~17
| |||||||||||||||||||||
M11 |
| A zone heating curve | / | 0~17
| |||||||||||||||||||||
M12 |
| B zone cooling curve | / | 0~17 0禁止/1低温曲线1/2低温曲线2/3低温曲线3/4低温曲线4/5低温曲线5/6低温曲线6/7低温曲线7/8低温曲线8/9高温曲线1/10高温曲线2/11高温曲线3/12高温曲线4/13高温曲线5/14高温曲线6/15高温曲线7/16高温曲线8/17曲线9 | |||||||||||||||||||||
M13 | B区制热曲线 | B zone heating curve | / | 0~17
| |||||||||||||||||||||
M14 |
| Curve 9 Cooling ambient Temp.1 | ℃ | -5~46 | |||||||||||||||||||||
M15 |
| Curve 9 Cooling ambient Temp. 2 | ℃ | -5~46 | |||||||||||||||||||||
M16 |
| Curve 9 Cooling outlet Temp. 1 | ℃ | 5~25 | |||||||||||||||||||||
M17 |
| Curve 9 Cooling outlet Temp. 2 | ℃ | 5~25 | |||||||||||||||||||||
M18 |
| Curve 9 Heating ambient Temp. 1 | ℃ | -25~35 | |||||||||||||||||||||
M19 |
| Curve 9 Heating ambient Temp.2 | ℃ | -25~35 | |||||||||||||||||||||
M20 |
| Curve 9 Heating outlet Temp.1 | ℃ | 25~65 | |||||||||||||||||||||
M21 | 曲线9制热出温2 | Curve 9 Heating outlet Temp.2 | ℃ | 25~65 | |||||||||||||||||||||
M22 | 制冷温度补偿 | Cooling Temp. compensation | ℃ | -10.0~10.0 | 制冷且非防冻运行,回水、出水温度的温度补偿。(温度探头采集不准确时使用) | ||||||||||||||||||||
M23 |
| Heating Temp. compensation | ℃ | -10.0~10.0 |
| ||||||||||||||||||||
M24 |
| Room Temp. return difference | ℃ | 1~10 |
| ||||||||||||||||||||
M25 | 制冷回温下限 | Return Temp. lower lim of cooling | ℃ | -10~35 |
| ||||||||||||||||||||
M26 |
| Return Temp. Upper lim of cooling | ℃ | -10~35 | 制冷模式目标温度上限。 | ||||||||||||||||||||
M27 | 制热回温下限 | Return Temp. lower lim of heating | ℃ | 0~80 | 制热模式目标温度下限。 | ||||||||||||||||||||
M28 | 制热回温上限 | Return Temp. Upper lim of heating | ℃ | 0~80 |
| ||||||||||||||||||||
M29 |
| Min. ambient Temp.of cooling | ℃ | -12~25 |
| ||||||||||||||||||||
M30 |
| Max. ambient Temp.of cooling | ℃ | 35~50 | 机组能够运行制冷功能的最高环境温度 | ||||||||||||||||||||
M31 | 制热最低环温 | Min. ambient Temp.of heating | ℃ | -26~15 |
| ||||||||||||||||||||
M32 |
| Max. ambient Temp.of heating | ℃ | 20~50 | 机组能够运行制热功能的最高环境温度 | ||||||||||||||||||||
M33 | 热水最低环温 | Min. ambient Temp.of hot water | ℃ | -26~5 | |||||||||||||||||||||
M34 | 热水最高环温 | Max.ambient Temp. of hot water | ℃ | 35~50 | |||||||||||||||||||||
M35 | 自动制冷最低环 | Min. ambient Temp.of automatic cooling | ℃ | 20~29 | |||||||||||||||||||||
M36 | 自动制热最高环 | Max. ambient Temp.of automatic cooling | ℃ | 10~17 | |||||||||||||||||||||
M37 |
| Holiday away from home heating | ℃ | 20~25 | |||||||||||||||||||||
M38 | 假日离家热水 | Holiday away from home hot water | ℃ | 20~25 | |||||||||||||||||||||
M39 |
| Auxiliary electric heater | / | 0~3
|
| ||||||||||||||||||||
M40 |
| External heat source | / | 0~3 0禁用/1仅制热/2仅热水/3制热&热水 | |||||||||||||||||||||
M41 | 辅热开启高温差 | Auxiliary heat on high differential | ℃ | 0~10 | |||||||||||||||||||||
M42 |
| Auxiliary heat on low differential | ℃ | 0~10 | |||||||||||||||||||||
M43 |
| Auxiliary electric heater set | / | 1~3 | |||||||||||||||||||||
M44 |
| Auxiliary heater on delay | Min | 15~120 | |||||||||||||||||||||
M45 | 辅助电热开环温 | Auxiliary electric heater on ambient Temp. | ℃ | -15~10 | |||||||||||||||||||||
M46 |
| Auxiliary electric heater open Temp. difference | ℃ | 2~10 | |||||||||||||||||||||
M47 | 水箱电热开启延 | Water tank electric heater open delay | Min | 60~240 | 热水模式时,压缩机开启后,水箱电加热器延迟开启时间。 | ||||||||||||||||||||
M48 | 水箱电热开环温 | Water tank electric heater on ambient Temp. | ℃ | -5~30 | |||||||||||||||||||||
M49 |
| External heat source on delay | Min | 15~120 | |||||||||||||||||||||
M50 |
| External heat source on Temp. difference | ℃ | 2~10 | |||||||||||||||||||||
M51 | 外部热源关温差 | External heat source off Temp. difference | ℃ | 0~5 | |||||||||||||||||||||
M52 | 外部热源开环温 | External heat source on ambient Temp. | ℃ | -15~10 | |||||||||||||||||||||
M53 | 制热水最大时长 | Hot water Max. time | Min | 10~600 | |||||||||||||||||||||
M54 |
| Hot water Min .time | Min | 10~600 | |||||||||||||||||||||
M55 |
| Floor heating preheating Temp. | ℃ | 25~35 | |||||||||||||||||||||
M56 | 地暖预热间隔 | Floor heating preheating interval | Min | 10~40 | |||||||||||||||||||||
M57 | 地暖预热时长 | Floor heating preheating duration | H | 48~96 | |||||||||||||||||||||
M58 |
| Floor heating water Temp. return | ℃ | 0~10 | |||||||||||||||||||||
M59 |
| Floor heating room Temp. return | ℃ | 0~10 | |||||||||||||||||||||
M60 | 地暖烘干前 | Floor heating before drying | DAY | 4~15 | |||||||||||||||||||||
M61 |
| Floor heating during drying | DAY | 3~7 | |||||||||||||||||||||
M62 | 地暖烘干后 | Floor heating after drying | DAY | 4~15 | |||||||||||||||||||||
M63 |
| Floor heating drying Temp. | ℃ | 30~55 | |||||||||||||||||||||
M64 |
| Solar hot water Temp. | ℃ | 40~80 | |||||||||||||||||||||
M65 |
| Solar hot water return difference | ℃ | 0~10 | |||||||||||||||||||||
M66 | 太阳能开启水温 | Solar on water Temp. | ℃ | 40~80 | |||||||||||||||||||||
M67 | 太阳能开启回差 | Solar on return | ℃ | 0~10 | |||||||||||||||||||||
C |
| ||||||||||||||||||||||||
C01 | 变频压机编码 | Inverter press code | / | 0~999 | |||||||||||||||||||||
C02 | 手动模式 | Manual mode | / | 0~1 0禁止/1使用 | |||||||||||||||||||||
C03 | 手动设定转速 | Manually set speed | rps | 0~300 | |||||||||||||||||||||
C04 |
| Anti-frequent start | S | 0~800 | |||||||||||||||||||||
C05 | 到温预降频 | Pre-frequency reduction at Temp. | rps | 0~20 | |||||||||||||||||||||
C06 |
| Drive speed lower limit | rps | 0~50 | |||||||||||||||||||||
C07 |
| Drive speed upper limit | rps | 10~300 | |||||||||||||||||||||
C08 | 制冷额定转速 | Cooling rated speed | rps | 35~80 | |||||||||||||||||||||
C09 |
| Heating rated speed | rps | 35~80 | |||||||||||||||||||||
C10 | 启动维持时间 | Start-up maintenance time | S | 60~900 | |||||||||||||||||||||
C11 | 高压限加偏差 | High pressure limit deviation | bar | -10.0~10.0 | |||||||||||||||||||||
C12 | 低压限加偏差 | Low pressure limit deviation | bar | -10.0~10.0 | |||||||||||||||||||||
C13 | 高压强卸偏差 | High-pressure strong discharge deviation | bar | -10.0~10.0 | |||||||||||||||||||||
C14 | 低压强卸偏差 | Low-pressure strong discharge deviation | bar | -10.0~10.0 | |||||||||||||||||||||
C15 | 低频运行最长时间 | Max. time of low frequency operation | Min | 15~500 | |||||||||||||||||||||
C16 | 强制回油时间 | Forced oil return time | S | 60~500 | |||||||||||||||||||||
C17 | 变频驱动地址 | Inverter drive address | / | 1~4 | |||||||||||||||||||||
C18 | 压机除霜转速 | Press defrost speed | rps | 40~100 | |||||||||||||||||||||
C19 | 压机启动转速 | Presser start speed | rps | 10~120 | |||||||||||||||||||||
C20 | 启动升频速率 | Start up frequency rate | rps | 1~60 | |||||||||||||||||||||
C21 | 运行升频速率 | Operating speed | rps | 1~60 | |||||||||||||||||||||
C22 | 除霜升频速率 | Defrost ramp rate | rps | 1~60 | |||||||||||||||||||||
C23 | 标准频率调整 | Standard frequency adjustment | rps | -30~30 | |||||||||||||||||||||
C24 | 启动升频间隔 | Start-up frequency interval | S | 1~200 | |||||||||||||||||||||
C25 | 调频比例带 | FM proportional band | / | 1~9000 | |||||||||||||||||||||
C26 | 调频积分时间 | FM integral time | / | 0~999 | |||||||||||||||||||||
C27 | 调频微分时间 | FM differentiation time | S | 0~900 | |||||||||||||||||||||
C28 | 调频动作周期 | FM action period | rps | 3~999 | |||||||||||||||||||||
C29 | 调频比例系数 | FM proportionality factor | / | 0.1~99.9 | |||||||||||||||||||||
C30 | 制冷冷凝上限 | Cooling condensing upper limit | ℃ | 30~120 | |||||||||||||||||||||
C31 | 制热冷凝上限 | Heating condensing upper limit | ℃ | 30~120 | |||||||||||||||||||||
C32 | 节能频率调整 | Energy saving frequency adjustment | rps | -30~30 | |||||||||||||||||||||
C33 | 制热蒸发下限 | Heating evaporation lower limit | ℃ | -50~50 | |||||||||||||||||||||
C34 | 额定维持时间 | Rated maintenance time | S | 0~900 | |||||||||||||||||||||
C35 | 强制降频排温 | Forced frequency reduction exhaust Temp. | ℃ | 80~150 | |||||||||||||||||||||
C36 | 回油运行频率 | Return oil running frequency | rps | 30~100 | |||||||||||||||||||||
C37 | 超静音最大转速 | Super silent Max. speed | rps | 40~100 | |||||||||||||||||||||
C38 | 强劲频率调整 | Powerful frequency adjustment | rps | -30~30 | |||||||||||||||||||||
C39 | 静音最大转速 | Silent Max. speed | rps | 40~100 | |||||||||||||||||||||
C40 | 回避频率范围 | Evasive frequency range | rps | 0~10 | |||||||||||||||||||||
C41 | 回避频率1 | Evasive frequency 1 | rps | 0~120 | |||||||||||||||||||||
C42 | 回避频率2 | Evasive Frequency 2 | rps | 0~120 | |||||||||||||||||||||
C43 | 回避频率3 | Evasion frequency 3 | rps | 0~120 | |||||||||||||||||||||
C44 | 回避频率4 | Evasion frequency 4 | rps | 0~120 | |||||||||||||||||||||
C45 | 压缩机启用维持转速 | Compressor start-up maintenance speed | rps | 10~120 | |||||||||||||||||||||
C46 | 低环启动维持转速 | Low ambient Temp. start-up maintenance speed | rps | 10~120 | |||||||||||||||||||||
G | |||||||||||||||||||||||||
G01 |
| Timed sterilization function | / | 0~1
| |||||||||||||||||||||
G02 |
| Sterilization Temp. | ℃ | 60~70 | |||||||||||||||||||||
G03 |
| Sterilization Max. cycle | Min | 90~300 | |||||||||||||||||||||
G04 |
| Sterilization high Temp. time | Min | 5~60 | |||||||||||||||||||||
F |
| ||||||||||||||||||||||||
F01 |
| Variable frequency fan setting | / | 0~5
| |||||||||||||||||||||
F02 |
| EC fan code | / | 0~999 | |||||||||||||||||||||
F03 |
| Cooling fan Max. | rpm | 0~2000 | |||||||||||||||||||||
F04 |
| Cooling fan Min. | rpm | 0~2000 | |||||||||||||||||||||
F05 |
| Energy-saving air speed adjustment | / | 0~2 | |||||||||||||||||||||
F06 |
| Variable frequency fan speed adjustment | / | 0~2
| |||||||||||||||||||||
F07 |
| Fan manual operation | rpm | 0~2000 | |||||||||||||||||||||
F08 |
| High wind module Temp. | ℃ | 60~150 | |||||||||||||||||||||
F09 |
| Cooling high wind ambient Temp. | ℃ | -30~60 | |||||||||||||||||||||
F10 |
| Cooling low wind ambient Temp. | ℃ | -30~60 | |||||||||||||||||||||
F11 |
| Heating high wind ambient Temp. | ℃ | -30~60 | |||||||||||||||||||||
F12 |
| Heating low wind ambient Temp. | ℃ | -30~60 | |||||||||||||||||||||
F13 |
| Cooling high wind condensing | ℃ | -30~60 | |||||||||||||||||||||
F14 |
| Cooling low wind condensing | ℃ | -30~60 | |||||||||||||||||||||
F15 |
| Heating high wind evaporation | ℃ | -30~60 | |||||||||||||||||||||
F16 |
| Heating low wind evaporation | ℃ | -30~60 | |||||||||||||||||||||
F17 |
| Air speed adjustment cycle | S | 0~100 | |||||||||||||||||||||
F18 |
| Air speed action ratio | % | 0~100 | |||||||||||||||||||||
F19 |
| Heating fan highest | rpm | 0~2000 | |||||||||||||||||||||
F20 |
| Heating fan lowest | rpm | 0~2000 | |||||||||||||||||||||
F21 |
| PWM fan pulse | / | 0~100 | |||||||||||||||||||||
F22 |
| Powerful wind speed adjustment | / | 0.00~2.00 | |||||||||||||||||||||
F23 |
| EC fan base site | / | 1~247 | |||||||||||||||||||||
F24 |
| Super quiet Max. wind speed | rpm | 500~900 | |||||||||||||||||||||
F25 |
| Number of variable frequency fans | / | 1~2 | |||||||||||||||||||||
F26 |
| Silent Max. wind speed | |||||||||||||||||||||||
F27 |
| PWM speed initial value | % | 0~100 | |||||||||||||||||||||
F28 |
| PWM speed coefficient | % | 1~999 | |||||||||||||||||||||
F29 |
| PWM speed interval | S | 1~20 | |||||||||||||||||||||
F30 |
| PWM speed deadband | / | 1~10 | |||||||||||||||||||||
F31 |
| Standard wind speed adjustment | / | 0.00~2.00 | |||||||||||||||||||||
F32 |
| Anti-cold wind function | / | 0~1
| |||||||||||||||||||||
F33 |
| Supply fan pause | S | 0~240 | |||||||||||||||||||||
F34 |
| Anti-cold air time | S | 0~60 | |||||||||||||||||||||
F35 |
| Frequency compensation coefficient | % | 1~300 | |||||||||||||||||||||
F36 |
| Correction factor lower limit | % | 1~100 | |||||||||||||||||||||
F37 |
| Standard wind speed adjustment | / | 0.00~2.00 | |||||||||||||||||||||
F38 |
| Exhaust air speed correction 2 | / | 0.00~2.00 | |||||||||||||||||||||
F39 |
| Exhaust air speed correction 3 | / | 0.00~2.00 | |||||||||||||||||||||
F40 |
| Discharge Temp. correction setting | / | 0~3
| |||||||||||||||||||||
F41 |
| Cooling stop wind Temp. difference | ℃ | 0~9999 | |||||||||||||||||||||
F42 |
| Heating stop air Temp. difference | ℃ | 0~9999 | |||||||||||||||||||||
F43 |
| Stop air return difference | ℃ | 0~60 | |||||||||||||||||||||
F44 |
| Medium wind Temp.(Heating) | |||||||||||||||||||||||
F45 |
| Medium wind Temp.(Cooling ) | |||||||||||||||||||||||
F46 |
| Fan medium speed(Cooling ) | |||||||||||||||||||||||
F47 |
| Fan medium speed(Heating) | |||||||||||||||||||||||
D |
| ||||||||||||||||||||||||
D01 |
| First defrost interval | Min | 0~255 | |||||||||||||||||||||
D02 |
| Defrost time | S | 90~1200 | |||||||||||||||||||||
D03 |
| Frost timing selection | / | 0~1
| |||||||||||||||||||||
D04 |
| Allowable defrost ambient Temp. | ℃ | 0~30 | |||||||||||||||||||||
D05 |
| Allowable defrost fin Temp. | ℃ | -20~10 | |||||||||||||||||||||
D06 |
| Defrost fin Temp. | ℃ | 0~30 | |||||||||||||||||||||
D07 |
| Exit defrost water discharge Temp. | ℃ | 0~60 | |||||||||||||||||||||
D08 |
| Fin ambient Temp. intelligent defrost | / | 0~1
| |||||||||||||||||||||
D09 |
| Moderate frost Temp. difference | ℃ | -30~30 | |||||||||||||||||||||
D10 |
| Heavy frost Temp. difference | ℃ | -30~30 | |||||||||||||||||||||
D11 |
| Temp. confirmation time | Min | 3~30 | |||||||||||||||||||||
D12 |
| Defrost ambient Temp.1 | ℃ | -20~15 | |||||||||||||||||||||
D13 |
| Defrost ambient Temp.2 | ℃ | -20~10 | |||||||||||||||||||||
D14 |
| Defrost ambient Temp.3 | ℃ | -20~10 | |||||||||||||||||||||
D15 |
| Defrost ambient Temp.4 | ℃ | -20~10 | |||||||||||||||||||||
D16 |
| Defrost interval 1 | Min | 0~255 | |||||||||||||||||||||
D17 |
| Defrost interval 2 | Min | 0~255 | |||||||||||||||||||||
D18 |
| Defrost interval 3 | Min | 0~255 | |||||||||||||||||||||
D19 |
| Defrost interval 4 | Min | 0~255 | |||||||||||||||||||||
D20 |
| Defrost interval 5 | Min | 0~255 | |||||||||||||||||||||
D21 |
| Difference between defrost fin Temp. and ambient Temp. 1 | ℃ | 0~20 | |||||||||||||||||||||
D22 |
| Difference between defrost fin Temp. and ambient Temp. 2 | ℃ | 0~20 | |||||||||||||||||||||
D23 |
| Difference between defrost fin Temp. and ambient Temp. 3 | ℃ | -10~20 | |||||||||||||||||||||
D24 |
| Difference between defrost fin Temp. and ambient Temp. 4 | ℃ | -10~20 | |||||||||||||||||||||
D25 |
| Difference between defrost fin Temp. and ambient Temp. 5 | ℃ | -10~20 | |||||||||||||||||||||
D26 |
| Low-pressure defrost setting | / | 0~1
| |||||||||||||||||||||
D27 |
| Low-pressure defrost detection delay | Min | 3~30 | |||||||||||||||||||||
D28 |
| Low-pressure defrost interval | Min | 5~60 | |||||||||||||||||||||
D29 |
| Low-pressure defrost fin Temp. | ℃ | -20~0 | |||||||||||||||||||||
D30 |
| Timed defrost interval | H | 0~18 | |||||||||||||||||||||
D31 |
| Emergency defrost fins ambient Temp. | ℃ | -30~50 | |||||||||||||||||||||
D32 |
| Defrost stop cut valve | / | 0~3
| |||||||||||||||||||||
D33 |
| Into defrost compressor delay | S | 0~255 | |||||||||||||||||||||
D34 |
| Into defrost four-way delay | S | 0~120 | |||||||||||||||||||||
D35 |
| Exit defrost compressor delay | S | 0~255 | |||||||||||||||||||||
D36 |
| Exit defrost four-way delay | S | 0~120 | |||||||||||||||||||||
D37 |
| Defrost cut valve frequency | rps | 20~100 | |||||||||||||||||||||
D38 |
| Time of drip after wind stop | S | 0~300 | |||||||||||||||||||||
D39 |
| Min. defrost interval | Min | 0~60 | |||||||||||||||||||||
D40 |
| Emergency defrost interval | Min | 0~255 | |||||||||||||||||||||
W |
| ||||||||||||||||||||||||
W01 |
| Anti-freeze interval 1 | Min | 0~100 | |||||||||||||||||||||
W02 |
| Anti-freeze interval 2 | Min | 0~100 | |||||||||||||||||||||
W03 |
| Water pump anti-freeze Temp. | ℃ | -10~20 | |||||||||||||||||||||
W04 |
| Electric heater anti-freeze Temp. | ℃ | -10~20 | |||||||||||||||||||||
W05 |
| Press machine anti-freeze Temp. | ℃ | -10~20 | |||||||||||||||||||||
W06 |
| Electrothermal antifreeze Temp. | ℃ | 5~20 | |||||||||||||||||||||
W07 |
| Compressor machine receding antifreeze Temp. | ℃ | 5~40 | |||||||||||||||||||||
W08 |
| Anti-freeze interval ring Temp. | ℃ | -10~20 | |||||||||||||||||||||
W09 |
| Into the antifreeze ring Temp. | ℃ | -10~20 | |||||||||||||||||||||
W10 |
| Retreat anti-freeze ring Temp. difference | ℃ | 0~10 | |||||||||||||||||||||
W11 |
| Anti-freeze function setting | / | 0~1
| |||||||||||||||||||||
W12 |
| Solar water pump anti-freeze | / | 0~1
| |||||||||||||||||||||
W13 |
| Open liquid injection valve exhaust Temp. | ℃ | 0~130 | |||||||||||||||||||||
W14 |
| Open liquid injection valve exhaust Temp. difference | ℃ | 0~30 | |||||||||||||||||||||
W15 |
| Wire controller communication detection |
| ||||||||||||||||||||||
W16 |
| Inverter fault self-reset | 0~2 | ||||||||||||||||||||||
P |
| ||||||||||||||||||||||||
P01 |
| Water pump operation mode | / | 0~2
| |||||||||||||||||||||
P02 |
| Inverter pump control | / | 1~4
| |||||||||||||||||||||
P03 |
| Water pump target speed | rpm | 1000~4500 | |||||||||||||||||||||
P04 |
| Inverter water pump manufacturers | / | 0~4 | |||||||||||||||||||||
P05 |
| Water pump target flow rate | undefined | 0~4500 | |||||||||||||||||||||
P06 |
| Lower return water pump operation | Min | 5~120 | |||||||||||||||||||||
P07 |
| Lower return pump sterilisation | / | 0~1
| |||||||||||||||||||||
P08 |
| Lower return pump timing | / | 0~1
|